H-1-2. Cold
Ambient air temperature should be between 0
℃
and 40
℃
, the cooler the better.
H-1-3. Safe
Do not install in battery compartment or other areas
where flammable fumes may exist, such as fuel
storage are as or engine compartments.
H-1-4. Ventilated
Allow at least one inch of clearance around the
inverter for air flow. Ensure the ventilation openings
on the rear and bottom of the unit are not
obstructed.
H-1-5. Dust-free
Do not install the Inverter in a dusty environment where
either dust, wood particles or other filings/ shavings
are present. These can pulled into the unit when the
cooling fan is operating.
H-1-6. Close to battery/ batteries
Avoid excessive cable lengths but do not install the
Inverter in the same compartment as batteries. Also
do not mount the Inverter where it will be exposed to
the gases produced by the battery. These gases are
very corrosive and prolonged exposure will damage
the Inverter.
H-2. AC safety Grounding:
During the AC wiring installation, AC input and output
ground wires are connected to the inverter. The AC input
ground wire must connect to the incoming ground from
your AC utility source.
The AC output ground wire should go to the grounding
point for your loads (for example, a distribution panel
ground bus.)