10-
Operational settings of the refrigeration controller TAR 1309 (standard)
Changes to the settings of the refrigeration controller should only be performed by a
refrigeration specialist.
Depending on the unit type - normal cooling (GEKN) or deep-freezing (GEKT) -, the
controller is set with the parameter described below. Should you need to adjust these
settings, please observe the specified permitted operation parameters P05 and P06 for room
temperatures. Non-observance will lead to the loss of any warranty claims for the
refrigeration unit.
Parameter
Description
Operation setting for
unit type:
GEKN
GEKT
P01
Actual room temperature (control sensor)
°C
-- --
P02 Actual
evaporator
temperature (defrost
limitation sensor) °C
-- --
P03
Set value of room temperature
+ 5°C
- 18°C
P04
Room temperature difference
2 K
2 K
P05
Highest permitted room temperature
+ 12°C
- 5°C
P06
Lowest permitted room temperature
- 5°C
- 25°C
P07 Switching
behaviour of the compressor
relay
(1= Cooling)
1 1
P08
Display mode (1=°C, 2=°F)
1
1
P09
Sensor calibration T1 (room)
0 K
0 K
P10
Sensor calibration T2 (evaporator)
0 K
0 K
P11 Defrost
limitation
temperature 12°C
12°C
P12
Defrost mode (1=electrical)
1
1
P13
Defrost cycle
12 Std
1
6
Std
1
P14
Defrost time limitation
35 min.
35 min.
P15
Defrost delay after switching on the
distribution voltage
60 min.
60 min.
P16
Drip time of evaporator
3 min.
3 min.
P17
Set value for after-running of evaporator
fan
50°C 50°C
P18
Operation mode of evaporator fan
1
1
P19
Starting delay of evaporator fan
5 min.
5 min.
P20
upper alarm temperature (P03 +_K)
13°C
2
– 8°C
2
P21
Lower alarm temperature
- 6°C
- 30°C
P22
Delay time for alarm
90 min.
90 min.
P23
Alarm / Fan mode
0
0
P24
time left until defrost
--
--
P25
time left until defrost finish
--
--
P26
time left until compressor start
--
--
P27
time left until alarm
--
--
P28
Display of remaining time
--
--
P29 Manual
defrost
--
--
P30 Code
input
88 88
1) It is important to ensure that the evaporator does not ice up during operation.
The defrost times are to be set according to need and the corresponding requirements.
2)
Entry of the alarm temperature in °C. This does not automatically adjust to the set-point for room temperature (P03).
Содержание GEKN 1200