Installing the water heater

Thermal Expansion

Determine if a check valve exists in the 

inlet water line. Check with your local 

water utility. 

It may have been installed in 

the cold water line as a separate back flow 

preventer, or it may be part of a pressure 

reducing valve, water meter or water softener. 

A check valve located in the cold water inlet 

line can cause what is referred to as a 

“closed 

water system”

. A cold water inlet line with 

no check valve or back flow prevention 

device is referred to as an 

“open”

 water 

system.
As water is heated, it expands in volume and 

creates an increase in the pressure within the 

water system. This action is referred to as 

“thermal expansion”

. In an 

“open”

 water 

system, expanding water which exceeds the 

capacity of the water heater flows back into 

the city main where the pressure is easily 

dissipated. 

“closed water system”

, however, prevents 

the expanding water from flowing back 

into the main supply line, and the result of 

“thermal expansion”

 can create a rapid 

and dangerous pressure increase in the 

water heater and system piping. This rapid 

pressure increase can quickly reach the 

safety setting of the relief valve, causing 

it to operate during each heating cycle. 

Thermal expansion, and the resulting rapid 

and repeated expansion and contraction of 

components in the water heater and piping 

system can cause premature failure of the 

relief valve, and possibly the heater itself. 

Replacing the relief valve 

WILL NOT

 

correct the problem!
The suggested method of controlling thermal 

expansion is to install an expansion tank in 

the cold water line between the water heater 

and the check valve (refer to the illustration 

on the next page). The expansion tank is 

designed with an air cushion built in that 

compresses as the system pressure increases, 

thereby relieving the over pressure condition 

and eliminating the repeated operation of the 

relief valve. Other methods of controlling 

thermal expansion are also available. Contact 

your installing contractor, water supplier or 

plumbing inspector for additional information 

regarding this subject.

Water Supply Connections

Refer to the illustration on the next page 

for suggested typical installation. The 

installation of flexible connectors is 

recommended on the hot and cold water 

connections. Flexible connections provide 

vibration isolation and allow the water heater 

to be easily disconnected for servicing if 

necessary. The 

HOT

 and 

COLD

 water 

connections are clearly marked and are 

3/4in. NPT on all models. Install a shut-off 

valve in the cold water line near the water 

heater.

See page 8 on "To Fill The Water Heater".
NOTICE: DO NOT apply heat to the 

HOT or COLD water connections. If sweat 

connections are used, sweat tubing to 

adapter before fitting adapter to the water 

connections on heater. Any heat applied to 

the water supply fittings will permanently 

damage the dip tube and/or heat 

traps.

Condensate Drains

Consult local codes or ordinances for 

specific requirements. Refer to page 7.

IMPORTANT: When making drain fitting 

connections to the drain tubing, use a thin 

layer of piping tape or silicone and install 

hand tight.
IMPORTANT: When making drain fitting 

connections to the drain tubing, 

DO NOT

 

overtighten. Overtightening fittings can split 

pipe connections on the drain pan.
•  This unit is equipped with a 3/4" NPT 

female primary condensate connection 

and a 3/8" NPT female overflow 

connection.  Use MIP fittings for 

connections.

•  DO NOT

 reduce drain line size less 

than connection size provided on 

condensate drain.

•  All drain lines must be pitched 

downward away from the unit a 

minimum of 1/8" per foot of line to 

ensure proper drainage.

•  Drain lines must include a P-trap if 

connected to a sewer pipe.

•  If no drain is available, then a common 

condensate pump with a capacity no 

less than 2 gallon per day must be 

installed.

•  DO NOT

 allow condensate to drain into 

the water heater drain pan.

•  The drain line should be insulated 

where necessary to prevent sweating 

and damage due to condensate forming 

on the outside surface of the line.

Содержание HB Duct Ready Series

Страница 1: ...u do not understand these instructions or any terms within it seek professional advice Any questions regarding the operation maintenance service or warranty of this water heater should be directed to...

Страница 2: ...great deal of time and money over the life of your water heater You ll find many answers to common problems in the Before You Call For Service section If you review our chart of Troubleshooting Tips f...

Страница 3: ...D A N G E R HOT Water temperature over 125 F can cause severe burns instantly or death from scalds Children disabled and elderly are at highest risk of being scalded See instruction manual before sett...

Страница 4: ...ay call 916 445 8100 or ask a water heater dealer However applicable local codes shall govern installation For residential water heaters of a capacity greater than 52 gallons consult the local buildin...

Страница 5: ...elements or checking controls The water heater and water lines should be protected from freezing temperatures DO NOT install the water heater in outdoor unprotected areas Make certain the floor under...

Страница 6: ...ontrolling thermal expansion are also available Contact your installing contractor water supplier or plumbing inspector for additional information regarding this subject Water Supply Connections Refer...

Страница 7: ...al parts or persons and to eliminate potential water damage Piping used should be of a type approved for hot water distribution The discharge line must be no smaller than the outlet of the valve and m...

Страница 8: ...resulting in severe personal injury or death If the water heater has been subjected to fire flood or physical damage DO NOT operate the water heater again until it has been checked by a qualified ser...

Страница 9: ...ational Appliance Energy Conservation Act standards with respect to insulation and standby loss requirements making an insulation blanket unnecessary The manufacturer s warranty does not cover any dam...

Страница 10: ...r is supplied with a built in water sensing circuit The water sensor rope is shipped in the warranty bag for field installation Remove water sensor rope from thebagandattachtotheconnector located near...

Страница 11: ...st is sufficiently away from structures to prevent condensation on surfaces Maximum heater performance is obtained by lowering the resistance to air flow regular filter maintenance is beneficial and p...

Страница 12: ...Bends Each Maximum Allowed 5 8 5 6 5 4 5 2 8 inch UL Certified Termination for ducting outside Each 5 5 5 5 Reduced diameter UL Certified Termination for ducting outside Each N A 10 15 20 8 inch Regi...

Страница 13: ...90 1 Kit should be purchased for this installation Ducting Example Flex Duct secured and sealed with Duct tie 2 places on Inlet 1 place on Outlet to secure Flex Duct to unit flange UL Certified termin...

Страница 14: ...er Air purged from water heater and piping Water connections tight and free of leaks Flexible water connections HVAC approved ducting Calculated length of duct no greater than maximum allowed UL Certi...

Страница 15: ...ing valves are recommended for reducing point of use water temperature by mixing hot and cold water in branch water lines It is recommended that a mixing valve complying with the Standard for Temperat...

Страница 16: ...tton Navigating the Home Screen To turn the water heating On press the Mode button once Water heater ships in the default Energy Saver mode with a temperature setting of 120 F Recommended temperature...

Страница 17: ...eriods This mode will result in maximum power consumption See Elec Heat Override Time in Settings Vacation This mode will allow duration setting between 1 and 28 days or set indefinitely with the Hold...

Страница 18: ...potential for HOT water SCALDS Energy Saver Mode Status Settings warm hot very hot Service Mode 120 Arrows to adjust temperature Energy Saver Mod Status Settings warm hot very hot Service Mode 120 set...

Страница 19: ...during service periods To Enabled Disabled the audible alarm press Enabled to highlight then press up down buttons to change to Enabled Disabled EcoNet Network Instance This number can be set between...

Страница 20: ...roduct Model Number Product Serial Number Software Version Number WH HPW4 H2 00 81 Water Heater Test Off alarms status sensors wifi status Water Heater Mode Off ECO Trip Electric Heat Control Off Comp...

Страница 21: ...ry month to clean the tank of these deposits Rapid closing of faucets or solenoid valves in automatic water using appliances can cause a banging noise heard in a water pipe Strategically located riser...

Страница 22: ...before placing it in operation NOTICE Refer to the Hydrogen Gas Caution in the Operating Instructions Anode Rod This water heater is equipped with an anode rod designed to prolong the life of the glas...

Страница 23: ...ff Confirm electric supply to water heater and see installation section of this manual The thermostat may be set too low See the Temperature regulation of the water heater section of this manual Leaki...

Страница 24: ...rm codes More information is available by selecting alarm and then pressing more info Current Alarms Alarm History A101 Suction Temperature Sensor Failure T300 Water Leak Sensor Not Installed A200 Hig...

Страница 25: ...unction Heater disabled A105 Evaporator Temp Sensor Failure Heatingsourcedefaultsto elementsduetoheatpump temperaturesensormalfunction A106 Discharge Temp Sensor Failure A107 Water Detected on Floor C...

Страница 26: ...unit 2 Refer to Use and Care Manual 3 Call your installer contractor 4 Call Tech Support at 1 800 995 0982 T300 Water Leak Sensor Not Installed Water Leak Sensor Not Installed 1 Install Water Leak Sen...

Страница 27: ...rating plate Part description as noted below and number of parts desired CAUTION For your safety DO NOT attempt repair of electrical wiring heating elements heat pump or electronic controls Refer rep...

Страница 28: ...ss panel s and insulation Rotate the crossbar up and down until it breaks away from the remainder of the cavity insert See illustration to the left Discard the crossbar It cannot and need not be repla...

Страница 29: ...E ECO EMERGENCY CUT OFF ET EVAPORATORTEMPERATURE EXV ELECTRONIC EXPANSIONVALVE FAN FAN GND NUT GROUND NUT ONTANK HPS HIGH PRESSURE SWITCH JCT BOX JUNCTION BOX LE LOWER ELEMENT LEAK LEAK SENSOR SOME MO...

Страница 30: ...act the Manufacturer s National Service Department at the following address 1241 Carwood Court Montgomery Alabama 36117 Phone 1 800 995 0982 When contacting the manufacturer the following information...

Отзывы: