COMBUSTION AND VENTILATION AIR (cont.)

VERTICAL VENT SYSTEMS:
1. A gas vent shall terminate above the roof surface with a listed

cap or listed roof assembly. Gas vents 12 inches in size or
smaller with listed caps shall be permitted to be terminated in
accordance with Figure 15, provided they are at least 8 feet
from a vertical wall or similar obstruction. All other gas vents
shall terminate not less than 2 feet above the highest point
where they pass through the roof and at least 2 feet higher
than any portion of a building within 10 feet.

2. A type B-1 gas vent shall terminate at least 5 feet in vertical

height above the highest connected equipment draft hood or
flue collar.

3. Must rise 

1

/

4

” per foot away from the furnace on horizontal runs

and be supported with straps or hangers so it has no sags or
dips. Supports at 4 foot intervals and at all elbows are recom-
mended.

4. The vent connector must be mechanically fastened to the out-

let collar of the furnace with at least (2) sheet metal screws ex-
cept vent connectors that are B-1 material. These shall be
assembled in accordance with the manufacturer’s instructions.
See Figures 16 and 17.

5. Any angle greater than 45 degrees from the vertical is consid-

ered horizontal. The total horizontal distance of a vent plus the
horizontal vent connector serving draft-hood equipped appli-
ances shall not be greater than 75 percent of the vertical
height of the vent.

Single appliance venting of a fan assisted furnace into a tile-lined
masonry chimney is prohibited. The chimney must be lined with
either Type B vent or with a listed, single wall, metal lining sys-
tem. Reference National Fuel Gas Code, ANSI Z223.1 and/or the
Natural Gas Installation Code, CSA-B149.1 & .2. See Figure 18
for typical B-1 vent chase.

NOTE:

A chimney adapter is available as an accessory (see ac-

cessory section of this manual). Follow manufacturer’s instruc-
tions.

SPECIAL VENT SYSTEMS (SVS)

IMPORTANT: 

It is THE FURNACE MANUFACTURER’s position

now that new installations of any HTPV pipe used in a category

III

vent application, including Selkirk’s Selvent™   

II

HTPV prod-

uct, should cease immediately.

!

WARNING

DO NOT CONNECT THIS FURNACE TO A CHIMNEY USED
TO VENT A SOLID FUEL APPLIANCE (WOOD OR COAL).
VENTING WITH A SOLID FUEL APPLIANCE CAN LEAD TO
IMPROPER FUNCTIONING OF THE UNIT, AND DUE TO
SOOTING, THE POSSIBILITY OF FIRE RESULTING IN
PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.

A0991-01

FIGURE 16

ATTACHING TO DRAFT INDUCER COLLAR

LISTED CAP

LISTED GAS VENT

ROOF PITCH = X/12

12

X

 - MINIMUM ALLOWABLE HEIGHT

        FROM ROOF TO DISCHARGE OPENING

F

 

 

 

 

 

                  

ROOF PITCH

   

 

“H” (MIN.) FT.

        FLAT TO 6/12   

 

       1.0

     OVER 6/12 TO 7/12 

                   1.25

    OVER 7/12 TO 8/12 

                   1.5

    OVER 8/12 TO 9/12 

                   2.0

    OVER 9/12 TO 10/12 

                   2.5

     OVER 10/12 TO 11/12                     3.25

    OVER 11/12 TO 12/12                     4.0
    OVER 12/12 TO 14/12                     5.0
    OVER 14/12 TO 16/12                     6.0
    OVER 16/12 TO 18/12                     7.0
    OVER 18/12 TO 20/12                     7.5
    OVER 20/12 TO 21/12                     8.0

ST-A1220-24

FIGURE 15

TYPICAL VENTING WITH “B-1” VENT

ST-A1220-24

Содержание (-)(-)80MDP050A30SA

Страница 1: ...IZONTAL SERIES U L and or C S A recognized fuel gas and CO carbon monoxide detectors are rec ommended in all applications and their installation should be in accordance with the manufacturer s recomme...

Страница 2: ...30 Humidifier 30 Filter 30 RXGW B01 Chimney Adapter 30 Four Inch Flue Adapter 30 11 TWINNING 32 Furnace Twinning Installations 32 Control Boards 33 35 12 HIGH ALTITUDE 36 Natural Gas at High Altitudes...

Страница 3: ...r is correct open the carton and verify that the furnace rating label specifies the same furnace model number that is speci fied on the carton label If the model numbers do not match re turn the furna...

Страница 4: ...hese publications are ANSI NFPA No 70 Latest Edition National Electrical Code NFPA90A Installation of Air Conditioning and Ventilating Sys tems NFPA90B Installation of warm air heating and air conditi...

Страница 5: ...erature rise in heat record air temperature rise ______ Air temperature rise in cool record air temperature rise VENTING ______ Correct vent pipe diameter and length according to NFGC tables _________...

Страница 6: ...IF THE FURNACE IS A MULTI STAGE FURNACE WARNING USE ONLY WITH THE TYPE OF GAS APPROVED FOR THIS FURNACE REFER TO THE FURNACE RATING PLATE WARNING NEVER TEST FOR GAS LEAKS WITH AN OPEN FLAME USE A COMM...

Страница 7: ...AS ALL JOINTS SEAMS AND OPENINGS IN THE EQUIPMENT AND DUCT MUST BE SEALED TO LIMIT THE MIGRATION OF TOXIC FUMES AND ODORS IN CLUDING CARBON MONOXIDE FROM MIGRATING INTO THE LIVING SPACE IF AIR MOVING...

Страница 8: ...SITE SELECTION 1 Select a site in the building near the center of the pro posed or existing duct system 2 Give consideration to the vent system piping when se lecting the furnace location Be sure the...

Страница 9: ...PLACEMENT OF COMBUSTIBLE MATERIALS ON AGAINST OR AROUND THE FURNACE JACKET CAN CAUSE AN EXPLOSION OR FIRE RESULTING IN PROP ERTY DAMAGE PERSONAL INJURY OR DEATH THE HOMEOWNER SHOULD BE CAUTIONED THAT...

Страница 10: ...lbs MAY REQUIRE 3 TO 4 OR 3 TO 5 ADAPTER 4 ADAPTER INCLUDED WITH 801P UNITS MAY BE 0 WITH TYPE B VENT MAY BE 1 WITH TYPE B VENT LEFT SIDE REDUCED CLEARANCE IN SHIP WGTS FIGURE 4 UPFLOW HORIZONTAL DIME...

Страница 11: ...Where the maximum airflow is 1800 CFM or more BOTH sides or the bottom must be used for the return air Do not take return air from the back of the unit NOTE DO NOT take return air from furnace rooms g...

Страница 12: ...M FLANGES OF CABINET BEFORE THE UNIT IS INSTALLED LIFT UP PULL OUT 1 REMOVE 2 SCREWS LIFT BASE UP SLIDE FORWARD TO REMOVE 2 INSTALLATION IS REVERSE OF REMOVAL VERIFY REAR FLANGE IS SEALED PROPERLY AS...

Страница 13: ...ustion gases from an adjacent fuel burning appliance NOTE Do not block furnace access with support rods Main tain clearances recommended in Figure 8 Allow enough space for proper service maintenance o...

Страница 14: ...of all appliances in the space If the open space contain ing the appliances is in a building with tight construction contem porary construction outside air may still be required for the appliances to...

Страница 15: ...inch of free area for each 1 000 BTUH of total input in the space Table 2 shows some typical examples of openings required for com bustion air openings required for a confined space B USING OUTDOOR AI...

Страница 16: ...EACH OPENING WHEN TWO OPENINGS ARE USED WITH A FURNACE 1 LOCATED IN A CONFINED SPACE 2 USING OUTDOOR AIR FOR COMBUSTION 3 COMMUNICATING DIRECTLY TO THE 3 OUTSIDE THROUGH AN OPENING OR 3 THROUGH A VERT...

Страница 17: ...S IS NOT A REQUIREMENT SEE PREVIOUS PAGE SINGLE ELBOW IS ALLOWED BUT MAY NOT PREVENT DEBRIS FROM BEING DROPPED INTO THE FURNACE GROUND OR SHELF SURFACE 6 MIN 6 MININUM CLEARANCE PVC DOUBLE ELBOW 8 SCR...

Страница 18: ...attic must be ventilated by gable or soffit vents COMBUSTION AIR FROM ATTIC If attic combustion air is used the inlet air opening at the furnace must be protected from accidental blockage Install a 9...

Страница 19: ...and or the Natural Gas Installation Code CSA B149 1 2 for proper installation practices NOTE Follow combustion air instructions as outlined in this man ual Single wall vent connectors to B 1 vent or m...

Страница 20: ...not be greater than 75 percent of the vertical height of the vent Single appliance venting of a fan assisted furnace into a tile lined masonry chimney is prohibited The chimney must be lined with eith...

Страница 21: ...R cont FIGURE 18 DEDICATED VENTING THROUGH CHIMNEY WITH B 1 VENT Combustion Air FIGURE 17 FRESH AIR INLET ST A1220 09 01 1 STANDARD 3 FLUE CONNECTION 2 4 ADAPTER OPTIONAL SEE NATIONAL FUEL GAS CODE FO...

Страница 22: ...venting system NOTE Ensure existing venting system complies with latest addi tion of National Fuel Gas Code ANSI Z223 1 and all local codes regulations 1 Visually inspect the venting system for prope...

Страница 23: ...N AIR AND TENDS TO COLLECT AT LOWER LEVELS MAKING IT MORE DIFFICULT TO SMELL AT NOSE LEVEL NATURAL GAS IS LIGHTER THAN AIR AND WILL RISE POSSIBLY ACCUMULATING IN HIGHER PORTIONS OF THE STRUCTURE IF A...

Страница 24: ...3 feet to easily remove the control valve assembly Install a manual shut off valve in the gas line outside the furnace cas ing The valve should be readily accessible to turn the gas supply on or off I...

Страница 25: ...TION TITLED HIGH ALTITUDE INSTALLATIONS OF THIS BOOK FOR INSTRUCTIONS WARNING NEVER PURGE A GAS LINE INTO THE COMBUS TION CHAMBER NEVER USE MATCHES FLAME OR ANY IGNITION SOURCE FOR CHECKING LEAK AGE F...

Страница 26: ...With LP gas have the LP supplier adjust the line pressure at the regulator Manifold Gas Pressure Measurement Natural gas manifold pressure should be 3 5 w c for high fire and 1 8 w c for low fire LP g...

Страница 27: ...r and the gas supply to the furnace 2 Remove the burner door from the furnace 3 Remove the burner assembly handle with care 4 Remove the two screws attaching the NOx insert retainer bracket to the cen...

Страница 28: ...lly connected to line volt age prior to reversing the electrical connection 2 Disconnect the wires from the door switch 3 Remove the junction box from the furnace cabinet wall by re moving the two scr...

Страница 29: ...d be sized as shown NOTE Do not use 24 volt control wiring smaller than No 18 AWG Install the room thermostat in accordance with the instruction sheet packed in the box with the thermostat Run the the...

Страница 30: ...ach option humidifier or electronic air cleaner RXGW C01 4 INCH FLUE ADAPTER See Figure 26 Refer to Venting section of this manual for more information See National Fuel Gas Code for sizing options FI...

Страница 31: ...HE FURNCE AT THE LOCATIONS PROVIDED CUT OUT USING EMBOSSED ANGLES AS A GUIDE FOR PROPER SIZE 23 X 14 ST A1220 07 00 RXGF CB 6625 7 5 5 FIELD SUPPLIED FILTER ST A1220 06 X0 FIGURE 26 FILTER LOCATIONS A...

Страница 32: ...be adequate to provide correct airflow to each furnace for supply and return UT ELECTRONIC CONTROLS 1095 300 CONTROL BOARD 62 104059 01 1 Single Stage Operation a Control board ONE is on furnace conn...

Страница 33: ...33 TWINNING CONTROL BOARDS Twinning FIGURE 27 UT ELECTRONIC CONTROLS 1095 300 CONTROL BOARD TWINNING CONNECTION SINGLE STAGE OPERATION ST A1205 05 X0...

Страница 34: ...34 TWINNING CONTROL BOARDS cont Twinning FIGURE 28 UT ELECTRONIC CONTROLS 1095 300 CONTROL BOARD TWINNING CONNECTION ONE STAGE THERMOSTAT TIMED STAGING GAS HEAT OPERATION ST A1205 06 X0...

Страница 35: ...35 TWINNING CONTROL BOARDS cont Accessories FIGURE 29 UT ELECTRONIC CONTROLS 1095 300 CONTROL BOARD TWINNING CONNECTION TWO STAGE OPERATION ST A1205 07 X0...

Страница 36: ...Sea Level Heating Value 1050 Q 23 81 ft3 Natural Gas per hour From Table F 1 of Natural Fuel Gas Code Handbook 2002 3 5 w c column Orifice required at Sea Level 43 From Table F 4 of National Fuel Gas...

Страница 37: ...90 FURNACE MODEL NATURAL GAS ORIFICE SELECTION BASED ON HEATING VALUE ELEVATION Table is derived from Appendix of the National Fuel Gas Code To determine the correct orifice for your installation con...

Страница 38: ...e LP orifices are based on an 11 of water column pressure at the orifice which dif fers from products that use 10 of water column at the orifice This difference requires a deviation from the NFGC orif...

Страница 39: ...spark igniter is energized to light the gas burners and stays energized for the up to 7 seconds after the gas valve opens 5 8 seconds after the gas valve opens the remote flame sen sor must prove fla...

Страница 40: ...times in a row the control enters one hour lockout and fault codes 10 and 11 will be displayed alternately as described above 2 When flame is lost five times in a row the control enters one hour lock...

Страница 41: ...our period will commence after flame is no longer detected Dead Blower has been detected main limit circuit open for more than 150 seconds When voltage has unexpectedly been detected on the gas valve...

Страница 42: ...display orientation is with the control placed in a vertical orientation and the low voltage terminal block T2 is on the left Cool Blower Off Delay SW2 SW3 A means of selecting the cooling speed blowe...

Страница 43: ...r amber L E D is provided to indicate flame sta tus When normal flame is sensed the flame L E D is con tinuously on The flame L E D will flash at a rate of one to four flashes per second if a weak fla...

Страница 44: ...pressure Then replace the regulator cap securely Any necessary major changes in the gas flow rate should be made by changing the size of the burner orifices To change orifice spuds shut off the manual...

Страница 45: ...local gas utility to obtain the yearly average heating value and orifice size required to fire each individual burner at 25 000 BTU HR NOTE Refer to the High Altitude Section of this manual and the Na...

Страница 46: ...re needs to be adjusted Use lower speed tap on the multi speed blower IMPORTANT The measured temperature rise should be in the middle of the range IMPORTANT Some high efficiency filters have a greater...

Страница 47: ...050314MSA 80MDP050A30SA 1 3 11 x 6 802PA075417MSA 80MDP075B30SA 802PA100521MSA 80MDP100C40SA 802PA125524MSA 80MDP125D50SA 1 2 11 x 7 1 2 11 x 10 3 4 11 x 10 802PA150524MSA 80MDP150D50SA 3 4 11 x 10 Lo...

Страница 48: ...led to diagnose and or correct the source of tripping If this unit is mounted in a closet the door must be closed when making this check PRESSURE SWITCH This furnace is equipped with a normally open p...

Страница 49: ...nd through it to keep from overheating CAUTION DO NOT OPERATE THE SYSTEM FOR EXTENDED PE RIODS WITHOUT FILTERS A PORTION OF THE DUST ENTRAINED IN THE AIR MAY TEMPORARILY LODGE IN THE AIR DUCT RUNS AND...

Страница 50: ...replacement marking which can be obtained through the distributor if any are found to be illegible or missing REPLACEMENT PARTS Please visit www myrheem com myruud com for replace ment parts informati...

Страница 51: ...ected by registers fans sunlight heat through walls pipes or wires in walls Check heat anticipator setting Furnace may need an isolation relay Check installation instructions under section titled Isol...

Страница 52: ...52 Wiring Diagram FIGURE 34 FOR MODELS WITH UT ELECTRONIC CONTROLS 1028 928 INTEGRATED FURNACE CONTROL AND DIRECT SPARK IGNITION CM 0814...

Отзывы: