4.1.9 Maximum store temperature 

If the adjusted maximum temperature is exceeded, the store 
will no longer be loaded in order to avoid damage caused by 
overheating. If the maximum store temperature is exceeded,  

will be shown.

Please note:

 The controller is equipped with a store emer-

gency  shutdown  function,  which  prevents  the  store  from 
being loaded when the store temperature exceeds 95 °C.

S MX

Maximum store temp. 
Adjustment range: 2..95 °C 
Factory setting: 60 °C

CMX: 

Collector maximum temp. 
Adjustment range 100... 190 °C 
Factory setting 120 °C

4.1.11 System cooling 

When the adjusted maximum store temperature is reached, 
the system stagnates. If the collector temperature increases 
to the adjusted maximum collector temperature (

CMX

), 

the solar pump is activated until the collector temperature 
falls below the maximum collector temperature. The store 
tempe rature may increase (subordinate active maximum 
store temperature), but only up to 95 °C (emergency shut-
down of the store).

OCX

Option system cooling 
Adjustment range OFF ... ON 
Factory setting OFF

4.1.10  Collector emergency shutdown temperature

If the adjusted collector emergency shutdown temperature 
(

EM

) is exceeded, the controller will switch off the solar 

pump (R1) in order to protect the system against overheating 
(collector  emergency  shutdown). The  factoring  setting  is 
140 °C but it can be changed within the adjustment range 
of 110 ... 200 °C.   (flashing) is displayed.

EM

:

Collector emergency shut-
down temperature 
Adjustment range: 

 

110 ... 200 °C 
Factory setting: 140 °C

If OREC is additionally enabled:

If the store tempe rature is higher than the maximum store 
temperature (

S MX

) and if the collector temperature is at 

least 5 K below the store temperature, the solar system 
remains activated until the store is cooled down below the 
adjusted maximum temperature (

S MX

) via the collector 

and the pipework. 
If the system cooling function is enabled, 

 (flashing) is 

shown on the display. Due to the cooling function, the sys-
tem will have a longer operation time on hot summer days 
and guarantees thermal relief of the collector field and the 
heat transfer fluid. 

CMN

:

Minimum collector temperature  
Adjustment range: 10 ... 90 °C 
Factory setting: 10 °C

4.1.12   Option collector minimum limitation

OCN: 

Mimimum collector function 
Adjustment range: OFF / ON 
Factory setting: OFF

The minimum collector temperature is the minimum 
temperature which must be exceeded for the solar pump 
(R1) to switch on. The minimum temperature prevents the 
pump from being switched on too often at low collector 
temperatures. If the temperature falls below the minimum 
temperature,   (flashing) is shown on the display.

Содержание DeltaSol C/3

Страница 1: ...com Thank you for buying this RESOL product Please read this manual carefully to get the best performance from this unit RESOL D e lt a S o l C 3 Mounting Connection Operation Troubleshooting Examples...

Страница 2: ...ppropriate usage This product is to be used in simple solar thermal systems in com pliance with the technical data specified in these instructions see p 3 Improper use excludes all liability claims In...

Страница 3: ...ng plastic PC ABS and PMMA Protection type IP 20 DIN 40050 Ambient temp 0 40 C Dimensions 172 x 110 x 46 mm Mounting wall mounting mounting into patch panels is possible Display system monitor for sys...

Страница 4: ...controller must additionally be supplied from a double pole switch with contact gap of at least 3 mm Please pay atten tion to separate routing of sensor cables and mains cables 1 Unscrew the cross hea...

Страница 5: ...neutral conductor N 20 phase L 12 ground clamp The controller is equipped with the RESOL VBus for data transfer with and energy supply to external modules The connection is carried out at the two term...

Страница 6: ...adjustment mode scroll down in the display menu and press the forward button 1 for approx 2 seconds after you have reached the last display item If an adjustment value is shown on the display the icon...

Страница 7: ...n the toolbar indicate the actual system status toolbar 2 2 System Monitoring display Monitoring Display Symbol normal flashing relay 1 active relay 2 active store maximum limitation active maximum st...

Страница 8: ...sensor collector with collector sensor pump store with heat exchanger afterheating with burner symbol temperature sensor 2 3 Flashing codes Pump symbols are flashing during the initialisation phase S...

Страница 9: ...the automatic mode with typical settings The pre programmed system scheme is Arr 1 2 select adjustment channel Arr change to the mode see 2 1 select the arrangement via the Arr index number save the a...

Страница 10: ...urs relay 2 11 kWh Heat quantity kWh 12 MWh Heat quantity MWh 12 time clock time 11 Arr 1 2 Arrangement DT O x x Switch on temperature difference 12 DT F x x Switch off temperature difference 12 S MX...

Страница 11: ...Only if the temperature sensors are connected dis played will S3 and S4 be displayed Display of the current temperature at the sensor TRF temperature return The operating hours counter accumulates the...

Страница 12: ...glycol 2 ethylene glycol 3 Tyfocor LS G LS The flow rate as well as the reference sensors S1 flow and S4 return are used for calculating the heat quantity sup plied It is shown in kWh in the channel...

Страница 13: ...ler will switch off the solar pump R1 in order to protect the system against overheating collector emergency shutdown The factoring setting is 140 C but it can be changed within the adjustment range o...

Страница 14: ...S MX is reached the controller keeps the solar pump running in order to prevent the collector from being overheated The store temperature may increase but only up to 95 C emergency shutdown of the sto...

Страница 15: ...ed out 4 1 17 Operating mode HND HND1 HND2 Operating mode OFF relay off flashing AUTO relay in automatic operation ON relay on flashing HAND HND1 HND2 Operating mode Adjustment range OFF AUTO ON Facto...

Страница 16: ...VBus 9 10 T2A 100 240V 50 60 Hz IP 20 Temp Sensor Pt1000 The symbol and the are shown Sensor fault An error code instead of a temperature is shown on the sensor display channel 88 8 888 8 Cable is br...

Страница 17: ...it no Heat exchanger blocked yes no Clean it Heat exchanger too small yes Repalce with correctly sized one no Plausibility control of the tube collector function Change Ton and Toff correspondingly S...

Страница 18: ...o Does the pump start up in manual operation yes No current check fuses replace them and check power supply The adjusted temperature difference for starting the pump is to high choose a value which ma...

Страница 19: ...he overvoltage protection RESOL SP1 Sensos Our product range includes high precision platin tempe rature sensors flatscrew sensors outdoor temperature sensors indoor temperature sensors cylindrical cl...

Страница 20: ...he Regelungen GmbH This especially applies for copies translations micro films and the storage into electronic systems Editor RESOL Elektronische Regelungen GmbH Important notice We took a lot of care...

Отзывы: