SAFETY, WARNINGS, INSTALLATION NOTES
9
•
The water heater will operate until a water temperature of up to 75°C is
reached, depending upon the thermostat setting.
Refer to “How Hot Should The Water Be?” on page 12 and “Temperature
•
The lever on the temperature pressure relief valve and expansion control
valve (if fitted) requires to be operated every six (6) months to clear any
deposits and to ensure the valve and its drain line are not blocked.
Refer to “Relief Valves” on page 9 and “Minor Maintenance Every Six Months”
on page 16.
•
For continued safety of this water heater it must be installed, operated and
maintained in accordance with the Owner’s Guide and Installation
Instructions.
•
Servicing of a water heater must only be carried out by qualified personnel.
Phone Rheem Service or their nearest Accredited Service Agent.
•
Only a person qualified to install or service a water heater can drain the water
heater, if this is required.
RELIEF VALVES
Temperature Pressure Relief Valve
This water heater incorporates a temperature
pressure relief valve located near the top of the
water heater. This valve is essential for the
water heater’s safe operation.
It is possible for the valve to discharge a
quantity of water through the drain line during
each heating period. This quantity should be
equal to approximately 1/50 of the hot water
used, as water expands by this volume when
heated.
Expansion Control Valve
In many areas, including South Australia and
scaling water areas, it is mandatory an
expansion control valve is fitted to the cold
water line to the water heater.
The expansion control valve will discharge the quantity of water from its drain
line during the heating period instead of the temperature pressure relief valve as
it has a lower pressure rating.