Placement of the HE3XINV

The HE3XINV is designed for installation in a sheltered location, 

out of the weather. 

The  preferred  mounting  location  is  sitting  on  a  concrete  floor.  

Unit base may be bolted to floor. The concrete will isolate any 

blower vibration.

Select a location that is central to the inside duct runs, and close 

to both the exhaust duct (to the outside) and the fresh air duct 

(from the outside).

The 

exhaust outlet and outside air inlet

 on the outside of 

the building should be at least 

ten feet apart

 to avoid cross-

contamination.

The exhaust outlet should not dump air into an enclosed space 

or any other structure. The inlets and outlets should be screened 

against insects and vermin and shielded from the weather to 

prevent the entry of rain or snow.

Install the ERV where you can open the door for cleaning the core 

and filter, and where you can get at the wiring for installation 

and service.

RA = Room Air into unit

OA = Outside Air into unit

FA = Fresh Air to inside

EA = Exhaust Air to outside

NOTE

Airstreams always cross in 

the energy-exchange core.

Duct Connections 

as Labeled

Alternate 

Duct Connections

RA

EA

FA

OA

RA

EA

FA

OA

The fresh air inlet should be at least 10’ away from 

chimneys, furnace and water heater exhausts, and 

other sources of carbon monoxide, humidity or other 

contamination. 

Do not locate the fresh air inlet where vehicles may 

be serviced or left idling. 

Never locate the fresh air inlet inside a structure.

Exhaust & Fresh Air Ducts

Between HE3XINV & Outside

Insulation

Ducts connecting the HE3XINV to the outside must be insulated, 

with sealed vapor barrier on both inside and outside of the 

insulation.

The exhaust outlet and fresh air inlet on the outside of the building 

should be at least ten feet apart to avoid cross-contamination. 

Wall caps should be designed to exclude animals and rain.  Wall 

caps should be sized for minimum pressure loss. To keep rain from 

being drawn in, the outside air intake should be large enough to 

keep inlet velocity below 500 feet per minute, (or as dictated by 

local practice).

Outside Wall Caps

FA

RA

EA

OA

OA

EA

Best Practice is to separate OA and EA Wall Caps by 10' or more.

Always insulate 

OA and EA Ducts.

Insulate FA and RA Ducts if 

installed in unconditioned spaces

or for sound attenuation.

Straight ducts at Blower Outlets

is preferred for best performance.

Содержание HE3XINV

Страница 1: ...xhausting of gases through the flue chimney of fuel burning equipment that might be installed in the area affected by this equipment If this unit is exhausting air from a space in which chimney vented...

Страница 2: ...to inside EA Exhaust Air to outside NOTE Airstreams always cross in the energy exchange core Duct Connections as Labeled Alternate Duct Connections RA EA FA OA RA EA FA OA The fresh air inlet should...

Страница 3: ...ive or negative pressure in the building is desired RenewAire heat recovery ventilators can generally operate with a flow imbalance of up to 20 without appreciable loss in heat recovery efficiency How...

Страница 4: ...IN INDOOR 1 5 MODEL HE 3X 20 16 17 UNUSED IN HE 3X MODELS 24 L LISTED N NON LISTED OPTION 4 OTHERS T TR TRANSFORMER WITH ISOLATION RELAY NONE W WHITE PAINT C CUSTOM PAINT X CUSTOM UNIT 1 2 3 4 5 6 7 8...

Страница 5: ...ns and manometers These also can be used to determine when filters should be cleaned or changed Use Static Taps in Doors to Measure Airflow Rates See Cross Core Static Drop in MEASURING AIRFLOW table...

Страница 6: ...locate pressure ports To read SCFM of Fresh Air FA install the high pressure side of your measuring device to the Outside Air OA port and the low pressure side to the Fresh Air FA port To read SCFM of...

Страница 7: ...DISCONNECT SWITCH MOTOR STARTER MOTOR STARTER FUSE IF INSTALLED AT FACTORY JUMPER PROVIDED MOTOR EA FACTORY SETTINGS Overload Relay Trip Settings Motor Nameplate FLA Overload Relay Mode Settings Manu...

Страница 8: ...Operation Call for EA Blower Operation OUT 24VAC Class II RELAY TRANSFORMER AND CIRCUIT BREAKER DISCONNECT SWITCH MOTOR STARTER MOTOR STARTER FUSE IF INSTALLED AT FACTORY 24VAC JUMPER PROVIDED FACTOR...

Страница 9: ...the control terminals of this unit 5 Unit is not equipped to receive analog signals such as 1 10vdc or 4 20mA 6 Unit is not equipped to communicate directly with Building Management Systems such as B...

Страница 10: ...Connect Terminals 2 3 Connect Switch between Terminals 1 4 UNIT INTERNAL CONTROL WIRING SIMPLIFIED A SWITCH OR NON POWERED CONTROL USING UNIT S 24VAC POWER SUPPLY UNIT INTERNAL CONTROL WIRING SIMPLIFI...

Страница 11: ...34772_006 HE3XINVMan_Jan12 indd Revised 01 2012 www renewaire com Page 11 HE3XINV Replacement Parts A CORES B FILTERS C DOOR D DRAW LATCH E DISCONNECT SWITCH F TRANSFORMER G ISOLATION RELAY H OVERLOAD...

Страница 12: ...Blowers every time you change the filters Confirm bearings are still secure to blower shaft It should not be possible to move the blower shaft back and forth along its length Confirm blower wheel is n...

Отзывы: