Rheem Direct Vent Gas Tankless Water Heater Скачать руководство пользователя страница 15

15

Water Supply Connections

IMPORTANT: Do not
apply heat to the HOT or
COLD water connections. If
sweat connections are used,
sweat tubing to adapter
before fitting adapter to the
water connections on
heater. Any heat applied to
the water supply fittings
will permanently damage
the internal components 
of the water heater.

Mounting the Water Heater

Make sure the location of the appliance allows
for easy access and operation.

Wall studs should be utilized when mounting
the water heater to the wall. Alternately, a
suitable piece of wood may be placed inside
or outside of the wall to span the distance
between the wall studs. Fasten the water
heater mounting brackets to the wood.

In case of dry wall or concrete wall, use 
drywall anchors or lag bolts.

The water heater requires 120VAC/60Hz.
Have a receptacle with ground terminal near
the water heater. The length of the power
supply cord is 10 feet (3 m).

Install a wood screw for the upper bracket
with a clearance of 1/8” (.32 cm) between the
wall and the screw head. Hang the center of
the upper bracket on the screw.

Using a wood screw and a washer, affix the

lower bracket to the wall (Left and Right).
Repeat to affix the top bracket.

The brackets can be adjusted to change the
distance between the back of the appliance
and the wall within the range of 3/8” (.95 cm)
to 1-1/2” (3.8 cm).

Loosen the adjustment screws of both the top
and the bottom brackets to adjust the distance
(See diagram below).

Bracket

Bracket

Adjustment Screws

Adjustment Screws

TOP

BOTTOM

Upper Bracket

Washer

Washer

Wood 
Screw

Wood 
Screw

Wood 
Screw

Lower Bracket

1/8" (.32 cm)

Clearance

Plumbing should be carried out by a qualified
plumber in accordance with local codes.

Use approved plumbing materials only.

The diameter of the pipe lines should be a
minimum of 3/4”.

To conserve energy and to prevent freezing,
insulate both cold and hot water supply 
lines. DO NOT cover the drain or pressure
relief valve.

To ensure proper operation of the water
heater, the following water pressure guidelines
should be followed:

Operation of the water heater requires the
minimum water pressure of 14 psi (97 kPa)
and a minimum water flow rate of 0.66
gpm (2.5 lpm).

A water pressure of 40 psi (276 kPa) is
required to achieve maximum flow rate.

To maintain proper performance, ensure
sufficient water supply pressure. The

Required Water Pressure = Min. Operating
Water Pressure (14 psi [97 kPa]) + Pipe
Pressure Loss + Faucet and Shower
Pressure Loss + Safety Margin (more than
5 psi [34 kPa]).

To supply hot water to upper floors,
additional water pressure (0.44 psi/ft 
[10 kPa/m]) must be ensured. The
measurement should be calculated by the
distance between the water inlet of the
water heater (ground level) to the hot 
water faucet (upper floor level).

Well water systems should be set to ensure
a minimum system pressure of 40 psi (276
kPa). The pressure should remain stable
during the operation of the water heater.

When the water is supplied from a water
supply tank, the height of the tank and the
diameter of the pipes and their relation to
water pressure should be taken into
consideration. 

Gravity water pressure is

not recommended

.

CAUTION:

Reinforcement of the wall is
required in case the wall is
not strong enough to hold
the appliance.

Thermal Expansion

A thermal expansion tank will be required if
the water heater is installed in a closed loop
system to prevent damage to heater, related
piping and relief valve. Replacing the relief
valve will not correct the problem! The
expansion tank is designed with an air cushion
built in that compresses as the system pressure
increases, thereby relieving the over pressure

condition and eliminating the repeated
operation of the relief valve. Other methods of
controlling thermal expansion are also
available. Contact your installing contractor,
water supplier or plumbing inspector for
additional information regarding this subject.

The image above may differ
in appearance from your
water heater.

The image above may differ in
appearance from your water heater.

Содержание Direct Vent Gas Tankless Water Heater

Страница 1: ...the proper installation and adjustment of the water heater and two to the owner operator to explain the features operation safety precautions maintenance and troubleshooting of the water heater This...

Страница 2: ...ce READ THIS MANUAL FOR YOUR RECORDS Write the model and serial numbers here You can find them on a label on the appliance Staple sales slip or cancelled check here Proof of the original purchase date...

Страница 3: ...er flammable materials and liquids adhesives solvents paint thinners etc and the vapors they produce are extremely dangerous DO NOT handle use or store gasoline or other flammable or combustible mater...

Страница 4: ...ng allows operating temperatures between 100 F 38 C and 120 F 49 C Temperatures of up to 140 F 60 C can be achieved with the MAIN UMC 117 remote control and a dip switch adjustment Only qualified serv...

Страница 5: ...e or LP gas must be used with great caution It is heavier than air and will collect first in lower areas making it hard to detect at nose level Before attempting to light the water heater make sure to...

Страница 6: ...ON READ ALL INSTRUCTIONS BEFORE USING WARNING For your safety the information in this manual must be followed to minimize the risk of fire or explosion electric shock or to prevent property damage per...

Страница 7: ...of any flammable liquids which may be improperly stored or accidentally spilled The water heater should be installed as close as practical to the vent termination to minimize vent length and the numbe...

Страница 8: ...operator to explain the features operation safety precautions maintenance and troubleshooting of the water heater This manual also includes a parts list It is imperative that all persons who are expec...

Страница 9: ...eting the installation and putting the water heater into service DANGER Failure to install the appliance vent adapter and properly vent the water heater to the outdoors as outlined in the Venting sect...

Страница 10: ...and dispose of condensate from venting systems When a water heater is vented horizontally the vent pipe can have a DOWNWARD or UPWARD slope towards the termination If an UPWARD slope is used a condens...

Страница 11: ...let to any building or other appliance 6 inches 15 cm for appliances 10 000 Btuh 3 kW 12 inches 30 cm for appliances 10 000 Btuh 3kW and 100 000 Btuh 30kW 36 inches 91 cm for appliances 100 000 Btuh 3...

Страница 12: ...maintenance Do NOT extend exposed vent pipe of indoor water heaters outside of building Guard vent against accidental contact with people and pets Indoor Water Heater 12 WARNING Moisture in the flue...

Страница 13: ...Example A Typical Horizontal Termination w 1 4 per foot DOWNWARD Slope 13 Installing the water heater...

Страница 14: ...llow the vent manufacturer s recommended installation instructions provided with the vent purchased from the manufacturer Chase Requires 6 15 cm Clearance to Combustibles Firestop Firestop Roof Jack A...

Страница 15: ...or pressure relief valve To ensure proper operation of the water heater the following water pressure guidelines should be followed Operation of the water heater requires the minimum water pressure of...

Страница 16: ...e copper connections are recommended on the HOT and COLD water lines so that the water heater may disconnect easily for servicing if necessary Install a Check Valve between the water heater and the wa...

Страница 17: ...be installed in the discharge line Notice Local codes govern the installation of relief valves If local codes require that a temperature and pressure relief valve should be installed the manufacturer...

Страница 18: ...the action of LP gas Use compound sparingly on male threads only A sediment trap should be installed at the bottom of the gas line Do not use excessive force over 31 5 ft lbs 42 7 Nm in tightening the...

Страница 19: ...controls can connect to the water heater Therefore a maximum of three controls can connect to the water heater No other manufacturer s controls are suitable for use with this water heater DO NOT atte...

Страница 20: ...NING Field wiring connections and electrical grounding must comply with local codes or in the absence of local codes with the latest edition of the National Electrical Code ANSI NFPA 70 or in Canada C...

Страница 21: ...personal injury or death CAUTION Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Verify correct operation after servicing BK 8 R...

Страница 22: ...22 Installing the water heater Typical Installation of Water Heater Venting Required...

Страница 23: ...y heat loss encountered with storage tank heaters This water heater does not store water making an insulation blanket unnecessary The manufacturer s warranty does not cover any damage or defect caused...

Страница 24: ...sufficient for the water heater Gas line equipped with shut off valve union and sediment trap Approved pipe joint compound used Soap and water solution used to check all connections and fittings for...

Страница 25: ...and all other labels on the water heater as well as the warnings printed in this manual Failure to do so can result in unsafe operation of the water heater resulting in property damage personal injur...

Страница 26: ...alves are available for reducing point of use water temperature by mixing hot and cold water in branch water lines Contact a licensed plumber or the local plumbing authority for further information Se...

Страница 27: ...otter water increases the risk of scald injury Always supervise young children or others who are incapacitated The water heater is equipped with a device that will shut off the gas supply to the burne...

Страница 28: ...nance and or cleaning ensure proper operation by turning on a hot water faucet Housekeeping Before performing Housekeeping tasks to this water heater turn the unit off and disconnect the power supply...

Страница 29: ...t It is recommended that qualified service personnel familiar with Category III venting inspect the venting system Check vent connection joint sections with a solution of soapy water to assure air tig...

Страница 30: ...freezing conditions even for a short period of time be sure to drain all water from the unit as instructed above Exposure to freezing conditions can occur from down draft of venting system or from in...

Страница 31: ...functions if applicable Check and replace if necessary Error code displayed on remote control See instructions for Error Code and if required contact a dealer for service Not enough water demand Incre...

Страница 32: ...r safety devices Refer repairs to qualified service personnel CAUTION Make certain power to water heater is OFF before removing protective cover FOR ANY REASON CAUTION Label all wires prior to disconn...

Страница 33: ...33...

Страница 34: ...splay of the Main Remote Control is on continuously Change the DIP Switch 4 setting back to the OFF position DO NOT alter any other DIP Switch The LED on the PCB will stop illuminating At the same tim...

Страница 35: ...35 Notes...

Страница 36: ...ll be located in the room that houses the appliance or equipment and shall a Be powered by the same electrical circuit as the appliance or equipment such that only one service switch services both the...

Отзывы: