2.9 HORIZONTAL
Units with an “H” (left-hand air supply) in the airflow direction position in the model number
have factory configured evaporator coils for installation in the horizontal position.
Conversion to Horizontal: A vertical upflow evaporator coil may be converted to horizon-
tal by removing the indoor coil and installing horizontal drain pan on coil as shown for right
hand or left hand air supply. Reinstall coil in unit as shown for right or left hand air supply.
See Figures 6 & 7.
Conversion in Horizontal Direction: Evaporator coils configured for horizontal left-hand
supply can be changed to horizontal right-hand supply by removing the indoor coil and
installing the drain pan as shown in Figures 6 & 7 for appropriate air supply direction.
Horizontal Drain Pan Model RXBD-CB: This drain pan is used on all coil models and
fits all unit sizes either right or left hand air supply.
• Install horizontal drain pan as shown for right hand or left hand supply. Drain pan con-
nections must be toward front of coil (header connection end). Install coil assembly
!
CAUTION
HORIZONTAL UNITS MUST BE CONFIGURED FOR RIGHT HAND AIR SUPPLY
OR LEFT HAND AIR SUPPLY. HORIZONTAL DRAIN PAN MUST BE LOCATED
UNDER INDOOR COIL. FAILURE TO USE THE DRAIN PAN CAN RESULT IN
PROPERTY DAMAGE.
FIGURE 6
INDOOR COIL AND DRAIN PAN SET-UP
HORIZONTAL LEFT-HAND AIR SUPPLY
FIGURE 7
INDOOR COIL AND DRAIN PAN SET-UP
HORIZONTAL RIGHT-HAND AIR SUPPLY
I156
I156
!
WARNING
THE FIRST 36 INCHES OF SUPPLY AIR PLENUM AND DUCTWORK MUST BE
CONSTRUCTED OF SHEET METAL AS REQUIRED BY NFPA 90B. THE SUPPLY
AIR PLENUM OR DUCT MUST HAVE A SOLID SHEET METAL BOTTOM
DIRECTLY UNDER THE UNIT WITH NO OPENINGS, REGISTERS OR FLEXIBLE
AIR DUCTS LOCATED IN IT. IF FLEXIBLE SUPPLY AIR DUCTS ARE USED THEY
MAY BE LOCATED ONLY IN THE VERTICAL WALLS, OF A RECTANGULAR
PLENUM, A MINIMUM OF 6 INCHES FROM THE SOLID BOTTOM. METAL
PLENUM OR DUCT MAY BE CONNECTED TO THE COMBUSTIBLE FLOOR
BASE, IF NOT, IT MUST BE CONNECTED TO THE UNIT SUPPLY DUCT
FLANGES SUCH THAT COMBUSTIBLE FLOOR OR OTHER COMBUSTIBLE
MATERIAL IS NOT EXPOSED TO THE SUPPLY AIR OPENING FROM THE
DOWNFLOW UNIT. EXPOSING COMBUSTIBLE (NON-METAL) MATERIAL TO
THE SUPPLY OPENING OF A DOWNFLOW UNIT CAN CAUSE A FIRE RESULT-
ING IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
EXCEPTIONS TO DOWNFLOW WARNINGS:
• INSTALLATIONS ON CONCRETE FLOOR SLAB WITH SUPPLY AIR PLENUM
AND DUCTWORK COMPLETELY ENCASED IN NOT LESS THAN 2 INCHES OF
CONCRETE (SEE NFPA 90B).
• INSTALLATIONS OF UNITS WITHOUT ELECTRIC HEATERS.