Section I :: User
EN
Type supervisor : Rhoss Sequencer
Lon factor:
No
BMS table: #0
Set the port on the BMS protocol RHOSS, speed 19200, NONE parity
and 2 stop bits.
The serial addresses must be unique and must be assigned
consecutively (1-10) to the individual units sequenced.
For more information on using the on-board display of individual units
refer to the manual H57850 - Electronic controls.
ALARM
!
Prg
MODE
ON
OFF
ALARM
!
Prg
MODE
ON
OFF
The sequencer invitation parameters are displayed in the input/output
status menu, specifically:
If the system has been set on OFF from the Sequencer, the chiller
display shows the following screen
Display
Description
Virt. probe
Value of the virtual adjustment probe
Virt. set
System set point
Virt. band
Unit proportional band calculated by RMST
Enter the Configuration menu BMS.
In I01a mask set:
Z-Power / Y-Power / Y-Flow EXP / EXP range