background image

39

Outdoor Reset Concept

The Temperature controller can  change the System Set 

Point  based  on  outdoor  temperature  (Outdoor  Reset). 

The temperature controller varies the temperature of the 

circulating  heating  water  in  response  to  changes  in  the 

outdoor  temperature.  The  heating  water  temperature  is 

controlled  through  the  modulation  and/or  sequencing  of 

the cascade. The Temperature controller can also control 

the system circulating pump with an adjustable Outdoor 

Cutoff. 
When the outdoor temperature is above the Outdoor Cutoff, 

the pump is turned off and no heating water is circulated 

through  the  system.  When  the  outdoor  temperature 

drops below the Outdoor Cutoff, the system pump relay 

is activated and the heating water circulates through the 

system. The temperature of the heating water is controlled 

by the Reset Ratio, Water Offset, and changes with the 

outdoor temperature.

Reset Ratio/Outdoor Reset

When a building is being heated, heat escapes through the 

walls,  doors,  and  windows  to  the  colder  outside  air.  The 

colder the outside temperature, the more heat escapes. If 

you can input heat into the building at the same rate that 

it is lost out of the building, then the building temperatures 

will remain constant. The Reset Ratio is an adjustment that 

lets  you  achieve  this  equilibrium  between  heat  input  and 

heat loss. The starting point for most systems is the 1.00 

(OD):1.00  (SYS)  (Outdoor  Temperature:  Heating  Water 

Temperature) ratio. This means that for every degree the 

outdoor temperature drops, the temperature of the heating 

water will increase one degree. 
With the VERSA, both ends of the slope are adjustable. It is 

factory set at 70°F (21ºC) water temperature (Boil START) 

at 70°F (21ºC) outdoor air (OUT START), and 180°F (82ºC) 

water temperature (Boil DESIGN) at 10°F (-12ºC) outdoor 

air (OUT DESIGN).
Each building has different heat loss characteristics. A very 

well insulated building will not lose much heat to the outside 

air, and may need a Reset Ratio of 2.00 (OD):1.00 (SYS) 

(Outdoor:  Water).  This  means  the  outdoor  temperature 

would  have  to  drop  2  degrees  to  increase  the  water 

temperature 1 degree. On the other hand, a poorly insulated 

building may need a Reset Ratio of 1.00 (OD):2.00 (SYS). 

This means that for each degree the outdoor temperature 

dropped the water temperature will increase 2 degrees. 
The  VERSA  Reset  Ratio  allows  for  full  customization  to 

match  any  buildings  heat  loss  characteristics.  A  heating 

curve that relies not only on Outdoor temperature but also 

on the type of radiation will improve heat comfort. The user 

can  fine  tune  these  adjustments  based  on  the  specific 

building need.

Reset Ratio Settings

The controller uses the four following settings to determine 

the reset ratio:

1.  Heater Start (Boil START). The Boil START temperature 

is  the  theoretical  heater  supply  water  temperature 

that  the  heating  system  requires  when  the  outdoor 

air temperature equals the OUT START temperature 

setting. The Boil START is typically set to the desired 

building temperature.

2.  Outdoor  Start  (OUT  START).  The  OUT  START 

temperature is  the  outdoor temperature  at which the 

control  provides  the  Boil  START  water  temperature 

to the system. The OUT START is typically set to the 

desired building temperature.

3.  Outdoor  Design  (OUT  DESIGN).  The  OUT  START 

is  the  outdoor  temperature  that  is  typical  coldest 

annual  temperature  where  the  building  is  located. 

This temperature is used when completing heat loss 

calculation for the building. 

4.  Heater  Design  (Boil  DESIGN).  The  Boil  DESIGN 

temperature is the water temperature required to heat 

the heater zones when the outdoor air is as cold as the 

OUT DESIGN temperature.

Warm Weather Shut Down (WWSD)

When the outdoor air temperature rises above the WWSD 

setting,  the  control  turns  on  the  WWSD  segment  in  the 

display.  When  the  control  is  in  the  Warm  Weather  Shut 

Down,  the  Dem  1  segment  is  displayed  if  there  is  a  heat 

demand. However, the control does not operate the heater 

to satisfy this demand. The control continues to respond to 

DHW demands.

Reset Ratio

The controller uses the following four settings to calculate 

the Reset Ratio (RR). For example, when using the default 

values, the RR is:

RESET RATIO =

(OUTDOOR START – OUTDOOR DESIGN)

(BOILER DESIGN – BOILER START)

RR = (70 - 10) / (180 - 70) = 0.55 

Therefore, the RR is 0.55:1 (Outdoor : Water).

Decreasing Outdoor Temperature

Inc

reasing 

W

at

er 

Temperatu

re

Boil

START

OUT

DESIGN

Boil DESIGN

START

OUT

Figure 40.  Reset Ratio

NOTE:

 The wiring diagrams in this manual show all 

standard options. Refer to the large wiring diagram 

provided with your heater for options installed on your 

specific unit(s).

Содержание Raypak MVB 1003A

Страница 1: ...other flammable vapors and liquids or other combustible materials in the vicinity of this or any other appliance To do so may result in an explosion or fire WHAT TO DO IF YOU SMELL GAS Do not try to...

Страница 2: ...n page 17 Second Note added on page 17 WH Direct DHW Configuration text revised on page 18 Electrical Power Connections text revised on page 20 Wiring the Cascade System Communication Bus Cascade Syst...

Страница 3: ...Connection 22 Venting General 24 Venting Installation Tips 26 Venting Configurations 26 Vertical Venting Category IV 26 Horizontal Through the Wall Direct Venting Category IV 28 Direct Vent Vertical 3...

Страница 4: ...at the time of heater installation ACAUTION If this heater is to be installed in a negative or positive pressure equipment room there are special installation requirements Consult factory for details...

Страница 5: ...sanitary rinse temperatures Safety and energy conservation are factors to be considered when setting the water temperature on the thermostat The most energy efficient operation will result when the t...

Страница 6: ...Identification The model identification number and heater serial number are found on the heater rating plate located on the upper rear jacket panel of the heater The model number will have the form H...

Страница 7: ...ns Top Figure 3 Component Locations Rear Figure 2 Component Locations Front LOW VOLTAGE SWITCH HIGH VOLTAGE SWITCH LOW VOLTAGE ELECTRICAL CONNECTIONS F10211 Figure 1 Component Locations Side Model No...

Страница 8: ...r side requires providing 12 service access on the opposite side Table C Clearances Indoor Installations 4 INSTALLATION Installation Codes Installations must follow these codes Local state provincial...

Страница 9: ...t the job site on the air filter intake at rear of the heater The elbow MUST be oriented with the opening facing downward TOP VIEW 24 610 mm SERVICE CLEARANCE REAR EXHAUST INSTALLATION FRONT VIEW VERT...

Страница 10: ...d above meter regulator assembly 3 91 cm within a height 15 above the meter regulator assembly I Clearance to service regulator vent outlet 6 1 83 m J Clearance to non mechanical air supply inlet to b...

Страница 11: ...s similar products Areas where contaminated combustion air commonly exists dry cleaning laundry areas metal fabrication plants beauty shops refrigeration repair shops photo processing plants auto body...

Страница 12: ...and the location of the opening s shall not interfere with the intended purpose of the opening s for ventilation air referred to in 1 This opening s can be ducted to a point not Conventional Combustio...

Страница 13: ...n the flue must be of a sealed joint design to ensure that the complete air system and combustion system is isolated from room air All ducting MUST be self supported Motorized Combustion Air Dampers o...

Страница 14: ...s of combustion from condensing beyond the ability of the condensate management system employed in this heater in most installations Warranty claims will be denied for damage or failures caused by con...

Страница 15: ...led so that the chilled medium is piped in parallel with the heater with appropriate valves to prevent the chilled medium from entering the heater The piping system of a hot water heater connected to...

Страница 16: ...with single or multiple boilers consult the VERSA IC manual 241493 for additional information on Cascade Systems in primary secondary piping configurations consult the VERSA IC manual 241493 for addit...

Страница 17: ...em temperature is controlled by the Supply sensor S3 whenever the indirect call for heat is not active The DHW Supply sensor S5 determines the indirect call tank setpoint During an indirect call for h...

Страница 18: ...eater and tank connections of no more than 100 eq ft of tubing gpm Gallons per minute flow rate MTS Minimum tubing size Must utilize optional cupro nickel tubes If over 25 grains per gallon a water so...

Страница 19: ...4 1253A 15 4 6 25 7 6 25 7 6 60 18 3 85 25 9 225 68 6 200 61 0 300 91 4 1503A 10 3 0 15 4 6 15 4 6 25 7 6 60 18 3 150 45 7 150 45 7 275 83 8 1753A 45 13 7 110 33 5 115 35 1 230 70 1 2003A 35 10 7 90 2...

Страница 20: ...tor which is located in the rear wiring box Use appropriately sized wire as defined by NEC CSA and or local codes All primary wiring should be 125 of minimum rating If any of the original wire as supp...

Страница 21: ...bserve proper wire colors while making electrical connections Many electronic controls are polarity sensitive Components damaged by improper electrical installation are not covered by warranty 5 Provi...

Страница 22: ...ound 3 Use a minimum 18 AWG wire for runs of up to 150 feet 4 Mount the outdoor sensor on an exterior surface of the building preferably on the north side in an area that will not be affected by direc...

Страница 23: ...e firing rate of a single MVB boiler Refer to the VERSA IC manual 241493 for additional information on Cascade Systems 2 To enable this remote control function set dip switch 5 to the UP position on t...

Страница 24: ...te production in the vent Category IV A heater which operates with a positive vent pressure and with a vent gas temperature that may cause excessive condensate production in the vent See Table I for a...

Страница 25: ...T extend exposed vent pipe outside of building beyond the minimum distance required for the vent termination Condensate could freeze and block vent pipe U S Installations Refer to the latest edition o...

Страница 26: ...nada CAUTION This venting system requires the installation of a condensate drain in the vent piping per the vent manufacturer s instructions Failure to install a condensate drain in the venting system...

Страница 27: ...EACH OTHER VENT CAPS AT STAGGERED ELEVATIONS FLUE GASES MOVING TOWARD EACH OTHER 1 25 mm MIN TYP 2 51 mm MIN TYP 1 25 mm MIN TYP DISCHARGE 4 0 30 5 cm MIN TYP DISCHARGE 4 0 30 5 cm MIN TYP Figure 26...

Страница 28: ...m should not exceed 75 equivalent ft 23 m in length If horizontal run exceeds 75 equivalent ft 23 m an appropriately sized variable speed extractor must be used Each elbow used is equal to 10 ft 3 m o...

Страница 29: ...hrough the Wall Venting FLUE EXHAUST VENT CAP ALTERNATE COMBUSTION AIR INTAKE LOCATION HEATER UNIT INSULATED EXHAUST VENTING 12 MIN 305 mm 36 MIN 91 m 6 MIN 152 mm 12 MIN 305 mm TEST PORT CONDENSATION...

Страница 30: ...ns Failure to install a condensate drain in the venting system will void all warranties on this heater The drain line must not be allowed to freeze Take appropriate measures Termination The vent cap M...

Страница 31: ...VERSA starts the burner at the minimum firing rate The burner cycle will terminate when both the Inlet and Outlet temperatures rise above 42 F 6 C 5 CONTROLS AWARNING Installation adjustment and serv...

Страница 32: ...low Figure 35 Flow Switch Low Water Cut Off Optional The optional low water cut off automatically shuts down the burner whenever water level drops below the level of the sensing probe A 5 second time...

Страница 33: ...sult the Touchscreen Quick Start User Guide 5000 74 and VERSA IC manual 241493 If your unit has Raymote installed refer to the Raymote installation and operation manual 241788 Figure 39 User interface...

Страница 34: ...3 Current system supply temperature Boil OUTLET All Current boiler outlet temperature Boil INLET All Current boiler inlet temperature Boil T All Current temperature difference between boiler outlet an...

Страница 35: ...Master Only ON OFF Cascade Alarm to all units in case of any unit presents alarm ON TARGET MAX H MODE 1 2 3 100 F 38 C to PIM value Maximum target system temperature 220 F 104 C TARGET MIN H MODE 1 2...

Страница 36: ...r during prepurge BLOW POSTt All Duration of blower postpurge BLOW POSTr All Blower during postpurge CASCADE TN BUS Cascade Follower Set Cascade ID for TN bus follower see VERSA IC manual 241493 MIN R...

Страница 37: ...t boiler outlet temperature Press UP DOWN for 1 sec to clear OUTDOOR HI H MODE 1 2 3 Records the highest outdoor temperature Press UP DOWN for 1 sec to clear OUTDOOR LO H MODE 1 2 3 Records the lowest...

Страница 38: ...RSA IC manual 241493 for details P N 104901 Software number of the Raypak VERSA DEFAULTS Resets to factory settings Press UP and DOWN for 1 second to show CLR and load factory defaults to all settings...

Страница 39: ...SYS This means that for each degree the outdoor temperature dropped the water temperature will increase 2 degrees The VERSA Reset Ratio allows for full customization to match any buildings heat loss c...

Страница 40: ...40 VERSA 013935F Raypak PIM RELEASED For Reference Only 6 WIRING DIAGRAM...

Страница 41: ...these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life This appliance has a hot surface igniter It is equipped with an ignition device which...

Страница 42: ...kout after the first failure to light 5 Wait until the controller indicates 100 on the firing rate display screen approximately 30 seconds MANIFOLD TAP AIR PRESSURE TEE MODELS 503A 1503A SHOWN Figure...

Страница 43: ...WC Table R MVB Air Pressure Settings User Test Set DIP switch 1 on the VERSA IC control to ON On Touchscreen click the Menu icon Tools icon Systems Tools Press Start to initiate User Test sequence Us...

Страница 44: ...be to it Connect the other end of the tube to a manometer and look for a build up of pressure Increasing pressure indicates a leaking gas valve which must be replaced 6 Remove rubber tube and manomete...

Страница 45: ...l allow one time operation of the limit and then must be returned to normal operation by turning dip switch 8 back to the OFF position Power to the unit must then be cycled off then on to return to no...

Страница 46: ...OOTING MVB Error Codes If any of the sensors detect an abnormal condition or an internal component fails during the operation of the MVB the display may show the error This code may either be the resu...

Страница 47: ...k blower wiring and blower AWARNING Do not use this appliance if any part has been under water Improper or dangerous operation may result Contact a qualified service technician to inspect the boiler a...

Страница 48: ...the gas supply See table for more information 4 flashes N A N A 5 flashes Low Voltage Fault Check the 24 VAC input voltage The voltage must be above 18 0 VAC 6 flashes N A N A 7 flashes Hi Limit Fault...

Страница 49: ...rvice agency 1 Visually check top of vent for soot Call service person to clean Some sediment at bottom of vent is normal 2 Visually inspect venting system for proper function deterioration or leakage...

Страница 50: ...r Check on page 43 3 Test high and low gas pressure interlocks if equipped Safety Inspection on page 44 Semi Annually 1 Recalibrate all indicating and recording gauges 2 Check flame failure detection...

Страница 51: ...ned 7 Test safety safety relief valves in accordance with ASME Heater and Pressure Vessel Code Section IV Filter Maintenance NOTE Use Raypak replacement filters kit number 012553F 12 X12 for models 50...

Страница 52: ...S 6 S 9 S 10 S 11 S 10 S 11 S 12 S 13 S 15 S 16 S 17 S 23 S 23 S 24 S 25 S 26 S 1 B 3 B 2 B 4 B 1 P 1 P 5 B 10 M 4 V 1 V OUTDOOR UNITS ONLY 2 V ROOFTOP VENTING ONLY 3 V SIDE WALL VENTING ONLY 13 C 1 O...

Страница 53: ...TAILS 3 C 5 C 2 J 3 J 19 S 6 O 8 O 4 J 6 J 4 C 15 C 11 J 12 J 2 O 7 O 2 H 3 H 4 H 5 H 6 H 10 H 4 H 31 S 5 H 1 M 5 M 5 M 7 M 8 M 2 S 3 S 7 S 18 S 6 C 7 C 4 O 3 O 5 J 20 S 8 J 21 S 7 J 9 J 14 S 10 J 27...

Страница 54: ...F 4 F 5 F 6 F 4 G 8 G 9 G 2 F 1 F 5 F 6 F 4 G 8 G 9 G 22 S 2 F 1 G 2 G 3 G 5 G 19 G 6 G 7 G 10 G 11 G 11 G 16 G 18 G 17 G 14 G 15 G 13 G 12 G BLOWER DETAIL MODELS 1753A 2003A MODELS 503A 1503A GAS TRA...

Страница 55: ...C Board Adapter Status Lights Wiring 014712F 014712F 014712F 014712F 014712F 014712F 014712F 16 J Reset Switch for Touchscreen 015879F 015879F 015879F 015879F 015879F 015879F 015879F F FAN 1 F Blower...

Страница 56: ...005755F 005755F 005755F 005755F 005755F 005755F 5 M Flue Collector Vertical Seal Gasket 011772F 011772F 011772F 011772F 011772F 011772F 011772F 18 M Heat Transfer Insulation Blanket 6 M Heat Transfer...

Страница 57: ...009129F 009129F 16 S Leg Bracket 4 pcs per boiler 007306F 007306F 007306F 007306F 007306F 007306F 007306F 17 S Base Reflector Panel 007307F 007307F 007307F 007307F 007307F 007307F 007307F 18 S Flue E...

Страница 58: ...l horizontally vented gas fueled equipment installed in every dwelling building or structure used in whole or in part for residential purposes including those owned or operated by the Commonwealth and...

Страница 59: ...PLACEMENT Under this Warranty Raypak will furnish a replacement for any failed part The failed part must first be returned to Raypak if requested with transportation charges prepaid and all applicable...

Страница 60: ...ombustion analyzer O2 _____________ _____________ See manual CO _____________PPM _____________PPM Less than 100 PPM CO2 _____________ _____________ See manual Model Number ____________________________...

Страница 61: ...61 NOTES...

Страница 62: ...62 NOTES...

Страница 63: ...63 NOTES...

Страница 64: ...Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A www raypak com...

Отзывы: