EN1R-1020 1004RANE 

 

 

 

 

INSTALLATION 

IMPORTANT 

Take care that installer is a trained experienced 

service person. 

Turn off gas supply before starting installation. 

Disconnect power supply to prevent electrical shock 

and/or equipment damage. 

Do not remove seals over inlet and outlet until the 

device is ready to be installed. 

If M5 air pressure connection is not to be used, it is 

recommanded to push a dust cap into the hole. 

Mounting position 

The gas control can be mounted 0 to 90

° 

in any direction 

from the upright position, i.e. from the position when electric 

coils are on top. 

Main gas connection 

IMPORTANT 

During tightening the main gas connection assure 

the gas control is secured against rotation by using 

the right spanner in order to ensure right mounting 

position and avoid excessive forces (see figure 5). 

 

Ensure the gas flows in the same direction as the 

arrow on the bottom of the gas control. 

 

Fig. 5. 

 

Gas controls with internal thread 

  Take care that dirt cannot enter the gas control during 

handling. 

  Use a sound taper fitting with thread according to ISO 7-1 

or a piece of new, properly reamed pipe, free from swarf. 

  Do not thread or tighten the pipe or pipe fitting too far (see 

table below). Otherwise distortion and malfunction could 

result. 

 

Pipe size (inch) 

Max. length of pipe thread (mm) 

3

/

8

 

14 

1

/

2

 

18.6 

  Apply a moderate amount of good quality thread 

compound to the pipe or fitting only, leaving the two end 

threads bare.If permitted by local safety regulations PTFE 

tape may be used as an alternative. 

 

Gas controls for flange connection 

  Insert ”O”-ring in the groove of each flange. If necessary 

grease ”O”-ring slightly to keep it in place. 

  Mount gas control between flanges using the four screws 

for each flange. 

Gas controls with external thread connection 

WARNING 

Fastening torque flat sealing ring only applicable for 

type Klingersil C4324 

 

With

1

/

2

” nut and flat sealing ring for pipe 14mm (see fig 5.) 

Nut:  drawing: ........................................ 45.006.583-005 

Flat sealing ring size: 

18 x 

10 x 1.5 mm: 

drawing ......................................... 45.006.582-002 

Fastening torque: maximum 40 Nm 

minimum 25 Nm 

Pipe end construction: see fig.: 8. 

With 

1

/

2

” nut and flat sealing ring for pipe 15 mm (see fig 5.) 

Nut:  drawing: ........................................45.006.583-004 

Flat sealing ring size: 

18 x 

10 x 1.5 mm 

drawing .........................................45.006.582-002 

Fastening torque: maximum 40 Nm 

minimum 25 Nm 

Pipe end construction: see fig.: 9. 

 

 

Fig. 6. External thread connection with nut and flat 

sealing ring 

 

With 

3

/

4

” nut and olive (see fig. 6.) 

Pipe diameter: 15 mm 

Nut:  drawing: ........................................45.006.583-003 

Fastening torque: maximum 50 Nm 

minimum 30 Nm 

Pipe end construction: square off end of tubing and 

remove burrs 

Содержание VK41 Series

Страница 1: ...V B E gas controls perform all the functions required to safely regulate gas flow to the main burner of domestic central heating equipment warm air furnaces back boilers and water heaters Models VK41 0 series line voltage gas control with pilot burner connection two automatic shut off valves and pilot burner connection for direct spark ignition DSI or hot surface ignition HSI applications VK41 5 s...

Страница 2: ...e applicable Standard at end outlet M8 x 1 for 4 mm outer diameter tubing M5 x 0 8 3 37 6 mm full thread 94 8 68 3 Side outlet Pressure tab 9 24 34 Cap screw offset adjustment 24 Side outlet optional 84 5 Hole 2 6 mm to connect ignition control Inlet Fig 1 Dimensional drawing standard version Fig 2 Dimensional drawing Quick connect and Throttle versions Pilot outlet M8 x 1 6H for 4 mm tubing 29 Ai...

Страница 3: ... indication on the housing is the maximum inlet pressure at which the gas control functions safely Maximum air pressure 8 mbar without outlet gas pressure before ignition 20 mbar with outlet gas pressure present after ignition Offset range 0 4 mbar 0 2 mbar with coils sidewards 0 24 mbar 0 36 mbar with coils on top Inlet End outlet Side outlet Body length mm Flanged Flanged 105 Flanged Flanged 105...

Страница 4: ...d with min 6 mm full thread In case of side outlet the three holes for mounting the flange are provided with M5 thread with a minimum of 6 mm full thread Electrical data Coil indication Supply voltage 220 240 Vrac 220 V 50 60 Hz using rectifier 240 V 50 60 Hz using rectifier 110 Vrac 110 V 50 60 Hz using rectifier 24 Vrac 24 V 50 60 Hz using rectifier Electrical connection Molex 1 1 square pin hea...

Страница 5: ...o far see table below Otherwise distortion and malfunction could result Pipe size inch Max length of pipe thread mm 3 8 14 1 2 18 6 Apply a moderate amount of good quality thread compound to the pipe or fitting only leaving the two end threads bare If permitted by local safety regulations PTFE tape may be used as an alternative Gas controls for flange connection Insert O ring in the groove of each...

Страница 6: ...ling ring connection 1 Fig 10 Pipe dia 15 mm for flat sealing ring connection 23 4 0 15 Fig 11 Pipe end for O ring connection 1 Fig 12 Pipe dia 15 mm for flat sealing ring connection 1 Fig 13 Pipe dia 18 mm for flat sealing ring connection Pilot gas connection at outlet side if applicable Square off the end of tubing and remove burrs Slip compression fitting over 4 mm tubing Insert tubing into aut...

Страница 7: ...control seems to operate normally but does not detect flame check for right polarity of power supply line neutral Checking flame current The minimum value should be in accordance with the specified value of the ignition control To check flame current connect a DC micro Ampèremeter between flame sensing wire and flame sensing rod If flame current is insufficient check that flame sensing rod is full...

Страница 8: ...on page 2 Apply a screwdriver to turn the screw To decrease the flow turn screw clockwise To increase flow turn screw counter clockwise WARNING Applied torque may not exceed 8 Ncm CHECKOUT After any adjustment check pressure taps and gas connections with an approved leak detection fluid for gas leakage After any adjustment set appliance in operation and observe a complete cycle to ensure that all ...

Отзывы: