background image

 

3.

  ASSEMBLY

3.1. 

GENERAL PRINCIPLES

During  installation,  ensure  a  free  air  flow  to  the  device  and  do  not  restrict 
the  air  stream  supply.  The  figures  below  show  the  recommended  distances 
between the heater and building partitions:

a) in case of wall mounting

b) in case of ceiling mounting

In case of higher heat demand, more units can be installed in the room. In order 
to ensure proper air flow, it is necessary to maintain the recommended distances 
between the heaters, as shown in the following figure.

3.2. 

ROTATING MOUNTING BRACKET

The  Reventon  Group  HC  serie

s

  devices  can  be  assembled  using  a  rotating 

mounting  bracket.  It  enables  the  heaters  installation  on  the  wall  or  ceiling, 
depending on the required optimal direction of airflow. 

4. 

INSTALLATION INSTRUCTIONS

4.1.

CONNECTION OF THE DEVICE TO THE HYDAULIC SYSTEM

-

pipes

 should

 be connected as indicated on the heater (supply from below, return 

from above)

-  connecting  the  device  to  the  hydraulic  installation,  do  remember  to  hold 
the connectors by pipes spanner

N

ot keeping to the recommendation may cause the damages of the heating coil. 

it is recommended to use filter on the water supply pipe

- it is recommended to use the following valves:

ź

vent valve in the highest place on the

 

hydraulic installation

ź

cut off valve on the supply and return pipes of the device

installation has to be secured against excessive increase of pressure

it is recommended to check the leak tightness of the hydraulic system before 

plugging  the electric supply

4.2. 

CONNECTION OF THE DEIVCE TO THE ELECTRICAL SYSTEM

-  a

ll  works  concerning  electrical  installation  should  be  made  by  the  qualified 

personnel (who possess required authorizations to install electrical equipment), 
based on wiring schematic diagrams (see 7)

the electrical installation of the building shall have a residual current device

it is recommended to check the electric installation and controls before the first 

start

5. 

PRECAUTIONS & WARNINGS

The  precautions  mentioned  below  must  be  strictly  followed  during  operation 
of the device:

all  works  concerning  electrical  installation  (disassembly,  repair  etc.)  should 

be made by the

 

qualified staff, who possess the qualifications due to the domestic 

and local norms, regarding electrical installations

- EC motor starts if voltage signal is at least 1.7 V - despite this for lower values 
of voltage

 

 the fan still remains under voltage

before service or exchange of the device it is obligatory to cut off the current 

supply

do not limit or cover the inlet and outlet of the device

-

do not install, service the device with wet hands or barefoot

the device should be kept out of reach of children and animals

-  the  device  does  not  consist  of  the  anti-frost  protection  -  the  temperature 
in the room, where device is installed,  should not go below 0°C; if such situation 
could take place empty the device out of water

after the turn off, the elements of device may be warm

after operating time of the device, please utilize it concerning the local norms 

and regulations

- i

t is recommended to clean the device periodically (at least twice a year):

ź

  

heating coil blow with compressed air

ź

  

fan casing and blades clean from dirt

-  failure  to  comply  with  cleaning  obligations  may  have  a  negative  effect 
on technical parameters of the device

 

and lead to loss of warranty

-  i

f the device is not used for a longer time disconnect the power supply

Supply

Return

Model

HC 3 A

HC 5 A

HC 7 A

3

3

3

3

1

1

2

5

5

5

5

2

2

4

8

8

8

8

3

3

6

HC20-3S

HC30-3S

HC35-3S

HC45-3S

HC50-3S

HC70-3S

HMI

HC3S

3

3

3

3

1

1

2

5

5

5

5

2

2

4

HC 14 A

RM- 16 A

16

16

16

16

7

6

12

19

19

19

19

8

7

14

HC80-3S

HC 1.2 A

1

1

1

1

-

1

-

COOPERATION OF CONTROLLERS WITH EQUIPEMENT

Содержание HC 20-EC Series

Страница 1: ...Technical documentation AIR WATER HEATERS IN EPP CASING HC EC SERIES MODELS HC 20 EC HC 30 EC HC 35 EC HC 45 EC HC 50 EC HC 70 EC ...

Страница 2: ...ing devices Reventon Group HC series are used to heat spaces such as production halls warehouses commercial room service spaces garages workshops greenhouses tents shops malls shopping malls etc However heating devices should not be used in corrosive environments for aluminum copper and steel as well as in highly dusty environments above 0 3 g m The devices should not be installed in rooms where t...

Страница 3: ...1 03 0 92 HC 30 EC 4100 m h 0 5 10 15 20 25 6 23 2 20 9 18 6 16 4 17 4 21 0 24 7 28 2 31 8 1 12 1 02 0 92 0 82 0 72 80 60 90 70 40 30 120 90 HC 20 EC 4300 m h HC 20 EC 4300 m h HC 20 EC 4300 m h HC 20 EC 4300 m h HC 30 EC 4100 m h HC 30 EC 4100 m h 6 5 4 4 3 7 6 5 5 4 5 5 4 3 2 4 3 2 2 1 1 1 0 0 0 5 3 2 1 0 8 7 7 6 5 11 9 8 7 5 8 7 5 4 3 Parameters Supply return water temperature C Dry bulb air in...

Страница 4: ...y kW Dry bulb air outlet temperature C Water flow m h Pressure drop in the heat exchanger kPa Parameters Supply return water temperature C Dry bulb air inlet temperature C Heating capacity kW Dry bulb air outlet temperature C Water flow m h Pressure drop in the heat exchanger kPa Parameters Supply return water temperature C Dry bulb air inlet temperature C Heating capacity kW Dry bulb air outlet t...

Страница 5: ...ers Supply return water temperature C Dry bulb air inlet temperature C Heating capacity kW Dry bulb air outlet temperature C Water flow m h Pressure drop in the heat exchanger kPa Parameters Supply return water temperature C Dry bulb air inlet temperature C Heating capacity kW Dry bulb air outlet temperature C Water flow m h Pressure drop in the heat exchanger kPa Parameters Supply return water te...

Страница 6: ...al installation should be made by the qualified personnel who possess required authorizations to install electrical equipment basedonwiringschematicdiagrams see7 theelectricalinstallationofthebuildingshallhavearesidualcurrentdevice itisrecommendedtochecktheelectricinstallationandcontrolsbeforethefirst start 5 PRECAUTIONS WARNINGS The precautions mentioned below must be strictly followed during ope...

Страница 7: ...from the controller In addition the device can be integrated with the BMS building control system usingtheMODBUScommunicationprotocol Voltage Frequency 230 V AC 50 60 Hz Maximum current 5 A Operating temperature range 0 45 C Regulation range 5 C 35 C Regulation accuracy 0 5 C External temperature sensor NTC 10K Communication RS485 Dimensions 86 x 86 x 13 3 mm Weight 270 g Degree of protection hous...

Страница 8: ...r 2 Main switch overcurrent circuit breaker 3 Air water heater HC EC 4 Potentiometr EC 5 Programmable controller HMI EC 6 Valve with actuator HC 3 4 7 External temperature sensor main switch and safety fuses are not included in the set ...

Страница 9: ......

Страница 10: ......

Страница 11: ...vedevicewithinaspecifiedtimelimit VII Warranty does not cover the parts of the device subject to normal maintenanceandthefollowingcases a mechanicaldamageoftheproduct b defectsanddamagesthrough improperstorageortransport improper or non compliant use and maintenance i e inconsistent withthemanual using the device in the improper conditions too high humidity too high ortoolowtemperature impactofthe...

Страница 12: ...Warranty card Reventon Group Sp z o o Ltd 556 Wyzwolenia Street 43 340 Kozy Poland ...

Страница 13: ...Reventon Group Sp z o o Ltd 556 Wyzwolenia Street 43 340 Kozy Poland www reventongroup eu ...

Отзывы: