background image

2.9 Burner position

The burner must conform to the local stand-

ards and legislations in place.

The RIELLO-burner has been designed to 

operate in the position shown in Figure 

11, the positions shown in Figure 12, won't 

allow the air damper to close when the 
burner is on standby.

Figure 11. 

Correct burner position

Figure 12. 

Incorrect burner position

2.10 Gas Installation/connection

WARNING

The installation must be purged and tested 

for soundness prior to commissioning. 

Always ensure that appropriate personal 

protective equipment is used

Service pipework must terminate at an 
approved isolating valve, and be adjacent 
to the position of the heater. The connec-
tion to the heater can be made by way of 
either an approved flexible coupling, or 
rigid connection. Threaded connections 
must comply with ISO288/1 of ISO 7/1, 
further information concerning the accepted 
practice in European countries is detailed 
in EN 1020. 

The diameter of the pipework from the 

isolating valve to the burner connection 
must not be less than the diameter of the 
burner connection inlet. 

2.11 Oil Installation/connection

WARNING

Prolonged exposure and contact with gas 

oil can result in the natural oils being 

removed from the skin, sensitisation can result in 
dermatitis.

Always ensure that the appropriate personal 

protective equipment is used.

2.12 Fuel supply

WARNING

Galvanised or plastic pipe work and fittings 

must not be used. (See BS 5410 Part 1)

The constraints of the application will, to a 
large extent, determine whether it is prefer-

able to use a single pipe gravity feed system, 
or whether the two pipe pumped system is 
more appropriate. Where more than one 
appliance is to share a common supply it 

will be necessary to use a pressurised ring 

main system.

All pipe work must be constructed and 

installed so that it does not permit the 
ingress of air. The construction, size, and 
position of the oil storage tank must take 
account of the current regulations, as well as 
suiting the requirements of the installation.

CAUTION

On pumped systems always check that the 

pump is correctly set up prior to operation.  
Ensure that valves are open allowing a 
free flow of oil through the system.

In order to promote trouble free operating it 
is necessary that the oil within the storage 
tank and oil line does not fall below the 
cold filter plugging point (cfpp), in the UK 
and with class D fuel (also referred to as gas 
oil). The critical temperature is -4°C for this 
summer grade.

The cfpp critical temperature for the winter 

grade is -12°C. If summer grade fuel is stored 
for winter use in areas prone to severe frosts 
and low temperatures it will be necessary 
to insulate or even heat the supply tank and 
pipe work.

Note: 

The fuel supplier should be contacted prior to 

installation so that any requirements concerning delivery, 
transport, storage and use can be addressed before work 

commences.

14

Содержание FSE 100

Страница 1: ...es in force All external wiring must comply with the codes of practice or rules in force in the country of installation Improper installation adjustment alteration service or maintenance can cause pro...

Страница 2: ...cluding children with reduced sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person resp...

Страница 3: ...ion 14 2 10 Gas Installation connection 14 2 11 Oil Installation connection 14 2 12 Fuel supply 14 2 12 1 Storage tank 15 2 13 Pipe work and fittings 15 2 14 Packaging 18 2 15 Flooring 18 2 16 Electri...

Страница 4: ...the instructions of this manual for the consequences of any operations carried out and not specifically provided for or for translations open to misinterpretation The electrical system must feature su...

Страница 5: ...en subject to and affected by the ingress of water in any form The heater is not operated at the rating s laid down in the manufacturers technical specifications The heater has not been operated or us...

Страница 6: ...level surface made from non combus tible material which is sufficiently robust to withstand the weight of the heater and any ancillary equipment 1 6 General requirements WARNING Unauthorised modifica...

Страница 7: ...ety thermostat factory calibration 80 C has the function of interrupting the burner operation in case of abnormal overheating of the air It is automatically reset It shall be correctly calibrated when...

Страница 8: ...mm nom FSE 40 600 770 1500 145 130 5 FSE 60 650 950 1650 225 150 6 FSE 75 650 950 1650 245 150 6 FSE 100 800 1200 1900 310 180 7 FSE 145 800 1200 1900 345 180 7 FSE 175 1000 1500 2150 485 205 8 FSE 22...

Страница 9: ...V 93 5 93 1 93 6 93 2 94 3 94 5 93 1 94 5 Gross flue gas temperature 2 C 155 155 155 155 140 140 155 140 Combustion chamber pressure Mbar 0 1 0 4 0 5 0 6 0 7 0 5 0 6 1 5 Heat output 1 kW 28 0 38 2 52...

Страница 10: ...useful efficiency el max At nominal heating capacity el min At minimum heating capacity el sb In stand by mode F env Envelope loss factor P ign Ignition burner consumption NOx Nitrogen oxide emission...

Страница 11: ...ould Be placed on a flat surface capable of bearing its weight Be supported over the entire perimeter of the lower base Be placed on a surface whose deflection and strength is such that it can prevent...

Страница 12: ...the system 2 5 Flue gas discharge Flue gas exhaust connection position and example of connection to the flue Condensate discharge fitting is necessary to prevent any condensate that has formed in the...

Страница 13: ...the ducts of the air inlet circuit to the side opening the appliance is set up for both right and left connections To change the air inlet side simply swap the grille and blanking panels around To att...

Страница 14: ...uel supply WARNING Galvanisedorplasticpipeworkandfittings must not be used See BS 5410 Part 1 The constraints of the application will to a large extent determine whether it is prefer able to use a sin...

Страница 15: ...pump is running the oil pressure can be increased sufficiently so as to cause damage to the seals within the pump The return oil should be discharged pref erably through an elbow onto a tank plate si...

Страница 16: ...ails 40 175 gravity feed from the bottom of the tank Table 7 Dimensions 1 Gate valve 2 In line filter 3 Pump 4 Relief valve 5 Pressure gauge 6 Pressure reducing valve 7 Return to tank Filler Maximum 4...

Страница 17: ...P should not exceed 4 metres to avoid damage to the pump seals The pump suction should not exceed a maximum of 4 metres Beyond this limit gas is released from the oil Oil lines must be completely air...

Страница 18: ...mally insulated Where ducting may be subject to deterio ration from exposure to moisture or high humidity material selection and insulation are prime considerations Joints and seams must be airtight a...

Страница 19: ...ture C 22 6 22 4 17 17 3 22 2 21 6 20 8 21 8 24 23 2 24 3 24 7 22 21 3 22 7 23 3 Td C 10 2 10 1 6 3 6 4 8 7 8 4 11 5 11 7 13 7 13 2 14 3 14 3 9 1 8 9 6 2 6 7 Smoke number No 0 0 1 1 1 0 0 0 0 0 3 Burn...

Страница 20: ...nection of the power supply phase neutral In any case make sure that the direction of rotation of the fans is correct The unit must be connected to an efficient earthing system The manufacturer shall...

Страница 21: ...10 M2 Fan motor if present 11 FAN thermostat 12 LM Manual reset safety thermostat 13 TR Automatic reset safety thermostat 14 F1 Fuse 15 BM Single stage burner terminal block 16 BP1 Double stage burne...

Страница 22: ...10 M2 Fan motor if present 11 FAN thermostat 12 LM Manual reset safety thermostat 13 TR Automatic reset safety thermostat 14 F1 Fuse 15 BM Single stage burner terminal block 16 BP1 Double stage burne...

Страница 23: ...Before resetting the device please verify that the issues have been resolved before continuing operation If confused please contact manufacturer for further clarification 3 4 1 Ventilation Heating Op...

Страница 24: ...each motor must be adjusted and its electrical absorption must be checked To change rpm of the fan perform the following operations Relax the belts tension by unloosing the screw 1 Remove the belt 4...

Страница 25: ...rance of 10 C Make sure that the manual resetting safety thermostat calibration is correct Check that the temperature near the safety thermostat is correct ambient temperature air temperature Check th...

Страница 26: ...pressed on both sides with the hands it should bend between 20 30 mm To manage the tension operate the two belt stretching bolts Thermostat safety check Check functionality of the safety thermostat a...

Страница 27: ...able burner via controller by selecting Heat Relay 2 Heat On Heat Auto This is dependent on control type supplied Refer to individual controller operating manual Burner will fire and establish within...

Страница 28: ...7 Electrode 3008930 3008931 3008930 3008931 3008930 3008931 3008931 3008932 Probe 3007987 3007988 3007988 3007988 3007988 3007988 Propane conversion kit 30 00 882 30 00 884 30 00 884 30 00 886 30 00 8...

Страница 29: ...Notes 29...

Страница 30: ...Notes 30...

Страница 31: ...Notes 31...

Страница 32: ...olmore Circus Queensway Birmingham West Midlands B4 6AT AFFIX AGENTS DETAILS HERE This document replaces the previous Manual Part No Reznor FSE EN Oct 18 D301160 Issue B Current full Part No Reznor FS...

Отзывы: