(4) Error / Warning information: Error / Warning code will be displayed in this
sector. Please refer to
chapter 10 "Diagnosis" on page 49
.
(5) Permanent monitoring: By default, its display as "Actual output frequency" is
set by parameter U2.09. Value and unit of parameter will be displayed.
(6) Panel Locked / Unlocked: Panel can be locked by the following ways:
●
Setting [U2.02] to '1', or
●
Pressing Func button with Loc button for longer than 3 s.
Panel can be unlocked by the following ways:
●
Setting [U2.02] to '0' (only in communication mode), or
●
Pressing Func button with Loc button for longer than 3 s.
Stop button is used to reset error, Run button is not used in brake
chopper.
8.2.2 Operating Example
Please follow the steps below to set parameter [b0.10] to '1: Restore to default
settings' through LCD panel.
1. Press Func button.
2. Rotate Rotary encoder to select parameter group b0.
3. Press Rotary encoder and rotate it to select parameter b0.10.
4. Press Rotary encoder and rotate it to select parameter value '1: Restore to
default settings'.
5. Press Rotary encoder to finish setting.
8.3 Dust Cover
Fig. 8-4: Dust Cover
The dust cover is standard accessory.
Bosch Rexroth AG
Operating Panel and Dust Cover
Brake Chopper
40/65
DOK-RCON03-EFC*BRAKE**-IT01-EN-P