FLUEING
42
Warning:
Failure to fill with water may cause flue gasses to escape through the condensate trap. The
condensate trap should be regularly checked to ensure it is filled with water, replenishing when required.
Notes
AS/NZS 3500.4 section 5.12 is used as a guide in preparing the following drainage recommendations.
As the condensate is mildly acidic, copper tube and fittings must not be used as they will corrode.
Use UPVC (Unplasticised Polyvinyl Chloride) or PE (polyethylene) piping.
The outlet of the drain line must be in such a position that flow can be easily seen, but arranged so that
discharge will not cause injury, damage or nuisance.
The drain line must not discharge onto electrical connections, earth stakes, copper pipe, concrete paths
or into a pond.