background image

13 

G

 

The compressor starts a couple of minutes later 
due to the delayed start of the outdoor part. 

8.    During the test run, check all regulating, control and 

safety mechanisms to ensure that they are function-
ing and set properly. 

9.    Check the indoor unit’s control mechanism using 

the functions described in the operating instructions. 

Timer, temperature settings, fan mode and dehu-
midifying mode as well as all other mode settings

 

10.  Measure overheating, outside, inside, outlet and 

evaporation temperatures and enter these values in 
the initial operation log. 

11.  Remove the manometer and reattach all parts that 

were removed 

Make sure that there are seals in the closing caps.

 

G

 

Operation/handling which does not comply with 
these instructions is prohibited!  
In cases of non-compliance, we assume no liability 
and the guarantee becomes null and void.

 

Customer Service and 
Guarantee

 

 

For the guarantee to be valid, the purchaser or his cus-
tomer must completely fill out the "guarantee certificate" 
enclosed with all units and send it back to REMKO GmbH 
& Co. KG

The units are repeatedly tested at the production site to 
ensure  that they are working properly. If a malfunction 
occurs that cannot be eliminated by the operating per-
sonnel, please contact your dealer or contact person. 

Proper use 

The outdoor parts have been designed and fitted exclu-
sively for operation with REMKO indoor units belonging 
to the RKV series. 

The manufacturer assumes no liability for damage re-
sulting from non-compliance with manufacturer specifi-
cations and legal requirements, or if modifications are 
made to the units. 

Only authorised personnel may come into contact with 
the cold cycle. This ensures that refrigerant does not es-
cape into the environment when the unit is being re-
paired. 

Both the refrigerant and the system parts are subject to 
special requirements for disposal. 

Important information about recycling! 

Environment and Recycling 

G

 

The refrigerant in use is a safety refrigerant. This 
means that, should damage occur, the quantities 
released will not cause injury to the respiratory 
systems of people and animals. Do not touch the 
liquid refrigerant as it can freeze the skin!

 

Wiring Diagram 

Connections of the indoor unit RKV-K 

The clamps of the indoor units can have different names 
depending on the type of unit. The clamps of the RKV-K 
unit have the following names: 

RKV-K 

Description 

Outdoor part 

Outer conductor 

Neutral conductor 

Control conductor 

compressor-contactor 

PE 

Protective conductor 

 

Cooling units RKV-K, RKV-W, RKV-T 

Red 

White 

Orange 

Yellow /
green 

Outdoor part 

To the compressor 

Protective conductor 

Power supply 

Indoor unit 

L1 

N

 

PE 

PE 

PE 

Control 
conductor 

Neutral conductor 

Outer conductor 

230 V~, 
50 Hz, 
L1 

PE 

Cooling / Heating units RKV 13 WH, RKV 24 WH 

L1 

Red 

White 

Orange 

Brown 

Black 

Yellow /
green 

To the compressor  
contactor 

To the reverse valve 

To the condenser 
ventilator 

Protective conductor 

Indoor unit 

Temperature 
sensor 

From 
plug P6 

PE 

Power supply 

PE 

230 V~, 
50 Hz, 
L1 

PE 

Outdoor part 

PE 

Neutral conductor 

Outer conductor 

Содержание RKS 510

Страница 1: ...REMKO powerful like a bear REMKO RKS 510 513 524 REMKO RKS 513 H 524 H Combi Air Conditioning Units Edition GB M08 Operation Technology Spare Parts...

Страница 2: ......

Страница 3: ...ration 12 Adding Refrigerant 12 Initial Operation 12 Customer Service and Guarantee 13 Environment and Recycling 13 Wiring Diagram 13 Initial Operation Certification 15 Combi Air Conditioning Units RE...

Страница 4: ...eratures between 15 and 46 C Never open the units housing There may cause an electric shock Protect the connection lines from being damaged for example by animals All REMKO air conditioners are suppli...

Страница 5: ...in your area Troubleshooting This unit has been designed based on state of the art manufacturing methods and it has been tested repeatedly to ensure that it is working properly However should problems...

Страница 6: ...rting current LRA A 23 31 77 31 77 Supplied fuse protection recommended A 16 16 25 16 25 Sound pressure level max dB A 49 49 59 49 59 Width mm 850 850 950 850 950 Depth mm 322 322 417 322 417 Weight k...

Страница 7: ...ng air conditioners high pressure and electrical current can pose hazards Be especially careful when covers are removed The components in the cold cycle can reach tem peratures of more than 70 C Selec...

Страница 8: ...s containing cement or lime Location of installation for the outdoor part The outdoor part must be set up on a surface that is level smooth and solid The outdoor part can either be set up outside or i...

Страница 9: ...escribe installation of the cold cycle and the assembly of the indoor unit and out door part 1 The required cross sections are provided in the Technical Data table 2 Install the indoor unit and connec...

Страница 10: ...ly removed from the system the manometer station valves are closed and the valves of the outdoor part are opened as described in the section Initial Operation Impermeability Test Once all connections...

Страница 11: ...both lines through the rubber protective rings of the fixed connection plate 5 Clamp the lines as shown in the wiring diagram on page 13 6 Place the line securely in the strain relief and reas semble...

Страница 12: ...documented Prior to handover After all components have been connected and checked the system can be put into operation To ensure that the unit is functioning properly a func tional check must be perfo...

Страница 13: ...liability for damage re sulting from non compliance with manufacturer specifi cations and legal requirements or if modifications are made to the units Only authorised personnel may come into contact w...

Страница 14: ...P 1 JP 2 JP 3 JP 4 JP 5 JP 6 JP 7 JP 8 Fuse 3 A 250 V TS 3 Winterregulation P1 Sensor VM C3 brn blu Ventilator blk brn wht blk or wht Legende TS1 terminal strip power supply TS2 terminal strip to indo...

Страница 15: ...ional quantities g Condensation pump Operator Assembly location Name Street Postal code city Telephone Fax Test of cold cycle Result Visual check Assembly of outdoor part and indoor unit R good Q poor...

Страница 16: ...REMKO GmbH Co KG Klima und W rmetechnik D 32791 Lage Im Seelenkamp 12 D 32777 Lage PO Box 1827 Phone 49 5232 606 0 Fax 49 5232 606260...

Отзывы: