Overview

•  Pre-assembled twin-line pump station
•  Integrated 

DeltaSol

®

 BX Plus controller (optional)

•  Energy-saving high-efficiency pump
•  Safety assembly with connection for the expansion vessel, safety 

valve and pressure gauge

•  Ball valves in flow and return with non-return valves and thermom-

eter handles

•  Flowmeter
•  Air separator for manual venting of the solar thermal system
•  Fill and drain valves
•  Wall mounting bracket and mounting material

Technical data 

Circulating pump: Wilo Stratos PARA 15/1-9 (

ErP power consumption of the 

pump

*

45 W)

Safety valve: 6 bar
Pressure gauge: 0 … 10  bar
Flowmeter:  5 … 35  l/min
For low-flow systems (0.2 l/min/m²) with collector fields of up to 100 m²
For high-flow systems (0.5 l/min/m²) with collector fields of up to 50 m²
Take the pressure loss of the system into account!
Ball valves in flow and return with non-return valves and thermometer 
handles

Non-return valve: Opening pressure 20 mbar, openable

Thermometer:  0 … 160 °C

 

Connection to expansion vessel: 1" ET, flat sealing
Outlet safety valve: 1" IT
Connections to the solar pipes: 1" IT
Maximum temperature flow / return:  120 °C / 95 °C
Maximum pressure: 6 bar
Medium: Water with max. 50 % glycol

Dimensions: approx. 470 x 380 x 220 mm (with insulation) 
Distance centres: 125 mm 
Distance centre/wall: 73 mm

Material: Fittings: brass 
Seals: AFM 34 
O-rings: FKM 
Insulation: EPP foam

*

 50 % of the rated  

power consumption

Pump characteristic / pressure loss characteristic

335

212

90

125

82

Pr

essur

e loss [kP

a]

Flow rate [m³/h]

Deliv

er

y height [m]

0

0

2

4

6

8

1

2

3

1,5

0,5

2,5

3,5

4044 / 15 PWM1 / 85 PWM2

3638 / 25 PWM1 / 75 PWM2

3231 / 35 PWM1 / 65 PWM2

2825 / 45 PWM1 / 55 PWM2

2419 / 55 PWM1 / 45 PWM2

2012 / 65 PWM1 / 35 PWM2

4450 / 

5 PWM1 / 

95 PWM2

Wilo Stratos PARA 1-9 min. 

Wilo Stratos PARA 1-9 max.

FlowSol

® 

XL

1606 / 75 PWM1 / 25 PWM2
1200 / 85 PWM1 / 15 PWM2

Содержание FlowSol XL

Страница 1: ...this RESOL product Please read this manual carefully to get the best performance from this unit Please keep this manual carefully FlowSol XL www resol com Manual en Installation Operation Commissioni...

Страница 2: ...trical works Initial installation must be effected by the system owner or qualified personnel named by the system owner Contents 1 Overview 3 2 Mounting the station 4 3 Flushing and filling the solar...

Страница 3: ...m into account Ball valves in flow and return with non return valves and thermometer handles Non return valve Opening pressure 20 mbar openable Thermometer 0 160 C Connection to expansion vessel 1 ET...

Страница 4: ...ing bracket Insert the flow and return lines into the wall mounting bracket and fasten them by means of the locking springs Connect the pipework between pump station and store and collector re spectiv...

Страница 5: ...essary Slowly discharge the heat transfer fluid by means of the drain valve 3 until the operating pressure is set Remove the hoses of the filling and flushing station and screw the caps onto the fill...

Страница 6: ...he union nut at the pressure side Now dismount the pump 10 Safety devices The pump station is equipped with a diaphragm safety valve which corresponds to the relavant directives and regulations For in...

Страница 7: ...ing solar thermal and heating systems Its many thought out details facilitate transport operation and cleaning the attractive design makes it the ideal companion for a professional performance Heat tr...

Страница 8: ...r the completeness of the drawings and texts of this manual they only represent some examples They can only be used at your own risk No liability is assumed for incorrect incomplete or false informati...

Отзывы: