R7284 SERIES ELECTRONIC OIL PRIMARY

69-2500—02

4

Error History Screens (Advanced 
Interface)

For all Error History screens, pressing “i” returns to the Normal 

Screen. 

From the home screen, press the up button to display most recent 

error.  

Press the up button again to proceed to the next most recent 

error or the down button to return to the previous error screen.

These three screens transition every 3 sec.

If no more errors are logged, the display shows “Error History 

End.”

Basic User Interface

The basic user interface consists of 3 buttons and an LED. Simple 

diagnostic information can be obtained through the interaction of 

the buttons and LED.

R7284 Status (Basic Interface)

Table 1. LED Codes.

Description

LED Code

Standby

Pulse (1/4 sec. ON, 4 sec OFF)

Call for Heat

Heartbeat (1/2 sec bright, 1/2 sec dim) *

Flame proven

On solid

Recycle

2 second ON, 2 second OFF flashing

Lockout

1/2 second on, 1/2 second OFF flashing

Interrupt

OFF

“i” button

Flame Strength Indication

Up button

Most recent error

Down button

Next most recent error

Содержание R7284 Series

Страница 1: ...and releasing the up arrow button during the Trial For Ignition In the advanced interface PUMP PRIME is displayed on the display along with the time left on the Trial for Ignition TFI Pressing the up arrow button adds a minute to the TFI time for a maximum of 10 additional minutes press the up arrow button 10 times Pressing the down arrow button subtracts a minute from the TFI time There is no vis...

Страница 2: ...ed Interface Installer setup is entered by pushing all three buttons simultaneously for 2 seconds NOTE Not all parameters are adjustable in all models Param eters not available for adjustment will display Locked when an attempt is made to modify them Pressing up or down during the Ignition Trial enters pump prime Each press of the up button adds a minute each press of the down button subtracts a m...

Страница 3: ... second increments from 0 to 8 minutes Configuration of the TT terminals vs an internal jumper This option allows you to jumper the TT terminals electronically so no physical jumper is needed Controls sparking during On Delay period Controls sparking during Run mode Interrupted vs Intermittent ignition Number of resets allowed before Restricted Lockout Appliance configuration boiler furnace water ...

Страница 4: ...more errors are logged the display shows Error History End Basic User Interface The basic user interface consists of 3 buttons and an LED Simple diagnostic information can be obtained through the interaction of the buttons and LED R7284 Status Basic Interface Table 1 LED Codes Description LED Code Standby Pulse 1 4 sec ON 4 sec OFF Call for Heat Heartbeat 1 2 sec bright 1 2 sec dim Flame proven On...

Страница 5: ...he down arrow button displays the next most recent error Once the up or down arrow is pushed the LED will display the most recent or next most recent alarm by blinking the error code See Table 3 R7284 Error Codes Basic Interface Table 3 Error Codes Flame Strength Indication Number of 1 2 sec flashes Cad Cell less than 400Ω 1 400Ω Cad Cell 800Ω 2 800Ω Cad Cell 1600Ω 3 1600Ω Cad Cell 6100Ω 4 Cad Cel...

Страница 6: ...R7284 SERIES ELECTRONIC OIL PRIMARY 69 2500 02 6 ...

Страница 7: ...R7284 SERIES ELECTRONIC OIL PRIMARY 7 69 2500 02 ...

Страница 8: ...gies Inc All rights reserved This product is manufactured by Resideo Technologies Inc and its affiliates www resideo com Resideo Technologies Inc 1985 Douglas Drive North Golden Valley MN 55422 1 800 468 1502 69 2500 02 M S Rev 03 21 Printed in United States ...

Отзывы: