REMKO PWW

Connection to water
heating system 

Prior to connection to the heating 
system on-site, it must be en-
sured that the respective capacity 
requirements of the unit can be 
made available at all times.

  Connection of the unit on the 

water side must take place on-
site via suitable pipe fittings and 
shut-off valves in the flow and 
return. 

The use of compensators and 
automatic deculators is recom-
mended!

  The water inlet (flow) is gener-

ally at the “top“.

  The connection side can be 

either on 

right or left.

  The fin heat exchangers must 

be thoroughly vented after 
installation. 

Air cushions in the heat 
exchanger will reduce the 
heating capacity!

  The fin heat exchangers operate 

in counterflow.

Heating medium connection

  See technical data for pipe con-

nection thread sizes.

Water inlet

Water  outlet

Air outlet

Air inlet

NOtE

When tightening the screwed 
connections of the heating 
medium connection, a suitable 
tool must be used to prevent 
the connecting pipes rotating 
in order to avoid damage.

Draining if there is a risk of 
frost

It is not possible to statically drain 
the fin heat exchanger completely. 
The fin heat exchanger can only be 
drained completely using com-
pressed air.

important information 
on frost protection!

To prevent frost damage, anti-frost 
protection must be provided at 
temperatures below 0°C.

Where systems in rooms at risk 
from frost are not used for ex-
tended periods, under no circum-
stances must water be present in 
the heat exchanger.

If this is not possible, a suitable 
antifreeze agent must be added to 
the heating medium (water).

Venting

Draining

Anti-frost thermostat

Pipe fitting

Water inlet

Water outlet

AttENtiON

Frost damage to the fin heat 
exchanger does not fall under 
the warranty!

Содержание PWW 100 Series

Страница 1: ...Edition GB T08 REMKO PWW Warm water heaters Operation Technology Spare Parts...

Страница 2: ......

Страница 3: ...6 Exploded drawing 20 Spare parts list 20 Intended use 21 Customer service and warranty 21 Environmental protection and recycling 21 Ratings tables Characteristics 22 Calculation examples 30 Planning...

Страница 4: ...tion grilles must not be removed or rendered inoperational The units must only be operated within the specified capacity limits and with the approved operating media Observe rating plate The air intak...

Страница 5: ...nce Units with fresh air inlet must be fitted with anti frost protection Heat exchanger copper aluminium The fin heat exchangers consist of copper pipes with pressed on aluminium fins The fin assembly...

Страница 6: ...to a load bearing outside wall 2 The air intake channel and air inlet piece must be fastened to the outside wall locally 3 Circulation fresh air operation via the roof The vertical part of this syste...

Страница 7: ...With the appropriate control units accessory speed selection takes place via Y D switching Motor protection is provided via built in thermal contacts that drop out at a fan motor winding temperature...

Страница 8: ...on thread sizes Water inlet Water outlet Air outlet Air inlet NOTE When tightening the screwed connections of the heating medium connection a suitable tool must be used to prevent the connecting pipes...

Страница 9: ...ction Where there is s risk of frost the entire system must be drained if no suitable antifreeze agent has been added Note The heat exchanger can only be drained completely using compressed air 9 It m...

Страница 10: ...1 Disconnect the electrical con nection of the motor 2 Remove the protection grille with fan from the housing 3 Remove the protection grille from the fan motor 4 Carefully refit the new fan in revers...

Страница 11: ...ofitting is easily possible Air outlet hood HG 4 This air outlet hood serves uniform air distribution in four directions at low mounting heights The air outlet hood is not suitable for mounting hoods...

Страница 12: ...00 1295 690 55 60 Filter box FK with pocket filter insert removable from the side filter class G3 depth 100 mm PWW a in mm b in mm c in mm 30 560 440 400 50 640 515 400 80 800 630 400 100 880 740 400...

Страница 13: ...20 100 840 410 1000 500 20 PWW a in mm b in mm c in mm d in mm 30 520 240 400 20 50 600 310 450 20 80 760 360 650 20 100 840 410 800 20 Flexible pipe SG Flexible conn vibration isolation betw unit and...

Страница 14: ...e final pressure difference is reached the filters must be replaced with filters with the same quality class Accessory installation Anti frost thermostat FS The anti frost thermostat is a precise wate...

Страница 15: ...ction IP 54 Operating time about 150 seconds Maximum ambient temperature 50 C Typ KSH N L1 230V 1 1 2 3 Aderbezeichnung Wiring diagram Stellungsgeber 0 10V Aderbezeichnung 1 2 3 5 N L1 y N L1 230V 1 1...

Страница 16: ...upply and protective conductor terminals main con tactor control switch with the functions Off Setting 1 Setting 2 control fuse indicator light extinguishes on fan faults and or interruption of power...

Страница 17: ...ctions based on the wiring diagrams in compliance with the applicable regulations taking into account local regulations Three phase 400V two speed fan maximum switching capacity 2 5 kW surface mountin...

Страница 18: ...es place via a large sized membrane keyboard In the automatic mode the fan speeds are controlled according to the freely programmable tempera ture difference Day night temperature control in cluding w...

Страница 19: ...ion Weight Control unit V A IP kg 3 EG 400 3 0 54 11 1 5 EG 400 5 2 54 15 6 EG TK TK W2 U2 V2 W1 V1 U1 J N L1 L2 L3 U1 V1 W1 TK TK RT RT N L1 L2 L3 PE J FS FS 12 11 14 N L L Raum thermostat Frostschut...

Страница 20: ...WW 50 EDP No PWW 80 EDP No PWW 100 EDP No 1 Heat exchanger Bg 2 1105211 1105215 1105219 1105223 1a Heat exchanger Bg 3 1105212 1105216 1105220 1105224 1b Heat exchanger Bg 4 1105213 1105217 1105221 11...

Страница 21: ...should be contacted Intended use Disposal of packaging Think of the environment when disposing of the packaging material Our appliances are carefully pa cked for transport and delivered in sturdy card...

Страница 22: ...0 21 1 31 17 4 31 19 0 35 15 8 36 16 7 36 13 6 37 13 8 37 11 7 38 11 5 38 9 3 38 29 9 28 27 5 35 28 2 31 25 5 36 26 4 33 23 5 38 24 5 36 21 4 39 22 9 41 19 4 43 21 1 43 17 4 44 19 0 45 15 8 46 16 7 46...

Страница 23: ...Accessories mounted on pressure side Component Type D Mixed air box MLK 5 Filter box filter clean FK 2 moderate filter clogging FK 7 Warmth channel interim piece per m KA 1 Fresh air inlet grille AG 4...

Страница 24: ...7 34 9 30 28 8 29 31 4 34 25 7 33 27 6 36 21 9 34 22 8 36 19 0 36 18 2 37 15 8 37 52 9 31 45 1 30 49 7 33 42 1 32 46 1 35 38 8 34 42 6 37 35 3 35 38 8 41 32 2 40 34 9 43 28 8 41 31 4 44 25 7 43 27 6 4...

Страница 25: ...x filter clean FK 2 moderate filter clogging FK 7 Warmth channel interim piece per m KA 1 Fresh air inlet grille AG 5 Circulation suction adapter UA 2 Fresh air inlet hood ALH 4 Component Type D Air o...

Страница 26: ...34 49 0 36 52 3 38 44 2 41 46 6 39 39 5 42 40 9 41 33 9 42 35 3 42 28 4 43 85 2 35 72 5 39 79 7 36 67 8 40 74 2 38 63 1 42 68 7 40 58 4 43 63 2 45 53 7 48 57 7 46 49 0 50 52 3 48 44 2 51 46 6 49 39 5...

Страница 27: ...ox filter clean FK 3 moderate filter clogging FK 7 Warmth channel interim piece per m KA 1 Fresh air inlet grille AG 4 Circulation suction adapter UA 2 Fresh air inlet hood ALH 4 Component Type D Air...

Страница 28: ...1 33 74 1 34 65 8 37 65 5 36 58 9 39 56 9 37 50 9 40 48 1 39 43 6 41 126 0 30 110 3 34 117 5 32 102 8 36 108 7 34 95 3 37 100 0 36 88 1 39 91 3 41 80 5 44 82 8 42 73 1 45 74 1 44 65 8 47 65 5 46 58 9...

Страница 29: ...x filter clean FK 3 moderate filter clogging FK 8 Warmth channel interim piece per m KA 1 Fresh air inlet grille AG 4 Circulation suction adapter UA 2 Fresh air inlet hood ALH 4 Component Type D Air o...

Страница 30: ...d Filter box FK 7 Air outlet nozzle AD 9 Total difference 16 Solution from the diagram VL 3400 2400 m3 h The heat outputs shown in the ratingtables are subject to variation as a result of Reduced air...

Страница 31: ...ating For the calculation example this results in Higher speed Air volume ratio Heat output correction factor fQ 0 75 Effective heat output QL 50 1 x 0 75 37 6 kW Lower speed Air volume ratio Heat out...

Страница 32: ...capacity Q of the REMKO heater takes into account the following components 1 Heat requirement QH of room to be heated Calculation according to DIN 4701 and 4108 2 Heat requirement QAL to heat fresh a...

Страница 33: ...nlet temperature at air heater tL2 C Air outlet temperature at air heater t C Air inlet outlet temperature difference at air heater t tL2 tL1 tW C Heating medium inlet outlet temperature difference at...

Страница 34: ...0 2 50 3 50 4 80 2 80 3 80 4 100 2 100 3 100 4 V R R 1 R 1 R R 1 R 1 R 1 R 1 R 1 R 1 R 1 R 1 R R R 1 R 1 R R 1 R 1 R 1 R 1 R 1 R 1 R 1 R 1 We reserve the right to make changes to dimensions and design...

Страница 35: ...ater or pumped hot water up to maximum 130 C Operat press max bar 16 16 16 16 16 16 Weight kg 24 26 27 31 34 36 Series PWW 80 2 PWW 80 3 PWW 80 4 PWW 100 2 PWW 100 3 PWW 100 4 Elec connection V 400 3...

Страница 36: ...is always up to date This has given us the reputation of being more than just a good reliable supplier REMKO a partner that helps solve problems Sales REMKO not only provides an extensive sales netwo...

Отзывы: