200W 200W 1600W 200W 1600W 900W
Safty notes
• Installation of these products should only be undertaken by a qualified electrician.
• The operational and electrical safety is only guaranteed, if the product is installed using its proper
accessories, in a position as specified in the installation instructions.
• Any interference with the product makes the guarantee void.
• If the time switch is mounted near equipment where heat produced raises the local ambient above 55°C. Then a space should be put
between the time switch and the equipment.
Function
The MicroRex D22 is a microprocessor controlled digital time switch. Eight programs of your choice can be stored and used to control the automatic operation of your electrical equipment. Each indi-
vidual weekday can have a separate program or you can have several days operating on the same „Block“ program. To program the MicroRex D22 a „picture“ is used and when this is complete the
chosen times are stored in the microprocessor memory. The MicroRex D22 makes available 2 separate switching channels. The summer-/winter changeover can be programmed for hand or automa-
tic operation.
State of output
= On
= Off
±
1h C
S OK
R
1
2
Hand switch
Channel 1
Channel 2
Choose function
Summer- / winter
changeover
Setting the hours, minutes,
days and channels
Delete
Fixing the hours, minutes,
days, channels and
continuous switching
Programming Buttons
1
2
1 2 3 4 5
6 7
Actual or „On“ time
Weekday
Day number
„Off“ time
Symbol for
„Set actual time“
„Off“ days
Liquid Crystal Display
Technical data
Supply voltage:
230V 50/60Hz
120V 50/60Hz
Consumption:
ca. 0,6W
Contact rating:
2 changeover contact 10A 250V~µ cos
ϕ
= 1
Parallel compensation: not allowed
Accuracy: ±2,5s/d
Terminal capacity:
single strand
multi strand
4 mm
2
2,5 mm
2
Program pictures:
8
Battery reserve:
100h
Storage ambient:
-10°C to +60°C
Working ambient:
-10°C to +55°C
Time switch
NT 29 17 87 02
MicroRex D22
S
OK
+
Presentation
Approximately 30 seconds after the supply voltage is connected the symbols
appear on the LCD.
Before any operations the complete memory must be reset.
2. Memory reset
1. Starting
This can only be done after a Reset.
Summer- / winter changeover can be made manually or automatically if set.
If manual changeover is required choose no during the date input. Automatic changeover
depends on your country / area. Choose the appropriate setting for your country / area.
3. Setting date and summer- / winter changeover
L
N
6 7 8
3 4 5
1 2
Connection
press both at
the same time
The time switch memory is completely clear.