RC210

90

68

120

68

RC220-RC265

90

110

120

110

RC270-RC280, 

RC88

100

160

130

160

RCG90-RCG100 155*

200*

185*

200*

Tabell 14pt bold 

Bold på rubriker uppe, allt under ska vara regular.

Allt utom spalten med RC-förteckningar ska vara 

centrerat i våg och lodrätt. RC-spalten ska vara 

vänsterlagd.

Strl på texten varierar beroende på utrymme men 

10pt är standard

www.rotork.com  www.remotecontrol.se

Name

Spec.

DEAD BAND

Mechanical Steps at least 0.2mA

What is DEAD BAND ? 

It’s an area/band where no action occurs due to the actuator input.

If the user inputs 12mA (50%), the actuator is supposed to stop exactly at 50% poaition. The actuator repeats from open 

to close in order to stop at 50% position at this point.

This is what we call hunting, and if the hunting effect repeatedly occurs the motor can be damage. Therefor a dead band 

is set to have some area in order to prevent this from happening.

It’s set to have 0.05mA per gradation. If it is at 1PH when shipped from the factory, it is set to have a 0.2mA dead band. If 

it is at 3PH, on the other hand, it is set to have a 0.3mA dead band.

ex) If it is set to have a 0.2mA dead band, the actuator is positioned between 11.8mA to 12.2mA. 

In case the actuator stops at the position of 12.1mA, the second least movement area will be at 

12.3mA. At this position no action occurs even when there is the input signal.

5

DEAD BAND

6

OTS, CTS Connector

8

OLS, CLS Connector

9

Potentiometer Connector

P3

P1

P2

Color

Resistance

P1

White

LOW

0 ~ 1000Ω

P2

Blue

COM

P3

Black

HIGH

When shipped from the factory and at full close, it is set at 80 ~ 120Ω.

( *Refer to P13 for Potentiometer setting)

Содержание RCEL

Страница 1: ...of the 3 phase wires on the terminal block CAUTION Specifications Input Power 90 230V AC 10 50 60Hz DC 24V AC 24V 10 Input Power must match motor Ratings Command Signal 4 20mA DC Default 0 5VDC 0 10V...

Страница 2: ...S Connector 7 Input Connector 8 OLS CLS Connector 9 Potentiometer Connector 10 DIP Switch for Input Setting 1 No 1 12 Connector 1 11 10 9 8 7 6 5 4 3 2 12 2 DIP SWITCH No 1 2 3 4 5 6 7 8 Name FC FO AF...

Страница 3: ...tor at Full Open Press the SPAN Button CH2 OFF Input and check if the device operates normally 6 REV It is used when the actuator operates in the inverse direction When REV is on and at 4mA the actuat...

Страница 4: ...ppening It s set to have 0 05mA per gradation If it is at 1PH when shipped from the factory it is set to have a 0 2mA dead band If it is at 3PH on the other hand it is set to have a 0 3mA dead band ex...

Страница 5: ...an Button Actuator automatically setting button Delivered from the factory the resistance value of potentiometer may can be changed if the user modifies its limit setting Please make sure to press the...

Страница 6: ...al Mode 1 When you pull the lever located on the side of actuator handle toward the handle the lever stands straight If you turn the handle in that condition the actuator moves 2 If the lever does not...

Страница 7: ...completed replace the top cover and secure it using the six cover screws 9 Apply the power and do a final check to confirm proper operation Main Power must only be applied when the top cover is re ins...

Страница 8: ...t the mechanical limit stop Actuator suddenly stops during operation The over torque switch has tripped Valves torque has increased Valve needs to be checked repaired or replaced or the over torque sw...

Отзывы: