Table N. Setup/Adjust Menu
Item
Application
Range
Description
Default
BOILER 1
All
ON <> OFF
Enable or Disable the operation of boilers in FT Bus. 1 is
enabled by default
ON
TARGET
H MODE 1, 2, 3 RSET <> SETP
RSET = Outdoor Reset, SETP =Setpoint
SETP
TANK SETP
WH
OFF, 50°F to 160°F
(10°C to 71°C)
Tank set point temperature
125°F (52°C)
TANK DIFF
WH
2°F to 10°F
(-17°C to -12°C)
Tank Differential temperature
3
MODE
H MODE 1, 2, 3 1,2,3
Piping and application configuration.
1
SETPOINT
H MODE 1, 2, 3 50°F (66°C) to PIM
value*
Boiler target temperature while a heat demand is present for
setpoint operation
180°F (82°C)
OUT START
H MODE 1, 2, 3 35°F to 85°F
(2°C to 29°C)
Outdoor starting temperature - outdoor reset
70°F (21°C)
OUT DESIGN
H MODE 1, 2, 3 -60°F to 45°F
(-51°C to 7°C)
Outdoor design temperature - outdoor reset
10°F (-12°C)
Boil START
H MODE 1, 2, 3 35°F to 150°F
(2°C to 66°C)
Starting boiler target temperature when the outdoor
temperature is at outdoor start outdoor reset
70°F (21°C)
Boil DESIGN
H MODE 1, 2, 3 70°F to 200°F
(21°C to 93°C)
Design boiler target temperature when the outdoor
temperature is at outdoor design outdoor reset
180°F (82°C)
Boil MASS
All
1<>2<>3
Thermal mass of the boiler
1
Cascade Type
Cascade
Master Only
SEQ, PAR
Cascade operation type
SEQ
Cascade Delay Cascade
Master Only
AUTO<> 0:10...10:00
Cascade Interstage delay before calling next boiler
AUTO
Cascade Alarm Cascade
Master Only
ON <> OFF
Cascade Alarm to all units in case of any unit presents alarm
ON
TARGET MAX
H MODE 1, 2, 3 100°F (38°C) to PIM
value*
Maximum target system temperature
220°F 104°C)
TARGET MIN
H MODE 1, 2, 3 OFF, 50°F to 190°F
(10°C to 88°C)
Minimum target system temperature
50°F (10°C)
TARGET DIFF
H MODE 1, 2, 3 2°F to 42°F
Differential for target system temperature
10°F (-12°C)
DHW SENSOR H MODE 1, 2, 3 OFF <> ON
Selects whether a DHW sensor is used for indirect DHW tank
OFF
DHW DIFF
H MODE 2, 3
2°F to 10°F
(-17°C to -12°C)
Differential for the target indirect DHW tank temperature
6°F (-14°C)
IND SUPPLY
H MODE 2, 3
OFF, 50°F (10°C) to
PIM value*
Target boiler temperature for the DHW heat exchanger during
indirect DHW operation
180°F (82°C)
DHW
PRIORITY
H MODE 2
OFF <> ON
Selects whether or not Indirect DHW priority is active during
indirect DHW operation
OFF
PRI OVR
H MODE 2, 3
Au, 0:10hr to 2:00hr
Sets the length of the indirect DHW priority override time
1:00hr
BOIL PURGE
All
0:20min to 10:00min
Sets the length of the boiler pump post purge
20 seconds
SYS PURGE
All
OFF, 0:20min to
20:00min
Sets the length of the system pump post purge
20 seconds
WWSD
H MODE 1, 2, 3 40°F to 100°F (4°C to
38°C)
The system warm weather shutdown temperature outdoor
reset
70°F (21°C)
UNITS
All
deg F <> deg C
Show units using icons in display
deg F
MODBUS
All
OFF<>MNTR<>
TEMP<>RATE
ModBus Operating Mode: Off, Monitor, Temp Control, Rate
Control
OFF
ADDRESS
All
1 to 247
ModBus slave address
1
DATA TYPE
All
RTU <> ASCI
Modbus data type
RTU
BAUD RATE
All
2400<>9600<>19K2<>
57K6<>115K
19K2
PARITY
All
NONE<>EVEN<>ODD
EVEN