LP CONVERSION
The valve can be converted to use
liquefied petroleum (LP) gas by
replacing the pressure regulator spring
with the conversion kit spring. This LP
kit spring allows the regulator to
maintain the proper manifold pressure
for LP gas. The correct burner LP
orifices are included in
the kit. See Figure 14.
NOTE:
Order the correct LP conversion
kit from the furnace manufacturer.
Furnace conversion to LP gas must
be performed by a qualified
technician.
To change orifice spuds for either
conversion to LP or for elevation:
1. Shut off the manual main gas
valve and remove the gas
manifold.
2. Replace the orifice spuds.
3. Reassemble in reverse order.
Consult the tables at right if there is any
question concerning orifice sizing.
4. Turn the gas supply back on and
check for proper operation and
manifold pressure.
5. Attach the notice label alerting the
next service technician that the
furnace has been converted to LP
gas.
NOx MODELS
When converting furnaces equipped
with NOx inserts to LP gas, remove the
NOx insert assemblies. Steps for
removal are listed below:
1. Turn off all electrical power and the
gas supply to the furnace.
2. Remove the burner door from the
furnace.
3. Remove the igniter assembly –
handle with care.
4. Remove the two screws attaching
the NOx insert retainer brackets to
the center panel. Pull the retainer
rod.
5. Put the two screws back into the
holes in the center panel.
6. Re-install the igniter and burner
assemblies.
7. Replace burner door.
8. Turn on electrical power and gas
supply to the unit.
18
RATING PLATE
ELEVATION
INPUT
BTU/HR
0 TO 7,999 FT.
8,000 FT. AND ABOVE
NATURAL GAS
HEATING VALUE @ 1,000 BTU/FT
3
, SPECIFIC GRAVITY 0.62
MANIFOLD PRESSURE @ 3.5
(
W.C.
45,000
43
45
50,000
42
43
67,500
43
45
75,000
42
43
100,000
42
43
125,000
42
43
150,000
42
43
L.P. GAS
HEATING VALUE @ 2,475 BTU/FT
3
, SPECIFIC GRAVITY 1.52/
MANIFOLD PRESSURE @ 10
(
W.C.
45,000
54
55
50,000
54
55
67,500
54
55
75,000
54
55
100,000
54
55
125,000
54
55
150,000
54
55
ORIFICE SIZING CHART
RATING PLATE
ELEVATION
INPUT
BTU/HR
0 TO 1,999 FT.
2,000 FT. TO 4,500 FT.
NATURAL GAS
HEATING VALUE @ 1,000 BTU/FT
3
, SPECIFIC GRAVITY 0.62
MANIFOLD PRESSURE @ 3.5
(
W.C.
45,000
43
45
50,000
42
43
67,500
43
45
75,000
42
43
100,000
42
43
125,000
42
43
150,000
42
43
L.P. GAS
HEATING VALUE @ 2,475 BTU/FT
3
, SPECIFIC GRAVITY 1.52/
MANIFOLD PRESSURE @ 10
(
W.C.
45,000
54
55
50,000
54
55
67,500
54
55
75,000
54
55
100,000
54
55
125,000
54
55
150,000
54
55
ORIFICE SIZING CHART (CANADA)
Содержание RGDG
Страница 22: ...22 I400 FIGURE 19 HONEYWELL NO S9201E2001 CONTROL BOARD TWINNING CONNECTION SINGLE STAGE OPERATION...
Страница 23: ...23 FIGURE 20 HONEYWELL NO S9201E2001 CONTROL BOARD TWINNING CONNECTION TWO STAGE OPERATION I400...
Страница 30: ...30 BLOWER PERFORMANCE DATA RGDG RGPH UPFLOW HORIZONTAL MODELS BLOWER PERFORMANCE DATA RGLH DOWNFLOW MODELS...
Страница 31: ...31 BLOWER PERFORMANCE DATA RGVH HORIZONTAL MODELS BLOWER PERFORMANCE DATA RGDJ RGPJ UPFLOW HORIZONTAL MODELS...
Страница 32: ...32 BLOWER PERFORMANCE DATA RGLJ DOWNFLOW MODELS ONLY BLOWER PERFORMANCE DATA RGVJ HORIZONTAL MODELS...
Страница 35: ...35 FIGURE 31 FILTER RETAINING RODS SIDE RETURN FIGURE 32 DOWNFLOW FILTER INSTALLATION...
Страница 43: ...FIGURE 36 FOR MODELS WITH UTEC 1012 920 OR HONEYWELL S9201E2001 INTEGRATED FURNACE CONTROL 43...
Страница 44: ...44 FIGURE 37 FOR MODELS WITH WHITE RODGERS 50A62 101 INTEGRATED FURNACE CONTROL...
Страница 45: ...45 FIGURE 38 FOR MODELS WITH UTEC 1012 925 INTEGRATED FURNACE CONTROL...
Страница 46: ...46...
Страница 47: ...47...
Страница 48: ...48 CM 398 Rheem Manufacturing Company Air Conditioning Division Fort Smith Arkansas...