Table O. Boiler Menu
Item
Application
Description
IGNITION
All
Current State of Ignition
LIMIT TEMP
All
Current Limit Temperature
AUX TEMP
H MODE 3
Current Auxiliary Temperature
EMS Vdc
All
Current EMS signal in Volts DC
FIRE RATE
All
PIM firing rate
SPEED X1000 BLOWER All
Blower speed, Revolutions/Minute
HIGH LIMIT
All
High Limit Setting *
H L OFFSET
All
High Limit Offset *
OPERATOR
All
Operator Limit Potentiometer (PIM) setting
AUTO DIFF
H MODE 1, 2, 3
Current auto differential
PUMP PREPt
All
Duration of pump prepurge
BLOW PREPt
All
Duration of blower prepurge
BLOW PREPr
All
Blower % during prepurge
BLOW POSTt
All
Duration of blower postpurge
BLOW POSTr
All
Blower % during postpurge
CASCADE
TN-BUS Cascade Follower
Set Cascade ID for TN-bus follower, see VERSA IC manual 241493
MIN RATE
All
Minimum modulation rate % during operation *
START RATE
All
Start modulation rate % during ignition *
MAX RATE
All
Maximum modulation rate % during operation *
FLAME CUR
All
Flame current in micro-amps
IGN TYPE
All
PIM board type
MASS
All
Thermal mass of the boiler
ID CARD
All
Identifies OEM identity card
PIM ID
All
Identifies OEM PIM PCB
SW ID
All
PIM software identification number
* Fixed values based on ID card
Boiler Menu
The Boiler View displays various items regarding ignition, temperature monitoring, and modulation rates. As well as
software and hardware information. See
Table O
.