![REXROTH HCS02.1 Series Скачать руководство пользователя страница 42](http://html1.mh-extra.com/html/rexroth/hcs02-1-series/hcs02-1-series_project-planning-manual_1449567042.webp)
6-2
Electrical Data
Rexroth IndraDrive C
DOK-INDRV*-HCS02.1****-PR02-EN-P
6.2
Power Section – DC Bus
Designation
Symbol
Unit
HCS02.1E-
W0012
HCS02.1E-
W0028
HCS02.1E-
W0054
HCS02.1E-
W0070
DC bus voltage (range) (unloaded)
U
DC
V
uncontrolled
U
LN
* 1.41
internal DC bus capacity
C
DC
mF
0.135
0.270
0.405
0.675
max. allowed external DC bus
capacitance
1)
C
DCext
mF
-
5
7
13
limitation of inrush current
charging via resistor; N/O contact:
min. 250.000 witching actions
continuous power soft-start resistor
P
DC(Start)
kW
0.05
0.15
0.35
0.5
max. DC bus charging energy
W
MAX
kWs
1
5
9
13
storable energy of the internal
DC bus capacitors at 3AC400V
W
DC
Ws
19
38
57
95
lower DC bus voltage limit
U
DC limit (min)
V
200
see also Functional Description of firmware
upper DC bus voltage limit (cut-off
threshold)
U
DC limit (max)
V
900
capacitance in DC bus against
ground; between L+ and L-
C
Y
nF
100
100
100
100
balancing factor for P
DC cont
(for parallel operation with common
DC bus)
with / without mains choke:
-
-
0.8 / 0.5
0.8 / 0.5
0.8 / 0.5
rated power at U
LN
= AC400V
without mains choke
minimum inductance of mains
supply
P
DC_cont
L
min
kW
uH
2.1
40
5.1
40
7.0
40
9
40
rated power at U
LN
= AC400V,
with mains choke
P
DC_cont
kW
2.1
5.1
10
14
1)
using additional capacitances at the DC bus requires mains choke
Fig. 6-2:
Data power section – DC bus
Содержание HCS02.1 Series
Страница 6: ...IV Contents Rexroth IndraDrive C DOK INDRV HCS02 1 PR02 EN P...
Страница 32: ...4 4 Identification Rexroth IndraDrive C DOK INDRV HCS02 1 PR02 EN P Notes...
Страница 96: ...10 4 Index Rexroth IndraDrive C DOK INDRV HCS02 1 PR02 EN P...
Страница 97: ......