20/25
9.3 Limit Control Fault Finding Chart (limit control trips)
Note
LCSA-4 air heaters are equipped with 2 limits (a recycling limit and a manual reset limit). During normal operation, neither limit should
trip even if the main electric supply is interrupted during operation. In the event of motor failure, the recycling limit will trip opening the gas
valve.
yes
no
yes
yes
no
yes
no
no
yes
yes
no
Check for excessive
main burner pressure
Does the fan
motor operate?
Remove the
restricition
Has any non-factory authorized air distribution
device been placed on the heater? Is there excessive
static pressure in the ductwork? Did the motor overload
trip?
Does the fan control
energize the fan motor
in less than 75"?
Adjust thermostat
temp. setting above
ambient to energize fan
& gas solenoid valve
Replace
the motor
Consult fan
fault finding
Does the limit trip
before the fan is
energized?
Place system in normal
operation
Consult fan
fault finding
Is there 220-240V at
terminals N and 4?
9.4 Fan Fault Finding Chart
no
no
yes
yes
Adjust thermostat
temperature
setting above ambient to
energize the fan and the
fan solenoid valve
Does the fan
operate ?
Is there 220-240V
at terminals N & 4?
Replace the
fan start relay
Replace fan
motor
Place the system
in normal operation