2
Technical data
2.1 Unit data
Series
WSP 80
WSP 110
WSP 140
WSP 180
System
Brine/water
Function
Heating/hot water
Cooling
Optionally passive
Compressor technology
Scroll
Heat pump manager
Smart Control Touch
Temperature operating limit brine
(heat source, heating)
°C
-10 - +25
Temperature operating limit brine
(heat sink, cooling)
°C
+5 - +18
Antifreezing agent
Glycol
Minimal brine concentration
°C
- 13
Min. heat source capacity
kW
5.0
7.0
9.0
15.0
Cooling capacity heat pump
kW
5.0
7.0
9.0
15.0
Inlet temp. Heating water, max.
°C
+60
Passive cooling (source) operating
limit
°C
+5 - +18
Min. inlet temperature, cooling water
°C
+15
Electrical auxiliary heater /
heating capacity
kW
optional/9.0
Domestic hot-water heating
(changeover valve)
optional outdoor
Connection oil / gas boiler
optional outdoor
Heating capacity, ErP
kW
5.0
8.0
9.0
17.0
Heating capacity/COP
1)
for B0/W35
kW/COP
5.7/4.7
7.9/4.8
10.8/4.9
17.2/5.2
Heating capacity/COP
1)
for B0/W55
kW/COP
5.2/2.6
6.9/2.7
9.2/2.8
15.0/2.8
Heating capacity/COP
1)
for W10/W35
kW/COP
7.6/5.8
9.7/6.0
14.1/6.3
22.6/6.5
Heating capacity/COP
1)
for W10/W55
kW/COP
6.6/3.2
8.4/3.2
11.9/3.5
19.2/3.5
Power consumption for B0/W35
4)
kW
1.2
1.7
2.2
3.3
Power consumption for B0/W55
4)
kW
2.0
2.6
3.3
5.4
Power consumption for W10/W35
4)
kW
1.3
1.6
2.2
3.5
Power consumption for W10/W55
4)
kW
2.1
3.2
3.4
5.5
9