Figure 14 Offset Chimney
Installation Example
Figure 15 Offset Chimney Through
a Wall Example
Table 6 Through the Wall Installation Dimensions
30
°
Offset Through the
Wall
45
°
Offset Through the
Wall
US and Canada
Canada Only
Minimum required
ceiling height
12'3"
11' 10" if not using the
bottom standoff
10' 6"
10' 1"
if not using the
bottom standoff
Height of the
center of the hole
in the wall
9' 9¼"
9' 4"
if not using the
bottom standoff
8' 9"
8' 3½"
if not using the
bottom standoff
Minimum height of
the hole
53"
35½"
Position of the hole Centered on the chimney coupling of the fireplace or on the
fireplace casing (not on the guillotine bay at the front)
Minimum width of
the hole
18"
These heights assumed that the first elbow is directly on the fireplace as depicted in
Figure 15. If this is not the case, these heights have to be increase by the length of
chimney installed on the fireplace before the first elbow.