Technical data
2.1 Unit data
Series
SKT 261
Operating mode
Design-Wall unit for inverter multisplit out-
door units for cooling and heating
Nominal cooling output
1)
kW
2.6
Nominal heat capacity
2)
kW
2.9
Application area (room volume), approx.
m
3
80
Adjustment range room temperature
°C
+17 to +30
Operating range
°C/r.H.%
+17 to +32 / 35 to 65
Refrigerant
R32
Operating pressure, max.
kPa
4200
Air flow volume per stage
m
3
/h
240/310/420
Sound pressure level per stage
3)
dB (A)
23/33/37
Sound power
dB (A)
53
Power supply
V/Hz
230/1~/50
Enclosure class
IP
X 0
Electrical rated power consumpt., cooling
1)
W
24
Electrical rated power consumpt., heating
2)
W
24
Electrical rated current consumpt., cooling
1)
A
0.11
Electrical rated current consumpt., heating
2)
A
0.11
Refrigerant connection, liquid pipe
Inches (mm)
1/4 (6.35)
Refrigerant connection, suction pipe
Inches (mm)
3/8 (9.52)
Condensate drainage connection
mm
18
Dimensions: Height / width / depth
mm
290/722/187
Weight
kg
7.4
EDP
1641122
1)
Air inlet temperature TK 27 °C / FK 19 °C, outside temperature TK 35 °C / FK 24 °C, max. air volume, 5 m
pipe length in combination with SKT outdoor unit
2)
Air inlet temperature TK 20 °C, outside temperature TK 7 °C / FK 6 °C, max. air volume, 5 m pipe length in
combination with SKT outdoor unit
3)
Distance 1 m free field
9