REFUdrive 500 RD51
Basic parameterization
5-7
DOK-RD500*-RD51*******-IB01-EN-P
Parameter
No.:
Name
Description / Explanation
selectable options
Factory setting
min ... max values
Pass-
word
0265.XX
Fixvalue main s/p
Supplementary parameter for “fixed setpoint”.
5.00 %
1
Parameter P0390 is the limit for frequency setpoints and
actual values.
P0390 is set to 50 Hz in the factory . In order to operate the
motor with 50 Hz, a setpoint of 100% must be entered.
XX = In parameters P0875, P0876; P0877;P0878, P0879 or
P0880 (Function: setpoint memory Bits 20 ... 23) the
index is selected, in which a value can be saved.
-199.99 ... 199.99 %
0297.00
Analog input window
Supplementary parameter for “analog input”.
0.50 %
1
The analog setpoint smoothing is specified in a window width
in %.
e.g. window width = 1 %. An actual setpoint change is only
transferred, if a change exceeding 0.99% of the possible end
value is identified at the analog input.
0.00 ... 20.00 %
0200.00
Analog input 1 norm.
Supplementary parameter for “analog input”.
100 %
2
The analog input normalization refers to the frequency nor-
malization P0390.
-199.99 ... 199.99 %
0202.00
Analog input 1 offs.
Supplementary parameter for “analog input”.
0.00 %
2
Analog input offset
-199.99 ... 199.99 %
0203.00
Analog input 1 sign
Supplementary parameter for “analog input”.
direct
2
Analog input signal
0 = direct
1 = absolute value
2 = inverted
3 = abs. value inverted
0 ... 3
0204.00
Analog input 1 filtr.
Supplementary parameter for “analog input”.
2 ms
2
Analog input, filter time to smooth the analog signal.
0 ... 10000 ms
0564.XX
Reaction on I < 4mA
Supplementary parameter for “analog input” 4...+20 mA“.
warning
2
Response for „I < 4 mA“
0 = no reaction
1 = warning
2 = fault
XX = 00 for STANDARD mode
XX = 01 for TEST mode
0 ... 2
0179.XX
V/f character. Fmax
100.00 %
2
XX = In the parameters P0875, P0876; P0877; P0878;
P0879 or P0880 (Function: setpoint memory bits 20 ...
23) the index is selected, in which a value can be
saved.
P0180 ... 199.99 %
0180.XX
V/f character. Fmin
0.00 %
2
XX = In the parameters P0875, P0876; P0877; P0878;
P0879 or P0880 (Function: setpoint memory bits 20 ...
23) the index is selected, in which a value can be
saved.
0.00 % ... P0179
0036
Braking resistor
REFU standard
1
Selects the connected brake resistor at power terminals C
and F.
0 = REFU standard
1 = disabled
2 = no protection
3 = external programable
Note: REFU
reduc drive converters supports no braking re-
sistor! Parameter 0036 must be set to 1 = disabled!
0 ... 3
0623.00
Ext. BR: Resistance
Supplementary parameters for brake resistor (P0036)
„external programmable“
199.9 W
2
This value should be taken from the rating plate of the brake
resistor.
0.1 ... 199.9 W
0624.00
Ext. BR: Rated power
Supplementary parameters for brake resistor (P0036)
„external programmable“
1.0 kW
2
This value should be taken from the rating plate of the brake
resistor.
0.1 ... 199.9 kW