![Reo Elektronik REOTRON MDW 700 Скачать руководство пользователя страница 12](http://html.mh-extra.com/html/reo-elektronik/reotron-mdw-700/reotron-mdw-700_operating-instructions-manual_1443245012.webp)
REOTRON MDW 700
Operating instructions
11
8.0 Settings
The following table contains all the available key settable parameters.
The unit is supplied with factory settings that can be recalled from access code “C210” under FAC. User
codes can be saved under code “C143” and then recalled with code “C210” under USPA.
Parameter:
Code
Factory
Default
Menu
Code
Set point – when internal set point is selected only!
•
Voltage set point
0...100 %
U.
0 %
002
•
Current set point
0...100 %
I.
0 %
002
•
Power set point
0…100 %
P.
100 %
002
Configuration
•
External set point OFF
0 / I
E.S.O
0
003
•
4...20 mA (only when E.S.O. = 0)
0 / I
4.20
0
003
•
Enable Inverse
0 / I
-En.
0
003
•
External Voltage set point
0 / I
E.F.U.
0
003
•
External Current set point
0 / I
E.F.I.
0
003
•
Power regulation
0 / I
E.F.P
0
003
•
Full wave control
0 / I
F.S.P
0
003
•
Ready relay
0 / I
r.b
0
003
Parameter
•
Minimum Output Voltage (without set point)
0...100 %
U.
0 %
020
•
Minimum Output Current (without set point)
0...100 %
I.
0 %
020
•
Minimum Output Power (without set point)
0...100 %
P.
100 %
020
•
Maximum Output Voltage (Limit)
25...100 %
u
100 %
020
•
Maximum Output Current (Limit)
25...100 %
i
100 %
020
•
Maximum Output Power (Limit)
25...100 %
p
100 %
020
•
Voltage Regulator – P Characteristic
1...100
P.U.
20
020
•
Current Regulator - P Characteristic
1...100
P.I.
15
020
•
Power Regulator - P Characteristic
1...100
P.P.
15
020
•
Soft Start (ramp)
0...60 Sec.
/.
0,1
020
•
Soft Stop (ramp)
0...60 Sec.
\
0,1
020
Interface
•
Interface ON
0 / I
S.I.F.
0
017
Service
•
Save User Parameter
PUSH
143
•
Restore Factory Default Settings
FAC.
210
•
Enable advanced Service mode
0 / I
En.S.
0
127
•
Display software version
001
Содержание REOTRON MDW 700
Страница 27: ...REOTRON MDW 700 Operating instructions 26 ...