Loop Installation 

The  vehicle  detection  characteristics  of  an  inductive  loop  detector  are  greatly  influenced  by  the  loop  size  and 
proximity to  moving  metal objects such as gates.  Vehicles such as small motorcycles and high bed trucks can be 
reliably  detected  if  the  proper  size  loop  is  selected.    If  the  loop  is  placed  too  close  to  a  moving  metal  gate,  the 
detector may detect the gate.  The diagram below is intended as a reference for the dimensions that will influence 
the detection characteristics. 

General Rules 

1. 

The  detection  height  of  a  loop  is  2/3  the 
shortest  leg  (A  or  B)  of  the  loop.    Example:  
Short  leg  =  6  feet,  Detection  Height  =  2/3  x  6 
feet = 4 feet. 

A = 

6 ft 

9 ft 

12 ft 

15 ft 

18 ft 

21 ft 

C = 

3 ft 

4 ft 

4.5 ft 

5 ft 

5.5 ft 

6 ft 

2. 

As the length of leg A is increased, distance C 
must also increase. 

3. 

For  reliable  detection  of  small  motorcycles, 
legs A and B should not exceed 6 feet. 

Loop Installation - Saw Cut Type

 

Mark the loop layout on the pavement.  Remove sharp inside corners that can damage the loop wire insulation. 

Set  the  saw  to  cut  to  a  depth  (typically  2"  to  2.5")  that  ensures  a  minimum  of  1"  from  the  top  of  the  wire  to  pavement 
surface.  The saw cut width should be larger than the wire diameter to avoid damage to the wire insulation when placed in 
the saw slot.  Cut the loop and feeder slots.  Remove all debris from the saw slot with compressed air.  Check that the 
bottom of the slot is smooth. 

It is highly recommended that a continuous length of wire be used to form the loop and feeder to the detector.  Loop wire 
is typically 14, 16, 18, or 20 AWG with cross-linked polyethylene insulation.  Use a wood stick or roller to insert the wire to 
the bottom of the saw slot (do not use sharp objects).  Wrap the wire in the loop saw slot until the desired number of turns 
is reached.  Each turn of wire must lay flat on top of the previous turn. 

The wire must be twisted together a minimum of 6 twists per foot from the end of the saw slot to the detector. 

The wire must be held firmly in the slot with 1" pieces of backer rod every 1 to 2 feet.  This prevents the wire from floatin g 
when the loop sealant is applied. 

Apply  the  sealant.    The  sealant  selected  should  have  good  adhering  properties  with  contraction  and  expansion 
characteristics similar to those of the pavement material. 

 

 

 

A

 

B

 

C

 

A = Loop dimension parallel to the gate

 

B = Loop dimension perpendicular to the gate

 

C = Distance of the loop from the gate

 

SLIDE GATE

 

1/8" to 1/4" SAW SLOT 

THE WIRE IS 
CONTINUOUSLY WOUND 
IN THE LOOP SAW SLOT 
FOR THE REQUIRED 
NUMBER OF TURNS (2 
turns shown) 

 turn 2 

 turn 1 

REMOVE SHARP 
INSIDE CORNERS 

FEEDER SLOT 

END OF SAW CUT 

THE WIRES MUST BE 
TWISTED TOGETHER 
6 TWISTS PER FOOT 
FROM THE END OF 
THE SAW CUT TO 
THE DETECTOR 

Recommended Loop Wire: 

Reno LW-120 for 1/8" slots 

 

Reno LW-116-S for 1/4" slots 

ROAD SURFACE 

MIN 

1" 

SAW SLOT 

SEALANT 

BACKER ROD 
1" piece spaced 
about every 1' 

LOOP WIRE 

3 TURNS 

Loop Perimeter  Number Of Turns 

10 feet - 13 feet 

14 feet - 26 feet 

27 feet - 45 feet 

46 feet - 100 feet 

100 feet and up 

 

Содержание AX2DL-XP

Страница 1: ...d in the table below Fail Safe Fail Secure Power Failure Loop Failure Power Failure Loop Failure Ch 1 Ch 2 Output No Call Call No Call No Call AB BA Output Call Call No Call No Call II Indicators and Controls i Detect Fail LEDs The detector has one green and two red LED indicators that are used to provide an indication of the detector s power status output state and or loop failure conditions The ...

Страница 2: ...to the original sensitivity level This feature is particularly useful in preventing dropouts during the passage of high bed vehicles The factory default setting is OFF no Sensitivity Boost Sensitivity DIP Switches 5 and 6 Each channel has four 4 sensitivity levels DIP switches 5 and 6 select one of the four sensitivity levels available as shown in the table below Use the lowest sensitivity setting...

Страница 3: ...icle can span both loops The expected installation is two loops one after the other in the same lane spaced anywhere from overlapping to 6 feet apart NOTE Contact a Field Engineer at Reno A E regarding loop configurations and loop spacing for specific applications When a vehicle enters the first channel s loop detection area that channel s DETECT LED will flash at a rate of 750 milliseconds ON and...

Страница 4: ...bottom of the slot is smooth 3 It is highly recommended that a continuous length of wire be used to form the loop and feeder to the detector Loop wire is typically 14 16 18 or 20 AWG with cross linked polyethylene insulation Use a wood stick or roller to insert the wire to the bottom of the saw slot do not use sharp objects Wrap the wire in the loop saw slot until the desired number of turns is re...

Отзывы: