D e lt a S o l
®
C/3
© RESOL 11150 deltasol_c/3.monen.ind
d
17
|
Pump starts for a short moment, switches-on/off
again,etc.
Is the temperature diffe-
rence at the controller
too small?
no
yes
Wrong position of the
collector sensor?
yes
Change
∆
T
on
and
∆
T
off
correspondingly
.
Mount the collector sen-
sor at solar flow (warmest
collector output); use the
immersion sleeve of the
respective collector.
Pump starts up very late..
The temperature difference between the store and the
collector increases enormously during operation; the
collector circuit cannot divert the heat.
Collector circuit pump
defective ?
no
yes
Heat exchanger calcified?
yes
Check / replace it
Decalify it
no
Heat exchanger blocked?
yes
no
Clean it
Heat exchanger too
small?
yes
Repalce with correctly
sized one
no
Plausibility control of the
tube collector function
Change
∆
T
on
and
∆
Toff
correspondingly
Switch-on-temperature
difference
∆
T
on
too
large?
no
yes
Non-ideal position of coll-
ector sensor (e.g. flatscrew
sensor instead of sensor in
immersion sleeves?)
o.k.
no
Pump is overheated, but no heat transfer from the colle-
ctor to the store, flow and return have the same tempe-
rature; perhaps also bubble in the lines
Vent the system; in crease
system pressure to at
least static primary pres-
sure plus 0,5 bar; if neces-
sary increase the pressure,
switch the pump on and
off for a short time
Air in the system?
no
yes
Is the collector circuit
blocked at the dirt trap?
yes
Clean the dirt trap
5.1Various
Activate tube collector
function if necessary.
yes
o.k.