background image

17040952—ENG 

 

4/12 

MAXIMUM

 

POWER

 ‐ By pushing the 

button 

again you 

enter the 
menu for 

setting 
maximum 

power. 

Here it is 
possible to 

limit the power level required for heating the 
environment. 

More details are given in the section ‘Thermo‐

regulation’. 
 

 

PARAMETERS

 

MENU

 ‐ Pushing the button 

again, enters the 

submenu

 

PARAMETERS

 

MENU

The 
parameters 

menu 

allows you 
to see the 

parameters 
of the air heaters and permits you to manage 

advanced functions. 

 

HEATING

 

MODE

 ‐ If you press 

, the control 

panel of the 

heating 
system 

appears 

  
 

 
 

The first row displays the icon illustrating the 

status of thermoregulation and the heaters and the 
number of heaters or slaves connected. 

The second row gives additional information about 
the status of heaters or anomalies. The third line, if 

available, shows the value of outdoor temperature 

or errors related to thermoregulation environment. 
 

This menu has a fixed frame. The options 
previously seen remain displayed for 20 seconds, 

then the display returns to the main screen. In this 

option however if the user does not push ESC or 
the 



buttons, the chronothermostat continues 

to show the control panel with the relevant 

information. 
 

AUTOMATIC

 

MODE

 ‐ By 

pressing the 

button 

again, you 

return to the 
first option. 

In case the automatic mode is already active, it 

does noet matter whether you push NO or OK. 
 

SETTING

 

MENU

 

 

Programming

 

This submenu 
allows you to 

manage 

temperature 
control 

environment, 
weekly program, time setting and language choice. 

 

Selecting the option 

‘Programming’

 you enter the 

weekly program 

submenu. 

 
Choosing the 

option 
‘Temperature’ 

you enter in the 

menu of the 4 
temperature levels T0, T1, T2 & T3. 

 
Push the buttons 

 and 

 to select the temperature 

level – to vary the temperature value use the 
b and ‐. 

 

The right side of the screen shows the relative 
position of the current temperature setpoint with 

respect to minimum (5°C) and maximum (30°C) 
values. 

The highest temperature is associated with T3 and 

the lowest temperature with T0, the chrono‐
thermostat meets the following constraint : 
T0

T1

T2

T3 and automatically resizes the 

temperatures. 

 

Choosing the 
option ‘Day 

program’ it 
takes you to 

following 

screen : 
 

 
At the top of the screen you select the day and at 

the bottom of the screen  the day program is 

displayed. Pressing the + and ‐ buttons you can 
select the day.  

 
For example, 

suppose you 

want to 
program the 

day "Monday",  
pressing OK 

button you 

enter the 
scheduling of time slots.  

The time slots  are programmed in three steps: 

initial time, temperature and final time. 
 

Содержание Kronos GA11

Страница 1: ...imum at 40 C Power sypply low voltage 3V via communication with control board of the air heater Protection degree IP30 Dimensions 140x90x32mm Compliance directive 2004 108 CE EMC directive 2006 95 CE LVD INSTRUCTIONS FOR USE The buttons have any versatile utilization depending on the selected menu The use of buttons is facilitated by the indications with text icons and other graphics that appear o...

Страница 2: ...e function of the active thermoregulation automatic manual summer or standby Automatic Temperature control environment according to the weekly program set by the user Program seen as a graph of the current day Manual Temperature control environment in accordance with user selected temperature thermostat function Summer Temperature control environment disable Summer ventilation can be activated man...

Страница 3: ...ng the button again the standby menu appears The standby mode allows you to turn off the system temperature control environment ventilation are disabled The first level menu is circular meaning that all screens are accessible by pushing the OVERTIME MODE Continuing and pushing the button again you can choose to activate the operating mode Overtime In operating mode Overtime the room thermoregul at...

Страница 4: ...ormation AUTOMATIC MODE By pressing the button again you return to the first option In case the automatic mode is already active it does noet matter whether you push NO or OK SETTING MENU Programming This submenu allows you to manage temperature control environment weekly program time setting and language choice Selecting the option Programming you enter the weekly program submenu Choosing the opt...

Страница 5: ... method used by the chrono thermostat for controlling room temperature This menu allows you to set the differential which can vary between 0 2 º C and 5 0 º C default value 2 0 º C d is the thermal differential Max is the maximum rate Ti and Ta stand for respectively room temperature set and room temperature measured The required percentage P is calculated as follows if Ta Ti d then P Max if Ti d ...

Страница 6: ...the function of reading and writing of TSP To change a TSP you must select the index idx desired using the and keys and push the SET button After that following screen appears where you can enter with the and buttons the desired value In the event that the board does not include the writing of this TSP read only the changes made to it will have no effect The number of TSP depends on the control bo...

Страница 7: ... Read slave The last item Read Slave of the PARAMETERS MENU you can view the percentage the value of the respective temperature probe of power and the LC1 temperature of hot air generators You are shown a number of rows corresponding to the number of slaves connected up to a maximum of 10 slaves In addition pushing from the main screen simultaneously the buttons 5 and 6 shown below in any operatin...

Страница 8: ...heir charging status WARNINGS ABOUT THE BACKLIGHT The display backlight is obtained from the reserve described in the previous paragraph It is possible therefore that in case of newly connected chronothermostat the brightness is minimal or absent because of insufficient internal charge this must not alarm as they are just a few hours of connection because the backlight to begin to be efficient You...

Страница 9: ...e of temp 0 C eg value 20 pas de ven l value 20 C vent P05 Offset_EF_MAX 0 50 0 To reduce maximum speed venter motor factory setting Example Max speed 7200 RPM P05 25 Max speed 7200 1 0 25 5400 RPM P06 Offset_EF_MIN 0 200 0 To increase minimum speed venter motor factory setting Example Min speed 1350 RPM P06 50 Min speed 1350 1 0 5 2025 RPM P07 0 10V threshold 0 5 5 0 1 0 V Setting threshold value...

Страница 10: ...working even when it is in off state wiring problem J11 signal 2 3 4 5 J11 signal 4 is broken bad print can be bad venter motor venter can also be in thermal lockout wait 1hour and try again 27 SR opened or not connected forced purge LC1 open or not connected 60 Parasite flame forced purge Sperious flame at start up you don t get lockout only if this stays for 10s this will change to error 15 81 I...

Страница 11: ...by GA11 Option 4 no additional setting required 1 GA11 for 4 units unit 1 no additional sensor unit 2 additional sensor unit 3 no additional sensor unit 4 no additional sensor unit 1 control through set point room temperature by GA11 unit 2 control through set point GA11 and room temperature SA temperature sensor unit 3 control through set point room temperature by GA11 unit 4 control through set ...

Страница 12: ...A temperature sensor unit 3 controlled through setpoint GA11 and room temperature SA temperature sensor unit 4 controlled through setpoint GA11 and room temperature SA temperature sensor Example Setpoint GA11 25 C Room temperature GA11 24 C is van geen belang SA unit 1 23 C SA unit 2 25 C SA unit 3 23 5 SA unit 4 22 C diff 2 C unit 1 is working at 100 unit 2 is working at 0 unit 3 is working at 75...

Отзывы: