GUIDELINES FOR USING EXTENSION CORDS
t *GZPVBSFVTJOHBOFYUFOTJPODPSEPVUEPPSTCFTVSFJUJTNBSLFEXJUIUIFTVGmYi8"w i8wJO$BOBEBUPJOEJDBUF
that it is acceptable for outdoor use.
t #FTVSFZPVSFYUFOTJPODPSEJTQSPQFSMZXJSFEBOEJOHPPEFMFDUSJDBMDPOEJUJPO"MXBZTSFQMBDFBEBNBHFEFYUFOTJPO
cord or have it repaired by a qualified person before using it.
t 1SPUFDUZPVSFYUFOTJPODPSETGSPNTIBSQPCKFDUTFYDFTTJWFIFBUBOEEBNQPSXFUBSFBT
Recommended Minimum Wire Gauge for Extension Cords (120 Volt)
Nameplate
Amperes
(At Full Load)
Extension Cord Length
25 Feet
50 Feet
75 Feet
100 Feet
150 Feet
200 Feet
0–2.0
18
18
18
18
16
16
2.1–3.4
18
18
18
16
14
14
3.5–5.0
18
18
16
14
12
12
5.1–7.0
18
16
14
12
12
10
7.1–12.0
18
14
12
10
8
8
12.1–16.0
14
12
10
10
8
6
16.1–20.0
12
10
8
8
6
6
ELECTRIC MOTOR LOADS
It is characteristic of common electric motors in normal operation to draw up to six times their running current while
starting. This table may be used to estimate the watts required to start electric motors; however, if an electric motor fails
to start or reach running speed, turn off the appliance or tool immediately to avoid equipment damage. Always check the
requirements of the tool or appliance being used compared to the rated output of the generator.
NOTE:
Operating voltage and frequency requirement of all electronic equipment should be checked before plugging
them into this generator. It may damage the equipment if the equipment is not designed to operate within a +/- 10%
voltage variation, and +/- 3 Herz frequency variation from the generator name plate ratings. To avoid damage, always
have an additional load plugged into the generator if solid state equipment (such as a television set) is used. A power
line conditioner is recommended for some solid state applications.
GENERATOR CAPACITY
Make sure the generator can supply enough continuous (running) and surge (starting) watts for the items you will
power at the same time. Follow the step below to prevent overload.
t
Add up the total rated wattage of all electrical items to be connected at one time. This total should NOT be greater
than generator's rated running wattage.
MOTOR SIZE
RUNNING WATTS
WATTS REQUIRED TO START MOTOR
UNIVERSAL
CAPACITOR
SPLIT PHASE
1/8
275
N/A
850
1200
1/6
275
600
850
2050
1/4
400
800
1050
2400
1/3
450
950
1350
2700
1/2
600
1000
1800
3600
3/4
850
1200
2600
--
1
1100
N/A
3300
--