Page 6

OA

RA

EA

FA

Pressure Points (4)

HE3XINV

Differential Static Across Core DSP vs. CFM

HE3XINV

DSP 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90

1.0

Fresh Air

 (FA)

CFM 760 1140 1520 1910 2290 2670 3050 3430 3810

Room Air

 (RA)

CFM 750 1120 1490 1860 2240 2610 2980 3350 3730

Measuring Airflow

Equipment Required

• 

A magnehelic gauge or other device capable of measuring 0 

to 1.5 in. water of differential pressure.

• 

2 pieces of natural rubber latex tubing, 1/8” ID, 1/16” Wall 

works the best. NOTE: Be sure to remove cap from pressure 

port before inserting tubing. Insure tubing is well seated 

in pressure ports. NOTE: The tubing should extend in the 

pressure port approx. 1 inch.

Cross Core Static Pressure Measurement Instructions

• 

The individual differential static pressures (DSP) can be 

measured using the installed pressure ports located in the 

front of the units core access doors. NOTE: These ports 

have been carefully located on the unit as to give you the 

most accurate airflow measurement. NOTE: Do not relocate 

pressure ports. 

• 

To read SCFM of Fresh Air (FA) install the “high” pressure side 

(+) of your measuring device to the Outside Air (OA) port and 

the “low” pressure side (-) to the Fresh Air (FA) port.

• 

To read SCFM of Room Air (RA) install the “high” pressure 

side (+) of your measuring device to the Room Air (RA) port 

and the “low” pressure side (-) to the Exhaust Air (EA) port.

• 

Use the reading displayed on your measurement device to 

cross reference the CFM output using the conversion chart. 

NOTE: Be sure to replace cap into pressure port when air 

flow measuring is completed.

HE3XINV Electrical Specifications

NOTE: Proper Wiring Size Selection and Wiring Installation 

are the Responsibility of the Electrical Contractor.

Blower & contactor voltages are specified with order and set at 

factory.

Brake Horsepower at various Blower RPM, Motor Rating, and ESP 

combinations are available on Spec Sheet or from factory.

Electrical Options and Ratings are identified on the Unit Label 

(located near electrical box). Find the complete Unit Model 

Number in the lower left corner of the Unit Label.

Danger of Electrical Shock when servicing an installed 

unit.

ALWAYS DISCONNECT POWER SOURCE BEFORE 

SERVICING! More than one disconnect switch may be 

required. 

Proper Wiring Size Selection and Wiring Installation 

are the Responsibility of the Electrical Contractor.

The  proper  operating  airflow  range  for  this  model  is  750  - 

3300 CFM.

Содержание HE3XINV

Страница 1: ...xhausting of gases through the flue chimney of fuel burning equipment that might be installed in the area affected by this equipment If this unit is exhausting air from a space in which chimney vented...

Страница 2: ...to inside EA Exhaust Air to outside NOTE Airstreams always cross in the energy exchange core Duct Connections as Labeled Alternate Duct Connections RA EA FA OA RA EA FA OA The fresh air inlet should...

Страница 3: ...ive or negative pressure in the building is desired RenewAire heat recovery ventilators can generally operate with a flow imbalance of up to 20 without appreciable loss in heat recovery efficiency How...

Страница 4: ...IN INDOOR 1 5 MODEL HE 3X 20 16 17 UNUSED IN HE 3X MODELS 24 L LISTED N NON LISTED OPTION 4 OTHERS T TR TRANSFORMER WITH ISOLATION RELAY NONE W WHITE PAINT C CUSTOM PAINT X CUSTOM UNIT 1 2 3 4 5 6 7 8...

Страница 5: ...ns and manometers These also can be used to determine when filters should be cleaned or changed Use Static Taps in Doors to Measure Airflow Rates See Cross Core Static Drop in MEASURING AIRFLOW table...

Страница 6: ...locate pressure ports To read SCFM of Fresh Air FA install the high pressure side of your measuring device to the Outside Air OA port and the low pressure side to the Fresh Air FA port To read SCFM of...

Страница 7: ...DISCONNECT SWITCH MOTOR STARTER MOTOR STARTER FUSE IF INSTALLED AT FACTORY JUMPER PROVIDED MOTOR EA FACTORY SETTINGS Overload Relay Trip Settings Motor Nameplate FLA Overload Relay Mode Settings Manu...

Страница 8: ...Operation Call for EA Blower Operation OUT 24VAC Class II RELAY TRANSFORMER AND CIRCUIT BREAKER DISCONNECT SWITCH MOTOR STARTER MOTOR STARTER FUSE IF INSTALLED AT FACTORY 24VAC JUMPER PROVIDED FACTOR...

Страница 9: ...the control terminals of this unit 5 Unit is not equipped to receive analog signals such as 1 10vdc or 4 20mA 6 Unit is not equipped to communicate directly with Building Management Systems such as B...

Страница 10: ...Connect Terminals 2 3 Connect Switch between Terminals 1 4 UNIT INTERNAL CONTROL WIRING SIMPLIFIED A SWITCH OR NON POWERED CONTROL USING UNIT S 24VAC POWER SUPPLY UNIT INTERNAL CONTROL WIRING SIMPLIFI...

Страница 11: ...34772_006 HE3XINVMan_Jan12 indd Revised 01 2012 www renewaire com Page 11 HE3XINV Replacement Parts A CORES B FILTERS C DOOR D DRAW LATCH E DISCONNECT SWITCH F TRANSFORMER G ISOLATION RELAY H OVERLOAD...

Страница 12: ...Blowers every time you change the filters Confirm bearings are still secure to blower shaft It should not be possible to move the blower shaft back and forth along its length Confirm blower wheel is n...

Отзывы: