Sequence of Operation

The following Sequence of Operation 

applies to PTAC/PTHP units. 

The 

R_ _C

  units are straight cool, single stage air conditioners avail-

able with electric or hydronic heat.
The 

R_ _H

 units are limited range, single stage heat pump.  Mechani-

cal compression heating (heat pump mode) is locked out at outdoor 

temperatures of approximately 35 ºF (1.7 ºC) and below.   Below 

these ambient temperatures, the auxiliary electric or hydronic heat 

will be used.

General

The unit is controlled by a microprocessor.  Thermostat and control 

connections are made to the control board. 

  - Control Board

Figure 7 

                     

Two configuration jumpers are located on the board, see Figure 

8. The Heat Pump Configuration Jumper is a 3 pin jumper.  

Straight 

• 

Cool

 units R_ _C, the jumper should be located on the 

outside two pins.  

Heat

• 

 Pump units R_ _H, the jumper should be located on the 

inside two pins.  

A second configuration jumper “TEST” allows for the control’s inter-

nal timers to be by-passed for test purposes.  Placing the jumper on 

the two pins enables the test mode.  
A status LED (Light Emitting Diode), LED1 is located on the center 

of the board.  A series of blinks communicates the status of the board.  

Between the blink sequence is a separation of approximately 2 seconds.  

The Status Code is listed below.

Trouble 

Code 

(Blinks)

Status

1

Normal Operation

2

Anti-Short Cycle Timer Active

3

Outdoor Coil Freeze Protection

4

Indoor Coil Freeze Protection

5

Simultaneous “Y” and “W” Call

Initial Power-Up or Power Restoration

When power is applied to the unit, either for the first time or after a 

power failure, the board will initialize itself.  During the initialization, 

LED1 will be lit continuously for approximately 5 seconds.  Following 

the initialization, a random start timer is initiated.  This timer adds 

a randomly selected 5-120 seconds to the start-up sequence, reduc-

ing the possibility of multiple units starting at the same time.  Once 

the random start timer has expired, a 180 second Anti-Short Cycle 

Timer is initiated and the Processor Board Trouble Code LED is set 

to blink a 2 flash code.  This timer prevents the compressor from rapid 

cycling.  After the Anti-Short Cycle Timer expires, the Processor Board 

Trouble Code LED is set to blink a 1 blink Trouble Code, indicating 

normal operation.

R_ _C / R_ _H; Cooling Operation

( For unit mount controls)
With the System Switch [SS] set to “Cool”, and the Fan Cycle Switch 

[FCS] set to “On” (Continuous Fan Operation), the indoor fan mo-

tor will start.  If the Fan Cycle Switch [FCS] is set to “Off” (Cycling 

Fan Operation), the indoor fan motor will start with a call for cool-

ing from the internal thermostat [T’stat].  If the unit is equipped 

with a Motorized Fresh Air Damper, and is active with the Fresh 

Air Switch [FAS], the damper will open with a call for the indoor 

fan.  If the room temperature is below the thermostat setting the fan 

operation will continue as noted above.  If the room temperature is 

above the thermostat setting, the reversing valve will be energized, 

the compressor and outdoor fan will start provided the Anti-Short 

Cycle Timer has timed out from the initial power-up, power restora-

tion or a previous compressor on cycle.  Operation will continue 

until the room temperature satisfies the thermostat.  Once the room 

temperature falls below the set point by 3 ºF (2 ºC), the compressor, 

outdoor fan motor and reversing valve will de-energize.  If the FCS 

is set to “Off”, the indoor fan will continue to operate for 60 seconds 

after the compressor stops.  If the FCS is set to “On”, the indoor fan 

will continue to operate.  As soon as the compressor is de-energized, 

the Anti-Short Cycle Timer will be initialized and will prevent the 

compressor from starting again for another 180 seconds.  While the 

Anti-Short Cycle Timer is active, the Processor Board Trouble Code 

LED is set to blink a 2 flash code.  After the Anti-Short Cycle Timer 

expires, the Processor Board Trouble Code LED is set to blink a 1 

blink Trouble Code, indicating normal operation.

LED

Indicator

Light

TEST 

Config.

Jumper

Heat 

Pump

Config.

Jumper

Replacement Packaged Terminal Air-Conditioning / Heat Pump

•  Installation, Operation, and Maintenance Manual •

P/N 240008639, Rev. B [8/16/2011]

 

13

 

Made in USA

Содержание R40C

Страница 1: ...oAire com An ISO 9001 2008 Certified Company P N 240008639 Rev B 8 16 2011 R40C Packaged Terminal Air Conditioner PTAC Straight cooling nominal capacities Btuh 9 000 12 000 15 000 kW 2 6 3 5 4 4 Installation Operation Maintenance Manual R40C Replacement for Fedders Model CMEA packaged terminal unit ...

Страница 2: ...neral Product Information 4 6 Product description 4 Standard controls and components 4 Factory installed options consult the factory 4 Field installed options 4 R40C Chassis 5 7 PTAC PTHP Model Coding 8 Features 9 10 Optional wall mounted thermostats 10 Preparing for the Installation of the PTAC PTHP 11 Electrical power connection 11 Remove the old chassis 11 Installation Instructions R40C 12 Sequ...

Страница 3: ...use as described in this manual Turn off the electrical supply before servicing the unit PTAC PTHP chassis are heavy To avoid injury use assistance when lifting Do not use the unit if it has damaged wiring is not working properly or has been damaged or dropped Failuretofollowtheseinstructionsmayresultinimproperinstalla tion operation service ormaintenance possiblyresultinginfire electrical shock p...

Страница 4: ...g emergency heat if an auxiliary heat source is available Low ambient protection see Microprocessor control board for details Ability to control a normally open or normally closed motor valve switch on hydronic heat units only Valve controls must be ordered for 24V or line voltage All hydronic heat units include molex plugs for connection of hydronic valve motor Remote mount controls include fan s...

Страница 5: ...uts 5 POS Terminal Block Optional Knockouts Thermostat System Switch SS Fan Speed Switch FSS Remote Mount Unit Mount R40C Chassis Figure 1 Replacement Packaged Terminal Air Conditioning Heat Pump Installation Operation and Maintenance Manual P N 240008639 Rev B 8 16 2011 5 Made in USA ...

Страница 6: ... Information continued Open Close Remove Screws to Open Door Rating Plate Electrical Diagram Replacement Packaged Terminal Air Conditioning Heat Pump Installation Operation and Maintenance Manual The Right Fit for Comfort 6 P N 240008639 Rev B 8 16 2011 ...

Страница 7: ...continued R40C Dimensioned Front View Figure 3 R40C Dimensioned Rear View Figure 4 Replacement Packaged Terminal Air Conditioning Heat Pump Installation Operation and Maintenance Manual P N 240008639 Rev B 8 16 2011 7 Made in USA ...

Страница 8: ...lve line volt 3 RMT remote tstat hyd heat N O or N C valve line volt 4 UM unit mount hyd heat N O or N C valve 24 volt 5 RMT remote tstat hyd heat N O or N C valve 24 volt Voltage A 115 V 1 60 Models 9 12 BTU only D 208 230 V 1 60 Chassis coding verify with rating plate Position number 1 2 3 5 4 6 7 8 9 10 11 12 13 14 15 R Cooling Capacity 09 9 000 Btuh 12 12 000 Btuh 15 15 000 Btuh Model coding F...

Страница 9: ... compressor from starting This staggers the starting of multiple units in a single facility preventing a large surge that might occur if all units started at the same time Anti short cycle timer standard The microprocessor control uses this timing to prevent short cycling of the compressor When the compressor cycles off on a heating or cooling call the controller starts a 180 second timer The comp...

Страница 10: ...point range of between 45 F 7 C and 90 F 32 C For heat pumps another option is EMI part number 240008209 This is a 2 stage heat cool thermostat which allows for emergency heat Selecting a thermostat by others When selecting a thermostat other than one offered by EMI choose a single stage heat cool 24v thermostat Straight cooling with electric heat or hydronic heat R10C PTAC s Select a thermostat t...

Страница 11: ...tage is 208v Change the transformer tap from orange to red See the wiring diagram for details Electrical power connection Check the RetroAire unit rating plate for circuit ampacity and 1 required breaker or fuse size Verify that the existing breaker or fuse is the correct size 2 Replace the breaker or fuse if incorrectly sized a Breakers must be type HACR only b Cord connected units verify that th...

Страница 12: ... supplied with unit Install only one set of left and right side baffles on the condenser coil by completing steps below Choosetheproperfittingbafflesforyourapplicationbyverifying selected baffles come in contact with the outdoor louver Make sure the baffles are directed inward toward the center of coil Securebafflestightlyintotheexistingholesofthecondensercoil using the screws provided NOTICE Thec...

Страница 13: ...ated and the Processor Board Trouble Code LED is set toblinka2flashcode Thistimerpreventsthecompressorfromrapid cycling AftertheAnti ShortCycleTimerexpires theProcessorBoard Trouble Code LED is set to blink a 1 blink Trouble Code indicating normal operation R_ _C R_ _H Cooling Operation For unit mount controls With the System Switch SS set to Cool and the Fan Cycle Switch FCS set to On Continuous ...

Страница 14: ...le Code LED is set to flash a 1 blink Trouble Code indicating normal operation R_ _H Auxiliary Heating Electric or Hydronic If the outdoor coil temperature falls to 25 ºF 4 ºC or below for180secondsatanytimeduringaheatingcall thecompressor and outdoor fan motor will be de energized and auxiliary heat will be energized The Anti Short Cycle Timer will be initi ated prohibiting compressor operation f...

Страница 15: ...t metal panels are in place and secure Attach the front panel to the existing cabinet enclosure Verify that nothing will interfere with the room discharge air or the return air of the units Examples Check for curtains or drapes that obstruct the air flow See Figure 8 and Figure 9 Check for plush carpeting that can obstruct the return air Items like these can cause serious damage to the chassis CAU...

Страница 16: ...ion HP Jumper Figure 10 selects heat pump or straight cooling TEST jumper to select normal or test mode This jumper is for use in testing only see Figure 11 and Figure 12 When the JUMPER pins are jumpered together all timers are elimi nated example anti short cycle purge etc This is mainly used for production line testing But it may be used for field testing as well The units are factory set with ...

Страница 17: ...r 3 switch to the YES position and verify the damper opens and allows fresh air to be moved into the space Then set the damper door switch to the NO position and verify the flow of air into the space has stopped Fresh air will only be available when the indoor fan is running Verify that the 4 HP jumper is set correctly for the unit type cooling only or heat pump unit see Figure 10 page 16 Set the ...

Страница 18: ...rom the processor board will activate the water or steam valve The motorized valve should open and allow hot water or steam to run through the coil The indoor fans will run blowing air through the hydronic coil If the unit is equipped with an Aquastat the indoor fan and the motorized damper operation will be delayed until the hydronic coil reaches 100 5 F 38 3 C Thesignaltothewaterorsteamvalvewill...

Страница 19: ...n will stop The indoor fan will switch off after the sixty second purge time has elapsed NOTICE Roomtemperaturemustbebelow85 F 29 C forthecompres sor to operate in heating mode on PTHP s with unit mounted controllers Place the thermostat or system switch in the 6 OFF position All operation should stop NOTICE Heat pump units are Limited Range equipped with back up electric resistance heat Limited R...

Страница 20: ...ing and the space gets warmer the hydronic valve will close and indoor fan will switch off after the sixty second purge time has elapsed Aftertheunitstartsrunningandthespacegetswarmer 3 adjustthe thermostattoacoolertemperaturesetting thehydronicvalvewill close and indoor fan will switch off after the sixty second purge time has elapsed If a warmer room temperature is desired 4 adjust the thermosta...

Страница 21: ...ton on the face of the switch see Figure 14 Maintenance Troubleshooting Figure 14 Manual Reset Limit Switch Reset Button Note Button will pop out when limit switch opens Push in to reset WARNING Clean or replace the return air filter as needed Allowing dust to collect on the filter will cause the unit to lose efficiency and eventually malfunction Check the filter at least once a month Some environ...

Страница 22: ...t Failure to do so could result in severe personal injury or death Should the heat pump fail the control board can be forced into electric heat mode This is a temporary solution until the heat pump system can be repaired Locate the circuit board in the control section of the unit 1 Locate the terminals where the outdoor sensor connects to the 2 circuit board Using a small needle nose type pliers d...

Страница 23: ... Make sure the sensors are correctly wired 77 F 10KOhms 50F 19 9KOhms 35F 30KOhms 30F 34 4KOhms The thermostat is satisfied but the fan is still running If the thermostat is set to auto mode once the thermostat is satisfied the fan will stay ener gized for an extra 60 seconds to purge the unit of excess cool or warm air in the plenum If the thermostat fan switch is set to ON the fan will stay ener...

Страница 24: ... the limit switch opens and de energizes the electric heat the limit switch will need to be manu ally reset To reset switch Remove the control box cover Locate the limit switch Push in the reset button on the face of the switch WARNING Clean or replace the return air filter as needed Allowing dust to collect on the filter will cause the unit to lose efficiency and eventually malfunction Check the ...

Страница 25: ...evelopment programs design specifications and performance data is subject to change with out notice Please consult the factory for further information For the most current unit system performance data please refer to our website at www ecrinternational com or Enviromaster International listing of certified products in the ARI certified directory at www ahridirectory org Replacement Packaged Termin...

Страница 26: ...5 6 30P 230 4000 17 4 18 22 3 5 208 4089 19 7 20 3 25 2 30 6 30P 230 5000 21 7 22 3 27 8 R40 9 000 BTU Table 3 electrical specifications R40 12 000 BTU Table 4 electrical specifications Power Supply Volt 1 60 Compressor Indoor Fan Motor Outdoor Fan Motor Electric Heat Unit Electrical Ratings Volt Min RLA LRA FLA Hp FLA Hp Htr Volt W HA TCA THA MCA MOCP Plug 115V 104 10 8 53 1 4 0 09 1 6 0 125 0 N ...

Страница 27: ...n RLA LRA FLA Hp FLA Hp Htr Volt W HA TCA THA MCA MOCP Plug 208 230V 197 7 4 33 0 6 0 08 0 71 0 09 0 N A N A N A 8 7 N A 10 6 15 6 15P 2 208 1636 7 9 8 5 10 6 15 6 15P 230 2000 8 7 9 3 11 6 3 208 2454 11 8 12 4 15 5 20 6 20P 230 3000 13 13 6 16 1 4 208 3271 15 7 16 3 20 4 25 6 30P 230 4000 17 4 18 22 5 5 208 4089 19 7 20 3 25 3 30 6 30P 230 5000 21 7 22 3 27 9 Electrical Specifications Replacement...

Страница 28: ...ECR International Inc 2201 Dwyer Avenue Utica NY 13501 e mail info RetroAire com An ISO 9001 2008 Certified Company The Right Fit for Comfort 28 P N 240008639 Rev B 8 16 2011 Warranty ...

Отзывы: