47
Low** 823 803 787 732 718 691 651 593
Med. Lo* 1030 1018 1006 976 929 897 850 808
Med. Hi 1129 1132 1112 1087 1054 1028 971 919
High 1361 1353 1331 1297 1264 1232 1164 1117
Low** 1229 1200 1181 1155 1120 1078 1013 970
Med. Lo 1308 1267 1266 1233 1204 1176 1113 1062
Med. Hi* 1553 1542 1516 1491 1451 1417 1358 1306
High 1969 1924 1893 1840 1803 1728 1657 1570
Low** 1209 1182 1131 1112 1051 976 929 867
Med. Lo* 1438 1420 1386 1350 1320 1293 1248 1186
Med. Hi 1902 1883 1844 1817 1753 1700 1636 1547
High 2071 2037 2001 1962 1905 1856 1807 1709
Low** 1358 1354 1331 13091 1250 1224 1154 1089
Med. Lo 1541 1517 1476 1453 1416 1371 1339 1277
Med. Hi* 1799 1774 1746 1712 1691 1629 1554 1495
High 2015 1989 1929 1902 1862 1815 1742 1665
Low** 1411 1395 1370 1334 1310 1252 1220 1150
Med. Lo 1606 1579 1569 1537 1499 1468 1407 1346
Med. Hi* 1889 1891 1849 1828 1764 1717 1659 1609
High 2178 2160 2105 2067 2024 1976 1916 1832
TABLE 12
AIR FLOW PERFORMANCE – (-)802P/(-)(-)80MDP SERIES MODELS
Model
Motor HP
Blower Size,
IN.
CFM Air Delivery
External Static Pressure, ” W.C.
Speed Tap
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
(-)802PA050314MSA
(-)(-)80MDP050A30SA
1/3
11 x 6
(-)802PA075417MSA
(-)(-)80MDP075B30SA
(-)802PA100521MSA
(-)(-)80MDP100C40SA
(-)802PA125524MSA
(-)(-)80MDP125D50SA
1/2
11 x 7
1/2
11 x 10
3/4
11 x 10
(-)802PA150524MSA
(-)(-)80MDP150D50SA
3/4
11 x 10
**Low Heating
*High Heating
Air
flo
w
BLOWER SPEED SELECTIONS
The furnace controls have four active quick connect termi-
nals for connecting the motor speed leads. These are:
1. LO HEAT/FAN — motor runs on this speed when the
thermostat is in the “FAN ON” position or when low
stage heat (W) is energized.
2. COOL — connect desired cooling speed.
3. HI HEAT — connect desired high heating speed.
4. H/C (for heat/cool) — connect desired speed when
high heating and cooling speed are the same.
In addition to the active motor terminals, there are two
motor parking terminals (labeled M1 and M2) available for
placing any unused motor taps. All unused motor taps
should be connected to either M1 or M2. These terminals
(M1 and M2) will not be energized under any condition.
IMPORTANT:
Do not connect any motor speeds to “HI
HEAT” and/or “COOL” if you use the “HEAT/COOL” termi-
nal.
If cooling speed and fan speed are desired to be the same,
this may be accomplished by not connecting “Y” to the in-
tegrated furnace control.
See selection titled “Field Selections – Dipswitches” for
setting the heating and cooling blower off delay times.