NOTE: STATIC DISCHARGE CAN DAMAGE INTEGRATED FURNACE CONTROL (IFC)
MAIN BURNER
REMAINS POWERED
AND LIT
INDOOR BLOWER MOTOR
STARTS 20 SECONDS
AFTER GAS VALVE OPENS
SYSTEM RUNS
UNTIL CALL FOR
HEAT ENDS
TURN THERMOSTAT TO OFF
VALVE SHUTS OFF
FLAME OFF
IDM MOTOR STOPS AFTER 5 SEC.
INDOOR BLOWER MOTOR
STOPS AFTER
90/120/160/180 SECONDS
TROUBLESHOOTING ENDS
NOTE: IF (IFC) GOES INTO LOCKOUT WAIT 30 SECONDS THEN
RESET SYSTEM
• CHECK POLARITY OF 115VAC SUPPLY
• CHECK CONTINUITY OF GROUND WIRE
• CHECK INSULATION OF IGNITER LEADS
• CHECK FLAME SENSE CURRENT (YELLOW LED)
LED IS ON IF FLAME CURRENT IS GOOD.
IT FLASHES IF CURRENT IS MARGINAL.
• TURN POWER OFF TO UNIT
• CLEAN FLAME SENSOR WITH STEEL WOOL IF LED FLASHES
• RESTORE POWER TO UNIT
• IF CHECKS ARE OK, REPLACE (IFC)
• CHECK FOR 115VAC ACROSS
REPLACE (IFC) IF
BLOWER MOTOR AND BLOWER
WIRING TO BLOWER
MOTOR TERMINALS (HEAT AND
MOTOR IS OK
NEUTRAL) ON (IFC)
REPLACE BLOWER MOTOR
NOTE: IF (IFC) GOES INTO LOCKOUT WAIT 30 SECONDS THEN
RESET SYSTEM
• CHECK CONTINUITY OF GROUND WIRE. NOTE: IF GROUND IS
POOR OR ERRATIC, SHUTDOWN MAY OCCUR OCCASIONALLY
EVEN THOUGH OPERATION IS NORMAL AT THE TIME
OF CHECKOUT.
• CHECK FLAME SENSE CURRENT
• CHECK FOR EXCESSIVE HEAT AT IGNITER BASE
(TEMP. ABOVE 1000 F (538 C) CAUSES SHORT TO GROUND)
• TURN POWER OFF TO UNIT
• CLEAN FLAME SENSOR WITH STEEL WOOL
• RESTORE POWER TO UNIT
• IF CHECKS ARE OK, REPLACE (IFC)
• CHECK FOR PROPER THERMOSTAT OPERATION
• REMOVE VALVE LEAD AT (IFC)
IF VALVE CLOSED, RECHECK THERMOSTAT AND
WIRING. IF NOT, REPLACE VALVE.
• CHECK FOR OPEN LIMIT.
• REPLACE (IFC)
• CHECK FOR OPEN LIMIT.
REPLACE (IFC)
REPEAT PROCEDURE UNTIL TROUBLE FREE
OPERATION IS OBTAINED.
YES
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
NO
Содержание RGDG
Страница 22: ...22 I400 FIGURE 19 HONEYWELL NO S9201E2001 CONTROL BOARD TWINNING CONNECTION SINGLE STAGE OPERATION...
Страница 23: ...23 FIGURE 20 HONEYWELL NO S9201E2001 CONTROL BOARD TWINNING CONNECTION TWO STAGE OPERATION I400...
Страница 30: ...30 BLOWER PERFORMANCE DATA RGDG RGPH UPFLOW HORIZONTAL MODELS BLOWER PERFORMANCE DATA RGLH DOWNFLOW MODELS...
Страница 31: ...31 BLOWER PERFORMANCE DATA RGVH HORIZONTAL MODELS BLOWER PERFORMANCE DATA RGDJ RGPJ UPFLOW HORIZONTAL MODELS...
Страница 32: ...32 BLOWER PERFORMANCE DATA RGLJ DOWNFLOW MODELS ONLY BLOWER PERFORMANCE DATA RGVJ HORIZONTAL MODELS...
Страница 35: ...35 FIGURE 31 FILTER RETAINING RODS SIDE RETURN FIGURE 32 DOWNFLOW FILTER INSTALLATION...
Страница 43: ...FIGURE 36 FOR MODELS WITH UTEC 1012 920 OR HONEYWELL S9201E2001 INTEGRATED FURNACE CONTROL 43...
Страница 44: ...44 FIGURE 37 FOR MODELS WITH WHITE RODGERS 50A62 101 INTEGRATED FURNACE CONTROL...
Страница 45: ...45 FIGURE 38 FOR MODELS WITH UTEC 1012 925 INTEGRATED FURNACE CONTROL...
Страница 46: ...46...
Страница 47: ...47...
Страница 48: ...48 CM 398 Rheem Manufacturing Company Air Conditioning Division Fort Smith Arkansas...