R7284 SERIES ELECTRONIC OIL PRIMARY
3
69-2500—02
NOTE:
The Ignition Time is only available for adjustment
during the first 100 cycles of operation. After
100 cycles the Ignition Time is locked in and can no
longer be adjusted.
Select between English, French, or Spanish by
using the up or down buttons and the “i” button
to select.
Adjustment of the Valve On Delay in five second
increments.
Ignition (lockout) Time adjustment.
Adjustment of the Burner Off Delay. Burner Off
Delay can be adjusted in 15 second increments
from 0 to 8 minutes.
Configuration of the TT terminals vs. an “internal
jumper.” This option allows you to jumper the TT
terminals electronically so no physical jumper is
needed.
Controls sparking during On Delay period.
Controls sparking during Run mode (Interrupted
vs. Intermittent ignition).
Number of resets allowed before Restricted
Lockout.
Appliance configuration (boiler, furnace, water
heater) for EnviraCOM™.
Enable advanced diagnostics mode and error
history. Selecting NO allows access to error
history and diagnostics only by entering Installer
Setup.
Exit installer setup.
If “QUIT” is selected, the user is prompted with a
screen asking if it is desired to rebaseline the
control.