14

•  Circuit breakers installed in this unit provide short-

circuit protection of the internal wiring and serve as 

a disconnect. The circuit breakers DO NOT provide 

over-current protection of the supply wiring and may 

be sized larger than the branch circuit protection. 

Overcurrent protection of the supply wiring is 

provided by the breaker in the distribution panel 
and must be sized as shown in 

Table 6 (page 19)

.

It is recommended that the line voltage (240 VAC) to 

the furnace be supplied from a dedicated branch circuit 

containing the correct fuse or circuit breaker for the furnace. 

For minimum circuit ampacity and maximum over-current 
protection, see 

Table 6

. See unit wiring diagrams (

Figure 

23

Figure 24

Figure 25

, & 

Figure 26

) for wiring details. 

Electrical components are shown in 

Figure 19 (page 16)

Supply circuit requirements are listed below:

•  -010  model  is  factory-wired  for  single-branch  supply 

circuit only.

•  -012 models are factory-wired for single-branch supply 

circuit (single-circuit kit factory installed). Dual-branch 

circuit can be used by removing factory-installed 
single-circuit kit. See 

Figure 17

.

•  -015, -017, -020 and -023 models are factory-wired for 

dual-branch supply circuit. Single-branch circuit can 

be used by installing optional single-circuit kit.

Connecting Supply Service Wires

Power entrance for all models may be through the right 

side or through the bottom of the unit.

1. Remove right-hand control panel (when viewing in 

downflow position).

2. Locate power supply knockouts in side of unit and in 

bottom of unit. Remove appropriate plug(s) or knockout 

opening applicable to selected wire size(s).

 WARNING:

To avoid personal injury or property damage, 

make certain that the motor leads cannot 

come into contact with non-insulated metal 

components of the unit.

3. Install listed cable connector(s) in opening(s). If metal-

sheathed conduit is used for incoming power line(s), 

provide an approved metal clamp on conduit and secure 

it in entrance knockout.

4. Insert supply service wire(s) through cable connector(s) 

and connect wires to circuit breakers (

Figure 17

 & 

Figure 

18

). 

NOTE: To install single-circuit kit, perform step 5. 

If single-circuit kit installation is not needed, go to step 

6.

5. To install optional single-circuit kit:

a.  Loosen lugs at supply side of circuit breakers.

b.  Remove cover from single-circuit kit (if supplied).

c.  Insert metal buss bars of kit into lugs of circuit 

breaker.

d.  Tighten lugs securely (45 in.-lbs. recommended).

6. Connect service ground wire(s) to grounding lug(s) 

provided. One ground is required for each supply circuit 
used. See 

Figure 19 (page 16)

.

Grounding

 WARNING:

To minimize personal injury, the furnace cabinet 

must have an uninterrupted or unbroken electrical 

ground. The controls used in this furnace require 

an earth ground to operate properly. Acceptable 

methods include electrical wire or conduit 

approved for ground service. Do not use gas 

piping as an electrical ground!

Thermostat / Low Voltage Connections

•  The furnace is designed to be controlled by a 24 VAC 

thermostat. The thermostat’s wiring must comply with 

the current provisions of the NEC (ANSI/NFPA 70) 

and with applicable local codes having jurisdiction.

•  The  thermostat  should  be  mounted  about  5  feet 

above the floor on an inside wall. DO NOT install the 

thermostat on an outside wall or any other location 

where its operation may be adversely affected by 

radiant heat from fireplaces, sunlight, or lighting 

fixtures, and convective heat from warm air registers 

or electrical appliances. Refer to the thermostat 

manufacturer’s instruction sheet for detailed mounting 
information. See 

Figure 22 (page 18)

 for typical 

thermostat connections.

•  For  proper  indoor  blower  operation  and  temperature 

rise, the RE9X electric furnace requires that the system 

thermostat be configured NOT to call for the indoor 

blower to operate in the heating mode. Refer to your 

specific thermostat installation instructions for details 

on the heating mode indoor blower configuration.

•  The  RE9X  series  electric  furnaces  incorporate 

an integrated control. The thermostat’s 1st stage 

compressor signal, 

Y, must be connected to the 

YELLOW control wire at the furnace to enable the 

indoor blower off-delay in the cooling mode.

 OPTIONAL

SINGLE CIRCUIT

ADAPTOR KIT 

CIRCUIT BREAKER

BRACKET 

60A

60A

ON

ON

OFF

OFF

CIRCUIT BREAKER
WIRE ASSEMBLIES

(FACTORY INSTALLED)

SUPPLY SERVICE WIRE

CONNECTION WITH SINGLE

CIRCUIT ADAPTOR KIT

 

Figure 17. Optional Single Circuit Adaptor Kit

Figure 18. Installation of Supply Service Wires

60A

60A

ON

ON

OFF

OFF

CIRCUIT BREAKER

WIRE ASSEMBLIES

(FACTORY INSTALLED)

CIRCUIT BREAKER

BRACKET 

SUPPLY SERVICE WIRE

CONNECTION WITHOUT SINGLE

CIRCUIT ADAPTOR KIT

Содержание RE9X-10N4

Страница 1: ... OU D EXPLOSION Le non respect des avertissements de sécurité pourrait entraîner un fonctionnement dangereux de l appareil des blessures graves la mort ou des dommages matériels Unentreteinincorrectpourraitentraînerunfonctionnement dangereux de l appareil des blessures graves la mort ou des dommages matériels Couper toute alimentation électrique au générateur d air chaud avant de prodéder aux trav...

Страница 2: ...for Downflow Systems 8 Furnace INstallATION 8 General Information 8 Before You Install this Furnace 8 Locating the Unit 8 Locating Cutting Floor Openings 9 Standard Duct Connector Installation 10 Narrow Duct Connectors 10 Round Duct Connector Installation 11 Alcove Installation 11 Closet Installation 11 Upflow Furnaces 12 Over the Floor Return Air System Non Ducted 12 Through the Floor Return Air ...

Страница 3: ...UTO in place of the HEAT and COOL Others may include all three Please refer to the thermostat manufacturer s User manual for detailed programming instructions NOTE Allow at least one hour for the room temperature to stabilize before you make a second adjustment to the thermostat setting After the desired comfort level is established makeonlysmalladjustmentstothethermostat setting to meet changing ...

Страница 4: ...s frequently and replace when necessary with filter of same dimensional size Filters designed to remove smaller particles such as pollen may require additional maintenance Coil Filters If a cooling coil is installed on your unit the furnace filter is not used Remove coil filters wash and allow to dry Re install coil filters to their original positions Blower Compartment Dirt and lint can create ex...

Страница 5: ...ings or structures under construction Minimum Installation Clearances Access for positioning and servicing the unit must be considered when locating unit The need to provide clearance for access to panels or doors may require clearance distances over and above the requirements For alcove installations allow 18 46cm inches minimum clearance from the front of the unit for future servicing Closet ins...

Страница 6: ...r entering through an opening in the floor or ceiling of a closet must meet all of the following requirements The return air opening regardless of its location in the closet must not be smaller than size specified on unit data label If located in the floor the opening must be provided with a means of preventing its inadvertent closure by flat object s placed over the opening A return air grille mu...

Страница 7: ...ngtheoptionalcoilcabinet Figure3 isrecommended The duct system must be properly sized to account for any additional external static pressure produced from the chosen filtering method NOTE Install a filter with a minimum unrestricted medium area of 324 in2 in the duct above the coil that is accessible for monthly cleaning or replacement by homeowner Filtering Methods Upflow Furnaces Non Ducted Retu...

Страница 8: ...This appliance will provide many years of safe and dependable comfort providing it is properly installed and maintained Abuse improper use and or improper maintenance can shorten the life of the appliance and create unsafe hazards Please read all instructions before installing the unit Approved installation operation and maintenance of this appliance must be in accordance with the listed specifica...

Страница 9: ...CUT OUT 14 1 4 DIAMETER FOR UPFLOW FURNACES WITH ROUND DUCT CONNECTORS C L STANDARD DUCT CONNECTOR ROUND DUCT CONNECTOR Locating Cutting Floor Openings Floor cut outs must be carefully located to avoid misalignment of the furnace and air duct Standard and round cutouts for upflow furnaces are shown in Figure 5 The cutouts for downflow furnaces are shown in Figure 6 1 Measure and mark the centerlin...

Страница 10: ... FOLD FLAP HERE REMOVE THIS FLAP REMOVE THIS FLAP C U T H E R E C U T H E R E C U T H E R E C U T H E R E CUT HERE CUT HERE CUT HERE CUT HERE CUT HERE FOLD FLAP HERE FOLD FLAP HERE Figure 9 Duct Connector Tabs DUCT CONNECTOR SUPPLY AIR DUCT BEND TABS TIGHTLY AGAINST SUPPLY AIR DUCT MOUNTING PLATE DUCT CONNECTOR CONNECTOR TABS SUPPLY AIR DUCT WOOD FLOOR Figure 8 Standard Duct Connector Installed NO...

Страница 11: ...s between 1 5 requirements are a louvered door with a minimum of 250 in2 1613 cm2 free area Afullylouveredclosetdoorisstronglyrecommended forbothinstallationtypes Forclosetinstallations thereturn air grille mounting frame is not used since the furnace is located inside the closet For examples of both types of installations see Figure 14 page 12 1 Cut return air opening in desired position in door ...

Страница 12: ...3 3 Route 240V supply circuit s and 24V wiring to closet See Figure 20 page 17 for appropriate locations 4 Position optional coil cabinet onto upflow stand or mounting platform and secure with three or more fasteners 5 Position furnace in upflow mode onto coil cabinet and secure with two or more fasteners 6 Use optional upflow duct connector or field supplied connector to attach furnace to overhea...

Страница 13: ...result in dangerous operation serious injury death or property damage Before servicing disconnect all electrical power to furnace When servicing controls label all wires prior to disconnecting Reconnect wires correctly Verify proper operation after servicing AVERTISSEMENT RISQUE DE CHOC ÉLECTRIQUE D INCENDIE OU D EXPLOSION Le non respect des avertissements de sécurité pourrait entraîner un fonctio...

Страница 14: ...oosen lugs at supply side of circuit breakers b Remove cover from single circuit kit if supplied c Insert metal buss bars of kit into lugs of circuit breaker d Tighten lugs securely 45 in lbs recommended 6 Connect service ground wire s to grounding lug s provided One ground is required for each supply circuit used See Figure 19 page 16 Grounding WARNING To minimize personal injury the furnace cabi...

Страница 15: ...Black Blower Installation 1 Turn off all electrical supply circuits to the furnace at the main service panel 2 Remove furnace front door and switch furnace circuit breaker s to OFF 3 Disconnect the motor plug from the control panel receptacle 4 Remove one screw from left side of blower and three screws from right side of blower Slide blower forward to remove 5 Install new blower NOTE Make sure the...

Страница 16: ...er Door Panel Jumper for Circuit Breaker Left Control Door Right Control Door Transformer Circuit Breaker Control Board DC Relay Control Board Bracket AC Relay Ground Lug Limit Capacitor Motor Capacitor Strap Blower Wheel Figure 19 RE9X Furnace Components ...

Страница 17: ...P Knockout 4 1 4 X 3 3 4 FRONT VIEW TOP VIEW LEFT SIDE BOTTOM VIEW RIGHT SIDE VentilAire Knockout 1 1 2 X 5 VentilAire Knockout 1 1 8 X 4 1 2 Optional Electric Ø 1 Optional Electric Ø 5 8 Tie Down Tab TOP VIEW FRONT VIEW LEFT SIDE RIGHT SIDE BOTTOM VIEW 19 7 8 20 14 7 8 17 3 8 24 3 4 6 17 13 1 2 3 3 4 16 1 2 2 16 1 2 4 3 8 Figure 21 RE9X Furnace Upflow Stand Dimensions ...

Страница 18: ...24 1 2 623mm NOTES 1 Heating output rated at listed voltage For outputs at voltages other than 240V multiply Btuh rating by the following factors x 0 92 230V x 0 84 220V x 0 75 208V 2 Height is 56 with return air grille installed 58 with coil cabinet and 72 with coil cabinet and upflow stand 3 The factory installed blower can be replaced with a multi speed blower allowing the units to accept up to...

Страница 19: ...ingle 51 2 70 64 Dual A 27 1 40 34 Dual B 24 2 30 30 15N4 Single 65 4 90 82 Dual A 44 6 60 56 Dual B 20 8 30 26 17N4 Single 70 4 90 88 Dual A 47 9 60 60 4 or more wire systems maximum wire lengths 24 Ga 25 22 Ga 45 20 Ga 70 18 Ga 110 Dual B 22 5 30 28 20N4 Single 86 2 125 108 Dual A 44 6 60 56 Dual B 41 7 60 52 23N4 Single 93 8 125 117 Dual A 45 5 60 57 Dual B 48 0 60 60 NOTE Wire size must be in ...

Страница 20: ... les branchements du thermostat 4 Si l un ou l autre des fils de cette unité requiert un remplacement il doit être remplacé par un fil en cuivre thermoplastique 105 C du même gabarit 5 Ne convient pas à l utilisation sur les systèmes qui excèdent 120 V à la terre 6 Consultez les instructions d installation pour un schéma de câblage complet 7 Le chauffage et la climatisation peuvent être câblés sur...

Страница 21: ...ements du thermostat 4 Si l un ou l autre des fils de cette unité requiert un remplacement il doit être remplacé par un fil en cuivre thermoplastique 105 C du même gabarit 5 Ne convient pas à l utilisation sur les systèmes qui excèdent 120 V à la terre 6 Consultez les instructions d installation pour un schéma de câblage complet 7 Le chauffage et la climatisation peuvent être câblés sur la même vi...

Страница 22: ...es fils de cette unité requiert un remplacement il doit être remplacé par un fil en cuivre thermoplastique 105 C du même gabarit 5 Ne convient pas à l utilisation sur les systèmes qui excèdent 120 V à la terre 6 Consultez les instructions d installation pour un schéma de câblage complet 7 Le chauffage et la climatisation peuvent être câblés sur la même vitesse à l aide du cavalier fourni Switch ci...

Страница 23: ...ment il doit être remplacé par un fil en cuivre thermoplastique 105 C du même gabarit 5 Ne convient pas à l utilisation sur les systèmes qui excèdent 120 V à la terre 6 Consultez les instructions d installation pour un schéma de câblage complet 7 Le chauffage et la climatisation peuvent être câblés sur la même vitesse à l aide du cavalier fourni Switch circuit breakers to the off position before s...

Страница 24: ...rate and maintain the equipment for the life of the product Safety should always be the deciding factor when installing this product and using common sense plays an important role as well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious injury death or propert...

Отзывы: