28
Fusing
AWG
16
14
12
10
8
6
4
2
0
Max.
Current
55A
40A
30A
25A
18A
75A
95A
130A
170A
**Utilize 1.56 Sizing Factor (SF)
Different safety factors could be used. The purpose is to oversize.
Series:
Total Amperage
= I
sc
1
= I
sc
2
* SF
Parallel
Total Amperage
=
(
I
sc
1
+ I
sc
2
)
* SF
The NEC code requires the overcurrent protection shall not exceed 15A for
14AWG, 20A for 12 AWG, and 30A for 10AWG copper wire.
NEC Maximum Current for different Copper Wire Sizes
Fuse from Controller to Battery
Fuse from Solar Panel(s) to Controller
Ex. 200W; 2 X 100 W panels
= 5.75A * 1.56
= 8.97
=(5.75A + 5.75A)* 1.56 = 17.94
Fuse = 18A fuse
Fuse
=
9A fuse
NOTE
Fusing is a recommended in PV systems to provide a safety measure for connections going from
panel to controller and controller to battery. Remember to always use the recommended wire
gauge size based on the PV system and the controller.
NOTE
Controller to Battery Fuse = Current Rating of Charge Controller
Ex. 20A MPPT CC = 20A fuse from Controller to Battery
Содержание Rover 100A
Страница 1: ...Rover 100A Version 1 4 Maximum Power Point Tracking Solar Charge Controller ROVER SERIES ...
Страница 12: ...1 Remove Cover 2 Connect Battery 3 Connect Solar Panels 11 ...
Страница 34: ...3 48 Volt System Conversion Efficiency 2 24 Volt System Conversion Efficiency 33 ...
Страница 35: ...34 NOTE Dimensions in millimeters mm Dimensions 443 320 270 280 4Xφ8 4Xφ12 110 50 ...