The  water  heater  must  be  installed  with  a  3”/5”  diameter  UL  approved  Category  III  Concentric  Stainless  

Steel  appliance  concentric  vent  pipe  or  Rheem  approved  concentric  vent  pipe.

Venting

The  installation  of  venting  must  comply    

with  national  codes,  local  codes  and  the    

vent  manufacturer’s  instructions.
The  water  heater  must  be  vented  to  the  

outdoors  as  described  in  these  instructions.  

DO  NOT

  connect  this  water  heater  to  a  

chimney.  It  must  be  vented  separately  from  

all  other  appliances.
All  concentric  vent  components  (adapters,  

pipe,  elbows,  terminals,  etc.)  should  be  

Rheem  approved  Stainless  Steel  Venting  

Material    

(e.g.  AL29-­4C).
The  specified  vent  termination  must  be  used.  

  

(Refer  to  pages  13  and  14  for  an  example  of  

the  concentric  vent.)
Use  the  screws  provided  to  connect  

the  concentric  vent  pipe  with  the  anti-­

disconnection  joint.
The  unit  can  be  vented  either  horizontally    

or  vertically.
Concentric  vent  pipe  runs  must  be  

adequately  supported  along  both  horizontal  

and  vertical  runs.
The  maximum  recommended  unsupported  

span  should  be  no  more  than  five  (5)  feet  

(1.5  m).  Support  isolation  hanging  bands  

should  be  used.  

DO  NOT

  use  wire.  (See  

diagram)

Notes  on  pre-­existing  vent:

If  the  water  heater  is  being  installed  as  a  

replacement  for  an  existing  water  heater,  a  

thorough  inspection  of  the  existing  venting  

and  air  intake  system  must  be  performed  

prior  to  any  installation  work.  Verify  that  the  

correct  materials,  vent  lengths  and  terminal  

locations  as  detailed  in  this  Use  and  Care  

Manual  have  been  met.  Carefully  inspect  the  

entire  venting  and  air  intake  system  for  any  

signs  of  cracks  or  fractures,  particularly  at  

the  joints  between  elbows  or  other  fittings  

and  the  straight  runs  of  vent  pipe.  Check  the  

system  for  signs  of  sagging  or  other  stresses  

in  the  joints  as  a  result  of  misalignment  of  

any  components  in  the  system.  If  any  of  

these

 

conditions  are  found,  they  must  be  

corrected  in  accordance  with  the  venting  

instructions  in  this  manual  before  completing  

the  installation  and  putting  the  water  heater  

into  service.

See  the  back  page  of  this  manual  

for  additional  requirements  for  the  

Commonwealth  of  Massachusetts.

DANGER:  Failure  to  

install  the  appliance  vent  

adapter  and  properly  vent  the  

water  heater  to  the  outdoors  

as  outlined  in  the  Venting  

section  of  this  manual  will  

result  in  unsafe  operation  of  

the  water  heater,  causing  death,  

serious  injury,  explosion,    

or  fire.  To  avoid  the  risk    

of  fire,  explosion,  or  

asphyxiation  from  carbon  

monoxide,  NEVER  operate  the  

water  heater  unless  it  is  

properly  vented  and  has  

adequate  air  supply  for  proper  

operation  as  outlined  in  the  

Venting  section  of  this  manual.

WARNING:  Use  only  3”/5”  

UL  approved  Category  III  

Concentric  Stainless  Steel  vent  

material  or  Rheem  approved  

concentric  vent  material.  No  

other  vent  material  is  

permitted.

WARNING:  Follow  

concentric  vent  

manufacturer’s  installation  

instructions  and  their  

recommended  clearances  to  

combustibles.

NO!

YES!

Venting  Lengths

MAXIMUM  VENT  LENGTH:

  

The  system  will  not  operate  if  there  is  

excessive  restriction  (pressure  drop)  in  the  

venting  system.  A  maximum  39’(12.0  m)  of  

vent  pipe  may  be  used  provided  there  is  only  

one  90°  elbow  in  the  system.  If  additional  

elbows  are  required:  two  elbows  can  be  used  

with  37’  6"(11.5  m),  three  elbows  can  be  used  

with  36’    (11.0  m)  or  four  elbows  can  be  used  

with  34’  6"  (10.5  m)  of  vent  pipe.  (See  table)

A  94°  elbow  is  equivalent  to  1’6”  (.5  m)  of  

straight  pipe.  A  45°  elbow  is  equivalent  to  

9”  (.25  m)  of  straight  pipe.

The  vent  termination  does  not  count  

in  equivalent  to  pipe  calculation  when  

determining  total  vent  lengths.  

The  vent  should  be  installed  with  a  slight  

downward  slope  of  1/4”  per  foot  of  

horizontal  run  toward  the  vent  terminal  (see  

diagram).  This  ensures  that  any  condensate  

formed  during  operation  of  the  unit  is  

evacuated  from  the  appliance  and  to  prevent  

rain  from  entering  the  appliance.

An  upward  slope  toward  the  vent  terminal  is  

not  acceptable  for  horizontal  venting  without  

installing  the  drain  tube  to  the  condensation  

trap.    For  horizontal  installation  with  less  

than  10’  (3.1m),  a  94°  elbow  is  required.  

MINIMUM  VENT  LENGTH

:  The  venting  

may  be  as  short  as  12”  (30cm),  in  addition  

to  installation  of  one  94°  elbow  and  one  

vent  termination  to  the  outdoors  through  a  

side  wall  (Total  equivalent  vent  length:  30”  

(76cm)).

Notice:

  Make  sure  that  the  seam  of  the  inner  

vent  pipe  in  horizontal  runs  is  toward  the  top  

of  the  installation  (see  diagram).

Vent Seam

Number  of  

90°  elbows  

(bends)

Maximum  

Length  of  

Straight  Pipe

1

39’

(12.0  m)

2

37'  6"

(11.5  m)

3

36"

(11.0  m)

4

34'  6"

(10.5  m)

5

33'

(10.0  m)

6

31'6"

(9.5  m)

9

AP15317 (10_09)  DV Gas Manual 10 30 09.indd   9

11/9/2009   3:10:25 PM

Содержание Ruud GT--200 DV N

Страница 1: ...ng of the water heater This manual also includes a parts list It is very important that all persons who are expected to install operate or adjust this water heater read the instructions carefully so they may understand how to perform these operations If you don t understand these instructions or any terms within it seek professional advice Any questions regarding the operation maintenance service ...

Страница 2: ...ater You ll find many answers to common problems in the Troubleshooting Guide If you review the chart of Troubleshooting Tips first you may not need to call for service READ THIS MANUAL Your safety and the safety of others are very important There are many important safety messages in this manual and on your appliance Always read and obey all safety messages This is the safety alert symbol Recogni...

Страница 3: ...e but are not limited to adhesives solvents paint thinners etc and the vapors they produce are extremely dangerous DO NOT handle use or store gasoline or other flammable or combustible materials anywhere near or in the vicinity of a water heater or any other appliance Be sure to read and follow the labels on the water heater as well as the warnings printed in this manual Failure to do so can resul...

Страница 4: ...r USC2 117 remote control Only qualified service personnel should perform this adjustment Only factory authorized remote control s should be used Notice When this water heater is supplying general purpose hot water requirements for use by individuals a thermostatically controlled mixing valve for reducing point of use water temperature is recommended to reduce the risk of scald injury Contact a li...

Страница 5: ...reat caution It is heavier than air and will collect first in lower areas making it hard to detect at nose level Before attempting to light the water heater make sure to look and smell for gas leaks Use a soapy solution to check all gas fittings and connections Bubbling at a connection indicates a leak that must be corrected When smelling to detect a gas leak be sure to sniff near the floor also G...

Страница 6: ...y greater than 52 gallons or tankless style consult the local building jurisdiction code for acceptable bracing procedures Have the installer show you the location of the gas shut off valve and how to shut it off if necessary Turn off the manual shut off valve if the water heater has been subjected to overheating fire flood physical damage or if the gas supply fails to shut off Read this manual en...

Страница 7: ...al to the vent termination to minimize vent length and the number of elbows required for venting The water heater should be installed with the proper venting materials and termination suitable for Category III venting or Rheem approved venting A fire stop plate should be installed at every penetration of a floor or ceiling if the vent is not running in a fire rated shaft Failure to install and pro...

Страница 8: ...is manual is twofold one to provide the installer with the basic directions and recommendations for the proper installation and adjustment of the water heater and two to the owner operator to explain the features operation safety precautions maintenance and troubleshooting of the water heater This manual also includes a parts list It is imperative that all persons who are expected to install opera...

Страница 9: ... vent the water heater to the outdoors as outlined in the Venting section of this manual will result in unsafe operation of the water heater causing death serious injury explosion or fire To avoid the risk of fire explosion or asphyxiation from carbon monoxide NEVER operate the water heater unless it is properly vented and has adequate air supply for proper operation as outlined in the Venting sec...

Страница 10: ... plumb the hose to a sanitary sewer drain See Examples A and B on pages 13 and 14 for DOWNWARD and UPWARD slope for horizontally vented water heaters When a water heater is vented vertically an UPWARD slope must always be used See the diagram on page 14 showing UPWARD slope for vertically vented water heaters Always attach a drain hose to the drain fitting and plumb the hose to a sanitary sewer dr...

Страница 11: ... cm for appliances 10 000 Btuh 3 kW 12 inches 30 cm for appliances 10 000 Btuh 3kW and 100 000 Btuh 30kW 36 inches 91 cm for appliances 100 000 Btuh 30kW 6 inches 15 cm for appliances 10 000 Btuh 3 kW 9 inches 23 cm for appliances 10 000 Btuh 3kW and 50 000 Btuh 15kW 12 inches 30 cm for appliances 50 000 Btuh 15kW K Clearance to mechanical air supply inlet 6 feet 1 83 m 3 feet 91 cm above if withi...

Страница 12: ...eople and pets Indoor Water Heater 12 WARNING Moisture in the flue gas will condense as it leaves the vent terminal In cold weather this condensate can freeze on the exterior wall under the eaves and on surrounding objects Some discoloration to the exterior of the building is to be expected However improper location or installation can result in severe damage to the structure or exterior finish of...

Страница 13: ... location If the heater is below the vent exit remove it from the wall and place it in a safe area while the vent opening is made Create a 6 diameter hole to allow the vent to pass without deformation or resistance Clean debris from the opening and hang the heater and secure all four mounting screws Dry fit the entire vent system from the heater to the vent termination including the wall plates Ma...

Страница 14: ...Firestop Support Plate Adjustable Roof Flashing Concentric Vent Pipe has 0 Clearance Requirment Storm Collar Support Clamp 1 4 per foot upward slope on horizontal run Vertical Termination Air Intake 3 5 Concentric Pipe Condensate Drain Line Form a Trap in the drain line To Drain Dispose of condensate in accordance to local codes Support Hanger Vertical Vent Installation with Horizontal offset Stra...

Страница 15: ...the water heater requires the minimum water pressure of 14 psi 97 kPa and a minimum water flow rate of 0 66 gpm 2 5 lpm A water pressure of 40 psi 276 kPa is required to achieve maximum flow rate To maintain proper performance ensure sufficient water supply pressure The Required Water Pressure Min Operating Water Pressure 14 psi 97 kPa Pipe Pressure Loss Faucet and Shower Pressure Loss Safety Marg...

Страница 16: ...ter and the water shutoff valve if either a thermal expansion tank or a backflow prevention device is not installed The following should be addressed in regards to the HOT WATER OUTLET Connections between the water heater and point s of use should be as short and direct as possible Local codes shall govern the exact type of pipe material to be used for water connections To conserve energy and mini...

Страница 17: ...ine Notice Local codes govern the installation of relief valves If local codes require that a temperature and pressure relief valve should be installed the manufacturer recommends a type 40XL Watts T P relief valve or an equivalent model be used Notice Manual operation of relief valves should be performed at least once a year Turn off the electrical power and gas shutoff valve Lift and release lev...

Страница 18: ...Do not use excessive force over 31 5 ft lbs 42 7 Nm in tightening the pipe particularly if teflon pipe compound is used as the unit may be damaged The inlet gas pressure to the water heater must not exceed 10 5 w c 2 6 kPa for natural or 14 w c 3 5 kPa for LP gas For purposes of input adjustment the minimum inlet gas pressure with main burner on is shown on the water heater rating plate If high or...

Страница 19: ...ctrical grounding must comply with local codes or in the absence of local codes with the latest edition of the National Electrical Code ANSI NFPA 70 or in Canada Canadian Electrical Code CSA C22 1 Part 1 F PRIORITY POWER ON OFF MAIN Control Base Plate Control screw Mounting Screw x 2 19 NOTICE If a manifold system is installed the main remote control connected to the manifold controller has priori...

Страница 20: ...Ensure the projections in the base plate fit into the housings in the remote control Fix the control to the base plate at the bottom of the remote control using the screw provided Proceed to Connecting the remote control to the water heater to complete installation Connecting the remote control to the water heater Ensure that the power to the water heater has been disconnected Loose the 1 screw lo...

Страница 21: ...RANGE CODE DE COULEUR COLOR CODE MIN BUTTON BOUTON MIN G YorG W BOUTON MAX BL BL BL LED G G MAX BUTTON ADJUSTER BUTTON BL BOUTON DE RÉGLAGE BL 1 2 3 4 5 A FOR INDOOR DIRECT VENT MODEL ONLY POUR MODÈLE INTÉRIEUR À ÉVENT DIRECT SEULEMENT 4 3 2 1 Y W R BK BL W BL R O Y FOR DIRECT VENT MODEL ONLY POUR MODÈLE À ÉVENT DIRECT SEULEMENT SW3 SW2 SW1 U 2 1 S 1 3 2 W W 1 2 3 4 I J H F W W 2 3 4 1 B R Y O W B...

Страница 22: ...ondensate Drain Line to Suitable Drain NOTICE The National Fuel Gas Code NFGC and B149 mandates a manual gas shut off valve See NFGC B149 for complete instructions Local codes or plumbing authority requirements may vary from the instructions or diagrams provided and take precedent over these instructions Vacuum Relief Valve Not Supplied If required install per local codes and valve manufacturer s ...

Страница 23: ... heater does not store water making an insulation blanket unnecessary The manufacturer s warranty does not cover any damage or defect caused by installation attachment or use of any type of energy saving or other unapproved devices other than those authorized by the manufacturer into onto or in conjunction with the water heater The use of unauthorized energy saving devices may shorten the life of ...

Страница 24: ...e is sufficient for the water heater Gas line equipped with shut off valve union and sediment trap Approved pipe joint compound used Soap and water solution used to check all connections and fittings for possible gas leak Gas Company inspected installation if required D Relief Valve Pressure Relief Valve properly installed and discharge line run to open drain Discharge line protected from freezing...

Страница 25: ...power to the appliance 3 Do not attempt to light the burner by hand 4 Turn the Gas Shutoff Valve located on the outside of the unit clockwise to the OFF position 5 Wait five 5 minutes to clear out any gas If you then smell gas STOP Follow B in the safety information above on this label If you don t smell gas go to the next step 6 Turn the Gas Shutoff Valve located on the outside of the unit counte...

Страница 26: ...s any difficulty in understanding or following the Operating Instructions or the Care and Cleaning section it is recommended that a qualified person or serviceman perform the work Operating the water heater DANGER There is a hot water scald potential if the temperature is set too high Households with small children disabled or elderly persons may require a 120 F 49 C or lower temperature setting t...

Страница 27: ...es the risk of scald injury Always supervise young children or others who are incapacitated The water heater is equipped with a device that will shut off the gas supply to the burner if the water heater exceeds normal operating temperatures Refer to the Before You Call For Service section located near the back of this manual or contact your dealer WARNING Should overheating occur or the gas supply...

Страница 28: ...periodically this may be due to a problem in the water system Contact the water supplier or your plumbing contractor on how to correct this DO NOT plug the relief valve outlet Rapid closing of faucets or solenoid valves in automatic water using appliances can cause a banging noise heard in a water pipe Strategically located risers in the water pipe system or water hammer arresting devices can be u...

Страница 29: ...glass If any unusual burner operation is noted the water heater should be shut off until qualified service assistance can be obtained CAUTION For your safety burner inspection and cleaning should be performed only by qualified service personnel For cleaning a vacuum cleaner can be used on the burner If the water heater is to remain idle for an extended period of time the power and water to the app...

Страница 30: ...enting system or from installation in areas exposed to cold air The water heater is equipped with a Freeze Protection Electric Heater As long as electricity is supplied to the water heater it prevents freezing inside the water heater down to an ambient temperature of approximately minus 30 F 34 C without wind conditions This device only protects the internal components of the water heater It does ...

Страница 31: ...e Check and replace if necessary Error code displayed on remote control See instructions for Error Code and if required contact a dealer for service Not enough water demand Increase water flow Water inlet filter clogged Clean water inlet filter Fixture aerator is clogged Clean aerator Scale buildup in heat exchanger Check for error code If required contact a dealer for service Hot and cold water l...

Страница 32: ...o qualified service personnel CAUTION Make certain power to water heater is OFF before removing protective cover FOR ANY REASON CAUTION Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation VERIFY PROPER OPERATION AFTER SERVICING 32 Error Code Possible Cause What To Do 11 The Gas Shutoff Valve is not opened completely Open the Gas S...

Страница 33: ...ent connectors or other safety devices Refer repairs to qualified service personnel WARNING For your safety DO NOT attempt to disassemble this unit for any reason Front View Unit Cover View Side View Heat Transfer Pipe Heat Exchanger Assy Electrode Ignitor Gas Valve Assy Gas Supply Cold Water Supply Water Flow Solenoid Drain Plug Circuit Board Blower Motor Flame Rod Film Type OHL Hot Water Outlet ...

Страница 34: ...d the Down button on the remote control for more than 5 seconds Number on the display of the remote control will begin to blink While the number is blinking push the Down arrow temperature adjustment button and the UP arrow temperature adjustment button at the same time Number of the display of the remote control will stop blinking Push the UP or Down button to set desired temperature Turn on the ...

Страница 35: ...e water heater is installed less than 3 280 feet 1 000m no action is required How to adjust the DIP switch on the PCB for high altitude installation Check the altitude above sea level where the water heater is installed If the altitude is more than 3 280 feet 1 000m the adjustment of DIP switch is required Turn off the gas shut off valve and water shutoff valve Remove the front cover Find the two ...

Страница 36: ...ide detector with alarm and battery back up may be installed on the next adjacent floor level b In the event that the requirements of this subdivision can not be met at the time of completion of installation the owner shall have a period of thirty 30 days to comply with the above requirements provided however that during said thirty 30 day period a battery operated carbon monoxide detector with an...

Отзывы: