II&E2020_11
Hi-Finity electric lock: Installation and testing
– Manual for the installer & electrician 15
3.3.3 Change operandi modus
!
Warning: Do not lock yourself out. Check if a 2
nd
entrance into the building is available
when changing the settings.
By default the lock will not drop down when the vent is in closed position : this is a safety modus for
balconies where only 1 entrance to the building is possible. The drop bolt will go down when a
pulse is triggered. LED feedback will show if this is done or not.
By default the LED will be off when the vent is in locked position. The LED will be on when the vent
is open. When the lock should lock, but is not yet locked because the magnet is not yet into place,
the LED will blink.
When it is required to
lock each time
the vent is back in closed position, follow the next procedure:
Take out the lock and R-Switch box
Unplug all wires on the R-Switch box
Unscrew the electronic board (PCB) from the housing.
Take out the PCB
Switch over the
dip-switch1
in the centre of the board
to “ON”.
Assemble the part again.
When it is required to
invert the functionality of the LED
, follow the next procedure:
Take out the lock and R-Switch box
Unplug all wires on the R-Switch box
Unscrew the electronic board (PCB) from the housing.
Take out the PCB
Switch over the
dip-switch2
in the centre of the board to “ON”.
Assemble the part again.
3.4 Testing
Now that the complete installation has been finished, perform a final Open/Close test,
using the button.