background image

If necessary it is possible to further secure 

or tamper proof the Alarm by using a No.2 

or No.4 (2 to 3mm diameter - not supplied) 

self tapping screw 6 to 8mm long to firmly 

lock the Alarm and its mounting plate 

together (see figure 6C).

5. Testing and Maintenance

Testing

Frequent testing of the system is a 

requirement to ensure its continued and 

safe operation. To test the Alarm press  

and hold the test button. The Green LED 

will flash and the horn will ramp up to full 

sound to indicate the Alarm is operating 

correctly. Guidelines and best practices 

for testing are as follows:

 

1. After the system is installed
2. Once weekly thereafter
3. After prolonged absence from the     

dwelling (e.g. after a holiday period)

4. After repair or servicing of any of the 

systems elements or household electrical 

works

Silencing (Hush)

When the Alarm sounds after sensing 

CO, pressing the test/hush button will 

immediately stop the horn (the red 

light will continue to flash). If CO is still 

present, the red light and the horn will 

turn on again after about 4 minutes. The 

unit can only be silenced once during a 

CO incident. At levels > 300ppm CO, the 

unit cannot be silenced.

Monitoring

The CO alarm will self check (monitor) 

itself and give a status update every 50 

seconds if there are any problems. The 

status of the Alarm can also be checked 

on demand by using the test button. If the 

Alarms are indicating a fault, pressing the 

test button will silence the beeps for a 24 

hour period. This is for your convenience 

and can only be done once.

the mounting plate attached.
6. Ensure the RF module is fitted 

correctly into the base of the Alarm.
7. Remove the battery door and gently 

pull the battery tab and replace the 

battery door. 
8. Carefully line up the Alarm on the 

base, gently press home & twist on – see 

figure 4. (This connects the batteries). 

The red, amber & green lights will 

immediately flash in sequence to show 

they are working. 

9. Press the Test button (after 15 

seconds) to ensure that the Alarm works 

(see figure 5).
10. Install all the other Alarms similarly.

Figure 5

4.2 How to Tamperproof the Alarm

 

The Alarm can be made resistant to 

unauthorized removal. Break off the small 

pillar on the base as shown in figure 6A. 

To remove the Alarm from the ceiling it is  

necessary to use a small screwdriver to 

release the catch (push catch towards the 

ceiling) and then twist off the alarm (see 

figure 6B).

7

Figure 6C

Figure 6A

Figure 6B

Содержание RE115

Страница 1: ...nd hold TEST button until sounder is done sounding beeps Panel will indicate a CO Test by sounding temporal 4 siren one time Interlogix Compatible Enrollment Place panel in enrollment mode Press and hold TEST button until sounder is done sounding beeps Panel will learn the CO alarm recommended group 34 Test that the CO alarm is enrolled in the panel Put panel into test mode Press and hold TEST but...

Страница 2: ...on the ceiling 300mm from walls and between 1 5m to 3m horizontally away from the appliance In rooms remote from the appliance install at head height where the light indicators can be seen Honeywell Compatible Enrollment Place panel in enrollment mode Zone type Carbon Monoxide Input type Supervised RF Transmitter When asked for a serial number trip tamper twice To tamper turn base counter clockwis...

Страница 3: ...e red alarm light immediately and then sounds a loud alarm if the CO persists Table B shows how the CO Alarm reacts to different levels of CO gas and exposure time At higher levels of CO the alarm turns on sooner The rate of flashing of the red light indicates the level of CO If your CO Alarm sounds follow the instructions in Section 6 NEVER IGNORE THE ALARM 3 2 3 Symptoms of CO Poisoning CO in PP...

Страница 4: ...t warns the homeowner that the unit has previously detected CO gas and been in alarm The memory feature has two operation modes memory indication for 24 hour period after alarm memory recall on demand 24 hour memory indicators After alarm the RED light will flash at different rates every 50 seconds depending on the level of CO detected see the CO Response Table Memory recall on demand To review th...

Страница 5: ... Outside of each separate dwelling unit sleeping area in the immediate vicinity of the bedroom 2 On every occupiable level of a dwelling unit including basements but excluding attics and crawl spaces 3 Other locations where required by applicable laws codes or standards The equipment should be installed using wiring methods in accordance with the National Fire Protection Association s Standard 72 ...

Страница 6: ...e is a partition in the room the CO Alarm should be located on the same side of the partition as the potential source In rooms with sloped ceilings the CO Alarm should be located at the high side of the room see figure 2 3 32 If locating the CO Alarm in a bedroom or in rooms remote from a fuel burning appliance see figure 3 Mount the CO Alarm relatively close to the breathing zone of the occupants...

Страница 7: ...t At levels 300ppm CO the unit cannot be silenced Monitoring The CO alarm will self check monitor itself and give a status update every 50 seconds if there are any problems The status of the Alarm can also be checked on demand by using the test button If the Alarms are indicating a fault pressing the test button will silence the beeps for a 24 hour period This is for your convenience and can only ...

Страница 8: ...t exposures to high or low temperatures or high humidity may reduce battery life Use only batteries specified in marking Use of a different battery may have a detrimental effect on alarm operation For environmentally sound disposal remove the Alarm from its mounting plate Quick Test with Carbon Monoxide The Carbon Monoxide Alarm checks for CO gas every 4 seconds and when exposed to the CO gas the ...

Страница 9: ...rk after you have carefully read all the instructions check that the unit has been installed correctly and ensured that it has good 1 Operate reset Silence button 2 Call your emergency services Fire Department or 911 3 Immediately move to fresh air outdoors or by an open door window Do a head count to check that all persons are accounted for DO NOT re enter the premises until the emergency service...

Страница 10: ...re not suitable as early warning Smoke Alarms Some fires produce Carbon Monoxide but the response characteristics of these CO Alarms are such that they would not give sufficient warning of fire Smoke Alarms must be fitted to give early warning of fire 7 The CO Alarm does not detect the presence of natural gas methane bottled gas propane butane or other combustible gases Fit combustion Gas Alarms t...

Страница 11: ...there is no source of hydrogen such as batteries being charged e g on boats or in Uninterruptable Power Supplies UPS 5 Ensure there is not excessive smoke or fumes from smoking devices 6 Ensure that there are no problems with the other RF interconnected Alarms and that all Alarms are housecoded correctly 7 Press the test hush button to silence the alarm If the unit continues to sound it is possibl...

Страница 12: ...ioélectrique subi même si le brouillage est susceptible d en compromettre le fonctionnement IC 8310A RE115 8310A RE215 8310A RE315 WARRANTY Resolution Products Inc will replace non portable products that are defective in their first five 5 years and all defective portable products in their first two 2 years 47 0024 00 RevA 2018 02 01 Tech Support Line 877 260 5578 www ResolutionProducts com FCC NO...

Отзывы: