REOTRON MDW 700
Operating instructions
7
Failure relay (clamp 44, 45, 46)
In case of an error (for example “Error Hot”) the contact 45 – 46 closes.
Clamp assignment:
44
normally close (NC)
45
change-over contact (CO)
46
normally open (NO)
4.0 Technical Data
Type
Input voltage [V]
Output voltage [V]
Output current[A]
MDW 700-10/230 - 400
230 – 400 V +/-10% 50/60Hz
Ue – 3 V
0…10
MDW 700-25/230 – 400
0...25
MDW 700-50/230 - 400
0…50
MDW 700-80/230 - 400
0…80
MDW 700-110/230 - 400
0…110
MDW 700-150/230 - 400
0…150
MDW 700-200/230 - 400
0…200
MDW 700-300/230 – 400
0...300
MDW WK 700-115/230 - 400
0…115
MDW WK 700-160/230 - 400
0…160
MDW WK 700-250/230 - 400
0…250
MDW WK 700-350/230 - 400
0…350
MDW WK 700-450/230 - 400
0…450
MDW WK 700-600/230 - 400
0…600
Load
R / RL, Transformer Load max. Induction 1,45 Tesla
Set point Inputs
current
voltage or power
0...+10 V
22 kR
0(4)...20 mA
100 R
Potentiometer 10 KR, internal Display
External feedback U
0...+/-5 V
22 kR
External feedback I
0...+/-5 V
22 kR
Feedback monitor / U or P
0...+10 V, DC
5 mA
Feedback monitor I
0...+10 V, DC
5 mA
Enable
Contact
5 mA or 24 V, DC
5 mA
Faulty relay
Change over contact 250 V, 1 A
Protection
IP 20
Operating temperature
0... + 45 °C
Liquid temperature WK Type 25 °C Input
Liquid quantity
H
2
O, 6 ltr/min
Storing temperature
-20...+75 °C
Rel. air humidity
93 % without condensation and surface water coning
Contamination level
degree 1 (IEC 664)
Mounting direction
Vertical (Connections below)
Mounting height
1000 m, 0,5 % rated current reduction for each additional 100 m
WK = water-cooled
4.1 Limited the output voltage by using line input from 230V or 240V
By using the controller at line input from 230 or 240V you must limited the output voltage under
Code 020 – point „u“. At line= 230V to 57% and at line= 240V to 60%.
5.0 Declaration of Conformity
In order to comply with the EMC requirements, when using phase angle controllers it is necessary to build
in a suitable filter in the line input, e.g. Book-style filter CNW 207 or CNW 107.