It allows the automatic variation of the machine work Set point according
to a current external signal (4-20mA).
In particular, a value determined by the 4-20mA input is added to or
subtracted from the machine setpoint.
It allows the automatic variation of the machine work Set point according
to a current external signal (4-20mA).
In particular, the machine setpoint is not considered in favour of the
value defined by the input 4-20mA.
Regulation in both heat and cool mode is as follows:
Regulation in both heat and cool mode is as follows:
Offset set point
Shifting set point
Display
Description
Sum/Win by DIN
Season change from digital inputq
Double set by DIN
Set point change from digital input
Double set
(recovery) by DIN
Set point change from digital input (recovery side)
Recover by DIN
Recovery consent from sequencer digital input
MIN
MAX
4
20
mA
MIN
MAX
4
20
mA
Example:
if the
set cool
is 12°C and MIN=2 and MAX=4 then the set can range within 14
and 16°C.
if the
set cool
is 12°C and MIN= -2 and MAX=2 then the set can range within
10 and 14°C.
Example:
if MIN=9 and MAX=14 then the set can range within 9 and 14°C.
Defining the unit activation sequence
If rotation type:USER is set, the following screens are displayed:
Activation sequence defined by the user. Unit 2 will always activate
before unit 1.
Activation sequence defined by the user. Unit 2 will always activate
before unit 1.
The
Set point
menu allows specifying the sequencer adjustment
temperature.
When you enter Clock/Time
Set point menu
Menu Clock/Time bands
Press
ENTER
to access the menu; press the button again to move
between the summer and winter set temperature fields, as well as the
adjustment band.
You can set the system time is to enable the time-band operation.