Drain hose outlet from indoor unit can be manage in 3 style ::rear ,left and right of the indoor unit 

 

Tighten both fare nuts into gas pipe and liquid pipe at the indoor unit with two holding spanners. 

5. Condense drain 

 

Be sure the unit reasonably level and pitched toward the drain to ensure proper grange. 

 

Piping material 
(a)

 

oft Vinyl chloride  Pipe  22 MM. Nominal pipe size. 

(b)

 

Hard Vinyl chloride  (PVC)   Coupling 22  mm. Nominal pipe size. 

 

Connect  the soft/hard vinyl chloride pipe to the  coupling, see fig.8 

 

The indoor unit uses gravity to drain: Therefore the piping outside the unit should slope downward. 

 

“IMPORTANT “ Avoid draining as shown in fig.  9. 

 
 
 
 
 
 
 
 
 
 
 
 

6.  Refrigerant piping 

 

Connections to the indoor unit are flared connection. 
1.  Make flared joints for both suction and liquid lines. 
2.  Ensure tube and fittings are in line with one another before tightening nut to provide concentric 
 seating of tube on prevent leakage. 

 

Brazing should be performed with a constant purge of nitrogen trough the piping. This to 
Keep inside of tube clean. 

 

Insulate suction and liquid and liquid line separately to prevent sweating. 

FIG 8 

FIG 9 

PIPE PREPARATION                            

 

-PIPE & ELECTRICAL WIRE CUTTING

 

* Use cutting tools easily found in the market. 
* Measure precisely both outer & inner pipe. 
* Provide Alltel bit longer pipe than the measurement. 
* Wire must be 1.5 m. longer than the refrigerant tube. 
 
      -REAMING 
* Clean inside of the inner refrigerant tube. 
* While reaming, the tube end must be on the top

 

  of the reamer to prevent any dust going back into 
  the tube. 
 
       -FLARING THE PIPE FND 
* Flare both ends of the pipe with flaring kit by 
  fitting the flare nut on the pipe before flaring. 
  Set the die on the pipe so that pipe end is 
  0.5 mm. Above top of the die .Check if the pipe 
  end is even and perfectly round. 
 

 

-

 WIRE CONNECTION AND TAPE COVERING 

(See the picture on the right hand side) 

 
 
 
 
 

Cutting Tool

Rough Cut

Right

Sloped Cut

Wrong

Refrigerant Tube

Reamer

Up side

down position

 Uneven

Thickness

Cracked

Poor

Skin

Uneven

 Slope

Low Pressure Refrigerant Tube

30-40 mm.

To Indoor Unit

To Outdoor Unit