background image

6

CIRCULATING AIR REQUIREMENTS

 WARNING:

All return ducts must be secured to the furnace 

with sheet metal screws. All return ducts must 

be adequately sealed. When return air is provided 

through the bottom of the unit, the joint between 

the furnace and the return air plenum must be 

air tight.
return air and circulating air ducts must not be 

connected to any other heat producing device 

such as a fireplace insert, stove, etc. This may 

result  in  fire,  explosion,  carbon  monoxide 

poisoning, personal injury, or property damage.

Plenums & Air Ducts

This unit is designed only for use with a supply and return 

duct. Air ducts should be installed in accordance with the 

standards of the National Fire Protection Association 

Standard for Installation of Air Conditioning Systems 

(NFPA 90A), Standard for Installation of Residence Type 

Warm Air Heating and Air Conditioning Systems (NFPA 

90B), and all applicable local codes. NFPA publications 

are available by visiting www.NFPA.org.
•  Plenums and air ducts must be installed in accordance 

with the Standard for the Installation of Air Conditioning 

and Ventilating Systems (NFPA No. 90A) or the 

Standard for the Installation of Warm Air Heating and 

Air Conditioning Systems (NFPA No. 90B).

•  Design the air ducts according to methods described 

by the Air Conditioning Contractors of America 

(ACCA).

•  Air  ducts  must  be  aluminum,  tin  plate,  galvanized 

sheet steel, or other approved materials for outlet or 

return air ducts.

•  Snap-Lock or Pittsburgh-Lock seams are preferred. All 

other types of seams must be made tight to prevent 

leakage.

•  It  is  good  practice  to  seal  all  connections  and  joints 

with industrial grade sealing tape or liquid sealant. 

Requirements for sealing ducts vary from region to 

region. Consult with local codes for requirements 

specific to your area.

•  Gas piping must not run in or through any of the air 

duct system.

•  Applicable installation codes may limit the furnace to 

installation in a single-story residence only. Furnace 

installations other than closet or alcove require ducted 

return air systems.

Return Air Connections

Air return to the furnace must have a minimum free area 
opening. See 

Table 1 (page 5)

. A return air grille for 

closet or alcove installations is available. Acceptable 

closet installations with return air entering through an 

opening in the floor or ceiling of a closet, must meet all 

of the following requirements:

•  The return air opening, regardless of its location in the 

closet, must not be smaller than size specified on unit 

data label. If located in the floor, the opening must be 

provided with a means of preventing its inadvertent 

closure by flat object(s) placed over the opening.

•  A  return  air  grille  must  be  used  when  furnace  is 

installed in a closet or alcove:

  Alcove installations: use return air grille & frame 

assembly P/N 902989 or equivalent. See 

Figure 2 

(page 7)

.

  Closet installations: use wall mount return air grilled 

P/N 902999 or equivalent. 

NOTE: For 5 ton A.C. or 

H.P. system, 155 in

2

 (1,000 cm

2

 ) must be added.

  Downflow alcove installations: the grille (with frame 

provided) may be attached to the top of the furnace 

and all paneling and trim flushed to it. This installation 

provides an access door for future installation of air 

conditioning or heat pump coils on top of the furnace.

•  Materials located in return air duct system must have 

a flame-spread classification of 200 or less.

•  Noncombustible  pans  having  1”  upturned  flanges 

must be located beneath openings in a floor-return 

duct system.

•  Wiring  materials  located  in  return  duct  system  must 

conform to NEC Article 300-22(c).

•  If return air opening is located below top of furnace, 

a minimum clearance must be provided between 
opening and furnace. See 

Table 1

.

Supply Air Connections

•  Supply duct system must be designed for proper air 

distribution. Static pressure measured externally to 

furnace shall not exceed static pressure rating listed 

on furnace nameplate.

•  Duct  system  must  be  designed  so  that  no  supply 

registers are located in duct system directly below the 

furnace.

Acoustical Ducts

Certain installations may require the use of acoustical 

lining inside the supply duct work.

•  Acoustical  insulation  must  be  in  accordance  with 

the current revision of the Sheet Metal and Air 

Conditioning Contractors National Association 

(SMACNA) application standard for duct liners.

•  Duct lining must be UL classified batts or blankets with 

a fire hazard classification of FHC-25/50 or less.

•  Fiber duct work may be used in place of internal duct 

liners if the fiber duct work is in accordance with the 

current revision of the SMACNA construction standard 

on fibrous glass ducts. Fibrous duct work and internal 

acoustical lining must be NFPA Class 1 air ducts when 

tested per UL Standard 181 for Class 1 ducts.

Содержание RE9X-10N4

Страница 1: ... OU D EXPLOSION Le non respect des avertissements de sécurité pourrait entraîner un fonctionnement dangereux de l appareil des blessures graves la mort ou des dommages matériels Unentreteinincorrectpourraitentraînerunfonctionnement dangereux de l appareil des blessures graves la mort ou des dommages matériels Couper toute alimentation électrique au générateur d air chaud avant de prodéder aux trav...

Страница 2: ...for Downflow Systems 8 Furnace INstallATION 8 General Information 8 Before You Install this Furnace 8 Locating the Unit 8 Locating Cutting Floor Openings 9 Standard Duct Connector Installation 10 Narrow Duct Connectors 10 Round Duct Connector Installation 11 Alcove Installation 11 Closet Installation 11 Upflow Furnaces 12 Over the Floor Return Air System Non Ducted 12 Through the Floor Return Air ...

Страница 3: ...UTO in place of the HEAT and COOL Others may include all three Please refer to the thermostat manufacturer s User manual for detailed programming instructions NOTE Allow at least one hour for the room temperature to stabilize before you make a second adjustment to the thermostat setting After the desired comfort level is established makeonlysmalladjustmentstothethermostat setting to meet changing ...

Страница 4: ...s frequently and replace when necessary with filter of same dimensional size Filters designed to remove smaller particles such as pollen may require additional maintenance Coil Filters If a cooling coil is installed on your unit the furnace filter is not used Remove coil filters wash and allow to dry Re install coil filters to their original positions Blower Compartment Dirt and lint can create ex...

Страница 5: ...ings or structures under construction Minimum Installation Clearances Access for positioning and servicing the unit must be considered when locating unit The need to provide clearance for access to panels or doors may require clearance distances over and above the requirements For alcove installations allow 18 46cm inches minimum clearance from the front of the unit for future servicing Closet ins...

Страница 6: ...r entering through an opening in the floor or ceiling of a closet must meet all of the following requirements The return air opening regardless of its location in the closet must not be smaller than size specified on unit data label If located in the floor the opening must be provided with a means of preventing its inadvertent closure by flat object s placed over the opening A return air grille mu...

Страница 7: ...ngtheoptionalcoilcabinet Figure3 isrecommended The duct system must be properly sized to account for any additional external static pressure produced from the chosen filtering method NOTE Install a filter with a minimum unrestricted medium area of 324 in2 in the duct above the coil that is accessible for monthly cleaning or replacement by homeowner Filtering Methods Upflow Furnaces Non Ducted Retu...

Страница 8: ...This appliance will provide many years of safe and dependable comfort providing it is properly installed and maintained Abuse improper use and or improper maintenance can shorten the life of the appliance and create unsafe hazards Please read all instructions before installing the unit Approved installation operation and maintenance of this appliance must be in accordance with the listed specifica...

Страница 9: ...CUT OUT 14 1 4 DIAMETER FOR UPFLOW FURNACES WITH ROUND DUCT CONNECTORS C L STANDARD DUCT CONNECTOR ROUND DUCT CONNECTOR Locating Cutting Floor Openings Floor cut outs must be carefully located to avoid misalignment of the furnace and air duct Standard and round cutouts for upflow furnaces are shown in Figure 5 The cutouts for downflow furnaces are shown in Figure 6 1 Measure and mark the centerlin...

Страница 10: ... FOLD FLAP HERE REMOVE THIS FLAP REMOVE THIS FLAP C U T H E R E C U T H E R E C U T H E R E C U T H E R E CUT HERE CUT HERE CUT HERE CUT HERE CUT HERE FOLD FLAP HERE FOLD FLAP HERE Figure 9 Duct Connector Tabs DUCT CONNECTOR SUPPLY AIR DUCT BEND TABS TIGHTLY AGAINST SUPPLY AIR DUCT MOUNTING PLATE DUCT CONNECTOR CONNECTOR TABS SUPPLY AIR DUCT WOOD FLOOR Figure 8 Standard Duct Connector Installed NO...

Страница 11: ...s between 1 5 requirements are a louvered door with a minimum of 250 in2 1613 cm2 free area Afullylouveredclosetdoorisstronglyrecommended forbothinstallationtypes Forclosetinstallations thereturn air grille mounting frame is not used since the furnace is located inside the closet For examples of both types of installations see Figure 14 page 12 1 Cut return air opening in desired position in door ...

Страница 12: ...3 3 Route 240V supply circuit s and 24V wiring to closet See Figure 20 page 17 for appropriate locations 4 Position optional coil cabinet onto upflow stand or mounting platform and secure with three or more fasteners 5 Position furnace in upflow mode onto coil cabinet and secure with two or more fasteners 6 Use optional upflow duct connector or field supplied connector to attach furnace to overhea...

Страница 13: ...result in dangerous operation serious injury death or property damage Before servicing disconnect all electrical power to furnace When servicing controls label all wires prior to disconnecting Reconnect wires correctly Verify proper operation after servicing AVERTISSEMENT RISQUE DE CHOC ÉLECTRIQUE D INCENDIE OU D EXPLOSION Le non respect des avertissements de sécurité pourrait entraîner un fonctio...

Страница 14: ...oosen lugs at supply side of circuit breakers b Remove cover from single circuit kit if supplied c Insert metal buss bars of kit into lugs of circuit breaker d Tighten lugs securely 45 in lbs recommended 6 Connect service ground wire s to grounding lug s provided One ground is required for each supply circuit used See Figure 19 page 16 Grounding WARNING To minimize personal injury the furnace cabi...

Страница 15: ...Black Blower Installation 1 Turn off all electrical supply circuits to the furnace at the main service panel 2 Remove furnace front door and switch furnace circuit breaker s to OFF 3 Disconnect the motor plug from the control panel receptacle 4 Remove one screw from left side of blower and three screws from right side of blower Slide blower forward to remove 5 Install new blower NOTE Make sure the...

Страница 16: ...er Door Panel Jumper for Circuit Breaker Left Control Door Right Control Door Transformer Circuit Breaker Control Board DC Relay Control Board Bracket AC Relay Ground Lug Limit Capacitor Motor Capacitor Strap Blower Wheel Figure 19 RE9X Furnace Components ...

Страница 17: ...P Knockout 4 1 4 X 3 3 4 FRONT VIEW TOP VIEW LEFT SIDE BOTTOM VIEW RIGHT SIDE VentilAire Knockout 1 1 2 X 5 VentilAire Knockout 1 1 8 X 4 1 2 Optional Electric Ø 1 Optional Electric Ø 5 8 Tie Down Tab TOP VIEW FRONT VIEW LEFT SIDE RIGHT SIDE BOTTOM VIEW 19 7 8 20 14 7 8 17 3 8 24 3 4 6 17 13 1 2 3 3 4 16 1 2 2 16 1 2 4 3 8 Figure 21 RE9X Furnace Upflow Stand Dimensions ...

Страница 18: ...24 1 2 623mm NOTES 1 Heating output rated at listed voltage For outputs at voltages other than 240V multiply Btuh rating by the following factors x 0 92 230V x 0 84 220V x 0 75 208V 2 Height is 56 with return air grille installed 58 with coil cabinet and 72 with coil cabinet and upflow stand 3 The factory installed blower can be replaced with a multi speed blower allowing the units to accept up to...

Страница 19: ...ingle 51 2 70 64 Dual A 27 1 40 34 Dual B 24 2 30 30 15N4 Single 65 4 90 82 Dual A 44 6 60 56 Dual B 20 8 30 26 17N4 Single 70 4 90 88 Dual A 47 9 60 60 4 or more wire systems maximum wire lengths 24 Ga 25 22 Ga 45 20 Ga 70 18 Ga 110 Dual B 22 5 30 28 20N4 Single 86 2 125 108 Dual A 44 6 60 56 Dual B 41 7 60 52 23N4 Single 93 8 125 117 Dual A 45 5 60 57 Dual B 48 0 60 60 NOTE Wire size must be in ...

Страница 20: ... les branchements du thermostat 4 Si l un ou l autre des fils de cette unité requiert un remplacement il doit être remplacé par un fil en cuivre thermoplastique 105 C du même gabarit 5 Ne convient pas à l utilisation sur les systèmes qui excèdent 120 V à la terre 6 Consultez les instructions d installation pour un schéma de câblage complet 7 Le chauffage et la climatisation peuvent être câblés sur...

Страница 21: ...ements du thermostat 4 Si l un ou l autre des fils de cette unité requiert un remplacement il doit être remplacé par un fil en cuivre thermoplastique 105 C du même gabarit 5 Ne convient pas à l utilisation sur les systèmes qui excèdent 120 V à la terre 6 Consultez les instructions d installation pour un schéma de câblage complet 7 Le chauffage et la climatisation peuvent être câblés sur la même vi...

Страница 22: ...es fils de cette unité requiert un remplacement il doit être remplacé par un fil en cuivre thermoplastique 105 C du même gabarit 5 Ne convient pas à l utilisation sur les systèmes qui excèdent 120 V à la terre 6 Consultez les instructions d installation pour un schéma de câblage complet 7 Le chauffage et la climatisation peuvent être câblés sur la même vitesse à l aide du cavalier fourni Switch ci...

Страница 23: ...ment il doit être remplacé par un fil en cuivre thermoplastique 105 C du même gabarit 5 Ne convient pas à l utilisation sur les systèmes qui excèdent 120 V à la terre 6 Consultez les instructions d installation pour un schéma de câblage complet 7 Le chauffage et la climatisation peuvent être câblés sur la même vitesse à l aide du cavalier fourni Switch circuit breakers to the off position before s...

Страница 24: ...rate and maintain the equipment for the life of the product Safety should always be the deciding factor when installing this product and using common sense plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious injury death or propert...

Отзывы: