Pump  starts  for  a  short  moment,  switches-on/off  
again,etc.

Is the temperature diffe-
rence at the controller 
too small?

no 

yes

Wrong position of the 
collector sensor?

yes

Change

 ∆

T

on

 and 

T

off 

correspondingly

.

Mount the collector sen-
sor at solar flow (warmest 
collector output); use the 
immersion sleeve of the 
respective collector.

Pump starts up very late..

The temperature difference between the store and the 
collector increases enormously during operation; the 
collector circuit cannot divert the heat.

Collector circuit pump 
defective ?

no

yes

Heat exchanger calcified?

yes

Check / replace it

Decalify it

no

Heat exchanger blocked?

yes

no

Clean it

Heat exchanger too 
small?

yes

Repalce with correctly 
sized one

no

Plausibility control of the 
tube collector function

Change

 ∆

T

on

 and 

Toff 

correspondingly

Switch-on-temperature 
difference 

T

on 

too 

large?

no

yes

Non-ideal position of coll-
ector sensor (e.g. flatscrew  
sensor instead of sensor in 
immersion sleeves?)

o.k.

no

Pump is overheated, but no heat transfer from the colle- 
ctor to the store, flow and return have the same tempe- 
rature; perhaps also bubble in the lines

Vent the system; in crease 
system  pressure  to  at 
least static primary pres-
sure plus 0,5 bar; if neces-
sary increase the pressure, 
switch the pump on and 
off for a short time

Air in the system?

no

yes

Is the collector circuit 
blocked at the dirt trap?

yes

Clean the dirt trap

5.1Various

Activate  tube  collector 
function if necessary.

yes

o.k.

Содержание DeltaSol C/3

Страница 1: ...com Thank you for buying this RESOL product Please read this manual carefully to get the best performance from this unit RESOL D e lt a S o l C 3 Mounting Connection Operation Troubleshooting Examples...

Страница 2: ...ppropriate usage This product is to be used in simple solar thermal systems in com pliance with the technical data specified in these instructions see p 3 Improper use excludes all liability claims In...

Страница 3: ...ng plastic PC ABS and PMMA Protection type IP 20 DIN 40050 Ambient temp 0 40 C Dimensions 172 x 110 x 46 mm Mounting wall mounting mounting into patch panels is possible Display system monitor for sys...

Страница 4: ...controller must additionally be supplied from a double pole switch with contact gap of at least 3 mm Please pay atten tion to separate routing of sensor cables and mains cables 1 Unscrew the cross hea...

Страница 5: ...neutral conductor N 20 phase L 12 ground clamp The controller is equipped with the RESOL VBus for data transfer with and energy supply to external modules The connection is carried out at the two term...

Страница 6: ...adjustment mode scroll down in the display menu and press the forward button 1 for approx 2 seconds after you have reached the last display item If an adjustment value is shown on the display the icon...

Страница 7: ...n the toolbar indicate the actual system status toolbar 2 2 System Monitoring display Monitoring Display Symbol normal flashing relay 1 active relay 2 active store maximum limitation active maximum st...

Страница 8: ...sensor collector with collector sensor pump store with heat exchanger afterheating with burner symbol temperature sensor 2 3 Flashing codes Pump symbols are flashing during the initialisation phase S...

Страница 9: ...the automatic mode with typical settings The pre programmed system scheme is Arr 1 2 select adjustment channel Arr change to the mode see 2 1 select the arrangement via the Arr index number save the a...

Страница 10: ...urs relay 2 11 kWh Heat quantity kWh 12 MWh Heat quantity MWh 12 time clock time 11 Arr 1 2 Arrangement DT O x x Switch on temperature difference 12 DT F x x Switch off temperature difference 12 S MX...

Страница 11: ...Only if the temperature sensors are connected dis played will S3 and S4 be displayed Display of the current temperature at the sensor TRF temperature return The operating hours counter accumulates the...

Страница 12: ...glycol 2 ethylene glycol 3 Tyfocor LS G LS The flow rate as well as the reference sensors S1 flow and S4 return are used for calculating the heat quantity sup plied It is shown in kWh in the channel...

Страница 13: ...ler will switch off the solar pump R1 in order to protect the system against overheating collector emergency shutdown The factoring setting is 140 C but it can be changed within the adjustment range o...

Страница 14: ...S MX is reached the controller keeps the solar pump running in order to prevent the collector from being overheated The store temperature may increase but only up to 95 C emergency shutdown of the sto...

Страница 15: ...ed out 4 1 17 Operating mode HND HND1 HND2 Operating mode OFF relay off flashing AUTO relay in automatic operation ON relay on flashing HAND HND1 HND2 Operating mode Adjustment range OFF AUTO ON Facto...

Страница 16: ...VBus 9 10 T2A 100 240V 50 60 Hz IP 20 Temp Sensor Pt1000 The symbol and the are shown Sensor fault An error code instead of a temperature is shown on the sensor display channel 88 8 888 8 Cable is br...

Страница 17: ...it no Heat exchanger blocked yes no Clean it Heat exchanger too small yes Repalce with correctly sized one no Plausibility control of the tube collector function Change Ton and Toff correspondingly S...

Страница 18: ...o Does the pump start up in manual operation yes No current check fuses replace them and check power supply The adjusted temperature difference for starting the pump is to high choose a value which ma...

Страница 19: ...he overvoltage protection RESOL SP1 Sensos Our product range includes high precision platin tempe rature sensors flatscrew sensors outdoor temperature sensors indoor temperature sensors cylindrical cl...

Страница 20: ...he Regelungen GmbH This especially applies for copies translations micro films and the storage into electronic systems Editor RESOL Elektronische Regelungen GmbH Important notice We took a lot of care...

Отзывы: